| Table 6 | - Heating | Inputs |
|
HEATING INPUT(BTU/HR)* | GAS | SUPPLY | PRESSURE (IN. W.C.) | MANIFOLD PRESSURE (IN. W.C.) |
NUMBER OF |
| Natural | Natural | |
| ORIFICES |
| ||
|
|
|
|
High Stage | Low Stage |
40,000 | 26,000 |
60,000 | 39,000 |
90,000 | 58,500 |
115,000 | 75,000 |
130,000 | 84,500 |
*Cubic ft of natural gas per hour for gas pressures Table 6.2 (b) NPFA 54 / ANSI Z223.1.
| Min | Max | High Stage | Low Stage | ||
2 | 4.0 | 13.0 | 1.4 | - | 2.0 | |
3 | 4.0 | 13.0 | 1.4 | - | 2.0 | |
3 | 4.0 | 13.0 | 1.4 | _ 2.0 | ||
3 | 4.0 | 13.0 | 1.4 | _ 2.0 | ||
3 | 4.0 | 13.0 | 1.4 | _ 2.0 |
of .5 psig (14 IN. W.C.) or less and a pressure drop of .5 IN. W.C. (based on a .60 specific gravity gas). Ref:
|
|
|
|
| Table | 7 - ECM | Wet | Coil Pressure | Drop (IN. | W.C.) |
|
|
|
|
| |
UNIT |
|
|
|
|
|
| STANDARD | CFM (SCFM) |
|
|
|
|
|
| ||
SIZE | 600 | 700 | 800 | 900 | 1000 | 1100 | 1200 | 1300 | 1400 | 1500 | 1600 | 1700 | 1800 | 1900 | 2000 | 2100 |
024 | 0.005 | 0.007 | 0.010 | 0.012 | 0.015 |
|
|
|
|
|
|
|
|
|
|
|
030 |
| 0.007 | 0.010 | 0.012 | 0.015 | 0.018 | 0.021 | 0.024 |
|
|
|
|
|
|
|
|
036 |
|
|
| 0.019 | 0.023 | 0.027 | 0.032 | 0.037 | 0.042 | 0.047 |
|
|
|
|
|
|
042 |
|
|
|
| 0.014 | 0.017 | 0.020 | 0.024 | 0.027 | 0.031 | 0.035 | 0.039 | 0.043 |
|
|
|
O48 |
|
|
|
|
|
| 0.027 | 0.032 | 0.036 | 0.041 | 0.046 | 0.052 | 0.057 | 0.063 | 0.068 |
|
060 |
|
|
|
|
|
|
|
|
| 0.029 | 0.032 | 0.036 | 0.040 | 0.045 | 0.049 | 0.053 |
|
|
|
|
|
| Table 8 - | Filter | Pressure Drop Table (IN. | W.C.) |
|
|
|
|
|
|
| |||
FILTERSIZE |
|
|
|
|
|
|
|
|
| CFM |
|
|
|
|
|
|
|
|
|
in.(mm) | 500 | 600 | 700 | 800 | 900 | 1000 | 1100 | 1200 | 1300 | 1400 | 1500 | 1600 | 1700 | 1800 | 1900 | 2000 | 2100 | 2200 | 2300 |
20X20X1 | 0.05 | 0.07 | 0.08 | 0.1 | 0.12 | 0.13 | 0.14 | 0.15 | ........... |
|
|
|
|
|
|
|
|
| |
(508x508x25) |
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
24X30X1 | .... |
|
|
| 0.05 | 0.6 | 0.07 | 0.07 | 0.08 | 0.09 | 0.1 | ........ |
|
|
|
|
|
|
|
(610x762x25) |
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
24X36X1 | ....... |
|
|
|
|
|
| 0.06 | 0.07 | 0.07 | 0.08 | 0.09 | 0.09 | 0.10 | 0.11 | 0.12 | 0.13 | 0.14 | 0.14 |
(610x914x25) |
|
|
|
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
IMPORTANT: When evaluating the refrigerant charge, an
indicated adjustment to the specified factory charge must always be
very minimal. If a substantial adjustment is indicated, an abnormal
condition exists somewhere in the cooling system, such as
insufficient airflow across either coil or both coils.
REFRIGERANT CHARGE
The amount of refrigerant charge is listed on the unit rating plate
and/or the physical data table. Refer to the Refrigeration Service
Techniques Manual, Refrigerants Section.
NO CHARGE
Check for leak. Use standard evacuating techniques. After
evacuating system, weigh in the specified amount of refrigerant (refer to system rating plate).
LOW CHARGE COOLING
Use Cooling Charging Chart (Fig. 23). Vary refrigerant until the
conditions of the chart are met. Note that charging charts are
different from type normally used. Charts are based on charging
the units to correct subcooling for the various operating conditions.
Accurate pressure gauge and temperature sensing devices are
required. Connect the pressure gauge to the service port on the
suction line. Mount the temperature sensing device on the suction line and insulate it so that the outdoor ambient does not affect the
reading. Indoor air CFM must be within the normal operating range of the unit.
TO USE COOLING CHARGING CHARTS
Take the liquid line temperature and read the manifold pressure gauges.
Refer to the chart to determine what the liquid line temperature
should be. |
|
|
|
|
|
|
NOTE: | If the problem causing | the inaccurate | readings | is a | ||
refrigerant leak, refer to Check for Refrigerant Leaks section. |
| |||||
EMERGENCY | COOLING | / | ||||
HEATING | MODE: |
|
|
| ||
This mode | of operation | is provided | only in the | case | where the | UI |
has failed | or is otherwise | unavailable. | If communications | cannot | be |
established with the UI, the Infinity furnace board will enable the
standard thermostat input terminals to allow simple thermostatic control of the 48XL unit.
For control with a standard thermostat, disconnect the ABCD
connectors from both control boards and using No. 18 AWG
make the connections between the standard thermostat, the furnace
board, and the HP/AC board per Fig. 22. Recommend the use of
interconnecting wire with 105C, 600V, 2/64" insulation.
The Infinity control will respond to cooling and heating demands
with the maximum safe airflow based on gas furnace output and unit cooling capacity.
26