Carrier 48XL installation instructions Table lO--Troubleshooting Chart Cont-Gas

Page 35

SYMPTOM

Burners will not ignite

Inadequate heating

Poor flame characteristics

Table lO--Troubleshooting

Chart

Con't-Gas

Furnace

CAUSE

Water in gas line

No power to unit

No 24-v power supply to control circuit

Mis-wired or loose connections

Misaligned spark electrodes

No gas at main burners

Inducer pressure switch not closing

Dirty air filter

Gas input to unit too low

Unit undersized for application

Restricted airflow

Limit switch cycles main burners

Incomplete combustion results in: Aldehyde odors, carbon monoxide, sooting flame, floating flame

Operation

REMEDY

Drain. Install drip leg.

Check power supply fuses, wiring or circuit breaker.

Check transformer.

NOTE: Some transformers have internal over-

current protection that requires a cool-down peri- od to reset.

Check all wiring and wire nut connections

Check flame ignition and sense electrode posi- tioning.

Adjust as necessary.

1.Check gas line for air. Purge as necessary. NOTE: After purging gas line of air, wait at least 5 minutes for any gas to dissipate before attempt- ing to light unit.

2.Check gas valve.

1.Check pressure switch wires, connections,

and tubing. Repair or replace if necessary. Clean or replace filter as necessary

Check gas pressure at manifold match with that on unit nameplate

Replace with proper unit or add additional unit Clean or replace filter. Remove any restriction.

Check rotation of blower, temperature rise of unit. Adjust as necessary.

1.Tighten all screws around burner compartment

2.Cracked heat exchanger. Replace.

3.Unit over-fired. Reduce input (change orifices or adjust gas line or manifold pressure).

4.Check burner alignment.

5.Inspect heat exchanger for blockage. Clean as necessary.

35

Image 35
Contents Installation Inspect Shipment Unit Operation and Safety HazardElectricalshockhazard Identify Unit024-030 IN. MMIN.MM NumberLeft Side View Frontview Rightsideview Front View RETURN-AIR Filters Throwaway CompressorsFurnace Section Burner Orifice No. Qty.Drill SizePlace ClearancesSelect and Install Ductwork See Detail a Carbon Monoxide Poisoning Hazard Install Flue HoodInstall Gas Piping Provide for Condensate DisposalElectrical Shock Hazard Install Electrical ConnectionsFire or Explosion Hazard HIGH-VOLTAGE ConnectionsAccessory Installation Routing Power Leads Into UnitConnecting Ground Lead to Ground Screw Routing Control Power WiresGround Screw Factory Connected OAT Black WiresField Connection RequiredFIRE, EXPLOSION,ELECTRICALSHOCK Hazard Unit Start-Up and TroubleshootingMotor Turns Slowly Verify Motor Winding SectionDUSO0003 DU500095 Status Code 33 Limit Circuit Fault Status Code 22 Abnormal FLAME-PROVING SignalStatus Code 23 Pressure Switch did not Open Status Code 25 Invalid Model Selection or Setup ErrorUtility Interface with Infinity Control Indoor Airflow AdjustmentsUnit Operation Hazard AIR Conditioner Sequence of Operation Cooling OperationHigh Stage Low Stage Amber LED Operation Fault Flash Possible Cause Action CodeRated Heating Sequence of OPERATION-GAS Heat Dehumidification ModeGAS Heat Mode and Adjustments Infinity Controlled LOW Ambient CoolingExample Fire and Unit Damage HazardU.S.A CanadaCheck Burner Flame Check GAS Input Propane GASCheck for Refrigerant Leaks Start-Up AdjustmentsLOW Charge Cooling To USE Cooling Charging ChartsRefrigerant Charge No ChargeFactorywiresprovided Field Connection Required BlackwiresMain Burners Limit SwitchIndoor Fan and Motor Burner IgnitionOutdoor Fan Electrical Controls and WiringPressure Switches Refrigerant Circuit Outdoor Coil, Indoor Coil, and Condensate Drain PanRefrigerant System Temperature Thermistors Pressure Switch PROTECTION-REFRIGERANTControl Fault 230V Line Power Disconnect DetectionOCT Failed Thermistor Default OperationThermistor Sensor Comparison Page Remedy SymptomTable lO--Troubleshooting Chart Cont-Gas Remove and Store in Job File