AIR CONDITIONER WITH PURON
REFRIGERATION SECTION
Puron refrigerant operates at
•Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright
position. Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.
•Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.
•Puron systems should be charged with liquid refrigerant. Use a
•Manifold sets should be 750 psig high side and 200 psig low side with 520 psig low side retard.
•Use hoses with 750 psig service pressure rating.
•Leak detectors should be designed to detect HFC refrigerant.
•Puron, as with other HFCs, is only compatible with POE oils.
•Vacuum pumps will not remove moisture from oil.
•Only use
•Do not install a
•POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
•POE oils may cause damage to certain plastics and roofing materials.
•Wrap all filter driers and service valves with wet cloth when brazing.
•A Puron
•Do not use an
•Never open system to atmosphere while it is under a vacuum.
•When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
•Do not vent Puron into the atmosphere.
•Observe all warnings, cautions, and bold text.
•Do not leave Puron suction line driers in place for more than 72 hrs.