Carrier 48XL installation instructions Check GAS Input Propane GAS, Check Burner Flame

Page 24

a.129secto. complete one revolution

b. 3600/129 = 27.9

c. 27.9 x 2 = 55.8 ft3 of gas flow/hr. d. 55.8 x 1050 = 58,590 Btuh input.

In this example, the nonfinal input rate for low stage is 58,500 Btu/hr, so the low stage manifold pressure is correctly set.

If the measured low stage rate is too low, increase the manifold pressure to increase rate. If the measured low stage rate is too high, decrease the manifold pressure to decrease rate.

NOTE: Double-check that UI is running on low stage gas heat while clocking the low stage firing rate.

4.Verify proper low stage gas heat temperature rise.

a.Furnace must operate within rise range listed on rating plate.

b.Select "COMFORT" or "EFFICIENCY" mode on UI.

"COMFORT" mode will provide a warmer supply air

temperature, while "EFFICIENCY" will provide lower gas consumption.

c.Make sure access panel is re-installed on the unit.

d. Measure supply and return temperatures as close to the

unit as possible. Subtract the return temperature from

the supply temperature to deternfine rise. Rise should fall within the range specified on the rating plate.

5.Adjust manifold pressure to obtain high stage input rate (See Fig. 19).

a.Set unit to run for 20 minutes in high-stage gas heat

operation using the "INSTALLER CHECKOUT" menu on the UI.

b.Remove regulator adjustment cap from high stage gas valve pressure regulator (See Fig. 19) and turn

high-stage adjusting screw (3/16 or smaller flat-tipped

screwdriver) counterclockwise (out) to decrease rate and clockwise (in) to increase input rate.

NOTE: DO NOT set high stage manifold pressure less than 3.2 IN.W.C. or more than 3.8 IN. W.C. for natural gas. If manifold pressure is outside this range, change main burner orifices.

c. Re-install high stage regulator adjustment cap.

d. Leave manometer connected.

6.Verify natural gas high stage input rate.

a.Turn off all other gas appliances and pilots served by the gas meter.

b.If unit is not running, set unit to run for 20 minutes in high stage gas heat operation using the "INSTALLER

CHECKOUT" menu on the UI.

c.Record number of seconds for gas meter to complete 1 revolution.

d.

Divide

number

of

seconds

in

step c. into

3600

(number

 

of seconds in 1 hour).

 

 

 

 

 

 

 

 

 

 

 

e.

Multiply

 

result

of

step

 

d. by

the number

of

cubic

feet

 

shown for one revolution of test dial to obtain cubic feet

 

of gas flow per hour.

 

 

 

 

 

 

 

 

 

 

 

f.

Multiply

 

result

of

step

 

f. by

Btu heating

value

of

the

gas

 

to obtain total measured input shown in Table 4.

 

 

 

(Consult

the

local

gas

supplier

if the

heating value of

 

gas is not known).

 

 

 

 

 

 

 

 

 

 

 

 

 

EXAMPLE:

 

Assume

a

90,000

 

high

stage

input

unit

is being

installed.

Assume

that

the

 

size

of the dial is 2 cubic

ft.,

one

revolution

takes

84

sec.,

and

the

heating

value

of

the

gas

is

1050

Btu/ft3. Proceed

as

follows:

 

 

 

 

 

 

 

 

 

 

 

 

 

a.

84 sec.

to

complete

 

one

revolution

 

 

 

 

 

 

b.

3600/84

= 42.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

c.

42.9

x

2 = 85.8

ft3

of

gas

flow/hr.

 

 

 

 

 

 

d.

85.8

x

1050

= 90,090

Btuh

 

input.

 

 

 

 

 

 

In this example, the nonfinal input rate for high stage is 90,000 Btu/hr, so the high stage manifold pressure is correctly set.

If the measured high stage rate is too low, increase the manifold pressure to increase rate. If the measured high stage rate is too high, decrease the manifold pressure to decrease rate.

NOTE: Double-check that User Interface is running on high stage gas heat while clocking the low stage firing rate.

7.Verify proper high stage gas heat temperature rise.

a.Furnace must operate within rise range listed on rating plate.

b.Make sure access panel is re-installed on the unit.

c.Measure supply and return temperatures as close to the unit as possible. Subtract the return temperature from the supply temperature to deternfine rise. Rise should fall within the range specified on the rating plate.

NOTE: If the temperature rise is outside the rating plate range, first check:

a. Gas input for low and high stage gas heat operation. b. Derate for altitude, if applicable.

c. Return and supply ducts for excessive restrictions causing static pressures in excess of .5 IN. W.C.

d. Make sure model plug is installed.

8.Final Check

a.Turn off gas to unit

b. Remove manometer from pressure tap.

c.Replace pipe plug on manifold (See Fig. 20). d. Turn on gas to unit.

e.Check for leaks.

CHECK GAS INPUT (PROPANE GAS)

Refer to propane kit installation instructions for properly checking gas input.

NOTE: For installations below 2,000 ft (610 m), refer to the unit rating plate for proper propane conversion kit. For installations

above 2,000 ft (610 m), contact your distributor for proper propane conversion kit.

CHECK BURNER FLAME

With burner access panel removed, observe the unit heating

operation. Watch the burner flames to see if they are light blue and

soft in appearance, and that the flames are approximately the same

for each burner. Propane will have blue flame (See Fig. 21). Refer

to the Maintenance section for information on burner removal.

MANIFOLD

PIPE PLUG

099019

Fig. 20 - Burner Assembly

24

Image 24
Contents Installation Unit Operation and Safety Hazard ElectricalshockhazardIdentify Unit Inspect ShipmentIN. MM IN.MMNumber 024-030Left Side View Frontview Rightsideview Front View Compressors Furnace SectionBurner Orifice No. Qty.Drill Size RETURN-AIR Filters ThrowawayClearances PlaceSelect and Install Ductwork See Detail a Install Flue Hood Install Gas PipingProvide for Condensate Disposal Carbon Monoxide Poisoning HazardInstall Electrical Connections Fire or Explosion HazardHIGH-VOLTAGE Connections Electrical Shock HazardRouting Power Leads Into Unit Connecting Ground Lead to Ground ScrewRouting Control Power Wires Accessory InstallationGround Screw OAT Black Wires Field ConnectionRequired Factory ConnectedUnit Start-Up and Troubleshooting FIRE, EXPLOSION,ELECTRICALSHOCK HazardVerify Motor Winding Section Motor Turns SlowlyDUSO0003 DU500095 Status Code 22 Abnormal FLAME-PROVING Signal Status Code 23 Pressure Switch did not OpenStatus Code 25 Invalid Model Selection or Setup Error Status Code 33 Limit Circuit FaultIndoor Airflow Adjustments Unit Operation HazardAIR Conditioner Sequence of Operation Cooling Operation Utility Interface with Infinity ControlAmber LED Operation Fault Flash Possible Cause Action Code Rated HeatingHigh Stage Low Stage Dehumidification Mode GAS Heat Mode and AdjustmentsInfinity Controlled LOW Ambient Cooling Sequence of OPERATION-GAS HeatFire and Unit Damage Hazard U.S.ACanada ExampleCheck GAS Input Propane GAS Check Burner FlameStart-Up Adjustments Check for Refrigerant LeaksTo USE Cooling Charging Charts Refrigerant ChargeNo Charge LOW Charge CoolingField Connection Required Blackwires FactorywiresprovidedLimit Switch Indoor Fan and MotorBurner Ignition Main BurnersElectrical Controls and Wiring Pressure Switches Refrigerant CircuitOutdoor Coil, Indoor Coil, and Condensate Drain Pan Outdoor FanRefrigerant System Pressure Switch PROTECTION-REFRIGERANT Control Fault230V Line Power Disconnect Detection Temperature ThermistorsFailed Thermistor Default Operation Thermistor Sensor ComparisonOCT Page Symptom RemedyTable lO--Troubleshooting Chart Cont-Gas Remove and Store in Job File