Table 6C Ð Superheat Charging Table, 50SX036
TEMP (F) |
|
|
|
|
|
| EVAP AIR Ð CFM |
|
|
|
|
| |||||
|
|
|
|
|
|
| 1200 |
|
|
|
|
|
| ||||
AIR ENT |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| Evap Air Ð Ewb (F) |
|
|
|
|
| |||||||
| COND |
|
|
|
|
|
|
|
|
|
| ||||||
|
|
| 54 | 56 | 58 | 60 | 62 |
| 64 |
| 66 |
| 68 | 70 | 72 | 74 | 76 |
65 |
| SPH | 21.3 | 21.3 | 21.3 | 21.3 | 22.0 |
| 22.6 |
| 23.3 |
| 23.5 | 23.7 | 23.8 | 23.3 | 22.8 |
70 |
| SPH | 19.3 | 19.3 | 19.3 | 19.3 | 20.2 |
| 21.2 |
| 22.2 |
| 22.3 | 22.5 | 22.6 | 22.0 | 21.5 |
75 |
| SPH | 17.2 | 17.2 | 17.2 | 17.2 | 18.5 |
| 19.7 |
| 21.0 |
| 21.1 | 21.3 | 21.4 | 20.7 | 20.1 |
80 |
| SPH | 13.6 | 13.6 | 13.6 | 13.6 | 15.1 |
| 16.6 |
| 18.0 |
| 18.5 | 18.9 | 19.3 | 19.4 | 19.5 |
85 |
| SPH | 10.1 | 10.1 | 10.1 | 10.1 | 11.7 |
| 13.4 |
| 15.0 |
| 15.8 | 16.5 | 17.3 | 18.1 | 19.0 |
90 |
| SPH | 6.5 | 6.5 | 6.5 | 6.5 | 8.8 |
| 11.2 |
| 13.5 |
| 14.6 | 15.7 | 16.8 | 17.2 | 17.6 |
95 |
| SPH | * | * | * | * | 6.0 |
| 9.0 |
| 12.0 |
| 13.4 | 14.8 | 16.2 | 16.2 | 16.2 |
100 |
| SPH | * | * | * | * | * |
| * |
| 6.0 |
| 8.7 | 11.4 | 14.1 | 14.9 | 15.6 |
105 |
| SPH | * | * | * | * | * |
| * |
| * |
| * | 8.0 | 12.1 | 13.6 | 15.1 |
110 |
| SPH | * | * | * | * | * |
| * |
| * |
| * | * | 10.0 | 11.5 | 13.0 |
115 |
| SPH | * | * | * | * | * |
| * |
| * |
| * | * | 8.0 | 9.5 | 11.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LEGEND | *Do not attempt to charge system under these conditions Ð refrigerant slugging may occur. |
Ewb Ð Entering Wet Bulb |
|
SPH Ð Superheat at Compressor (F) |
|
Table 6D Ð Superheat Charging Table, 50SX042
TEMP (F) |
|
|
|
|
|
| EVAP AIR Ð CFM |
|
|
|
|
| |||||
|
|
|
|
|
|
| 1400 |
|
|
|
|
|
| ||||
AIR ENT |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| Evap Air Ð Ewb (F) |
|
|
|
|
| |||||||
| COND |
|
|
|
|
|
|
|
|
|
| ||||||
|
|
| 54 | 56 | 58 | 60 | 62 |
| 64 |
| 66 |
| 68 | 70 | 72 | 74 | 76 |
65 |
| SPH | 23.9 | 23.9 | 23.9 | 23.9 | 24.4 |
| 24.9 |
| 25.5 |
| 25.8 | 26.1 | 26.5 | 25.6 | 24.7 |
70 |
| SPH | 21.9 | 21.9 | 21.9 | 21.9 | 22.4 |
| 22.9 |
| 23.4 |
| 23.7 | 24.1 | 24.5 | 24.0 | 23.5 |
75 |
| SPH | 19.8 | 19.8 | 19.8 | 19.8 | 20.3 |
| 20.8 |
| 21.3 |
| 21.7 | 22.0 | 22.4 | 22.4 | 22.4 |
80 |
| SPH | 16.3 | 16.3 | 16.3 | 16.3 | 17.9 |
| 19.6 |
| 21.3 |
| 21.5 | 21.7 | 21.8 | 21.8 | 21.8 |
85 |
| SPH | 12.7 | 12.7 | 12.7 | 12.7 | 15.6 |
| 18.4 |
| 21.3 |
| 21.3 | 21.3 | 21.3 | 21.3 | 21.3 |
90 |
| SPH | 9.2 | 9.2 | 9.2 | 9.2 | 12.0 |
| 14.9 |
| 17.8 |
| 18.7 | 19.7 | 20.8 | 20.8 | 20.8 |
95 |
| SPH | 5.6 | 5.6 | 5.6 | 5.6 | 8.5 |
| 11.3 |
| 14.2 |
| 16.2 | 18.2 | 20.2 | 20.2 | 20.2 |
100 |
| SPH | * | * | * | * | * |
| 8.0 |
| 10.6 |
| 13.1 | 15.6 | 18.1 | 18.9 | 19.6 |
105 |
| SPH | * | * | * | * | * |
| * |
| 7.1 |
| 10.1 | 13.1 | 16.1 | 17.6 | 19.1 |
110 |
| SPH | * | * | * | * | * |
| * |
| * |
| 7.0 | 10.5 | 14.0 | 15.5 | 17.0 |
115 |
| SPH | * | * | * | * | * |
| * |
| * |
| * | 8.0 | 12.0 | 13.5 | 15.0 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
LEGEND | *Do not attempt to charge system under these conditions Ð refrigerant slugging may occur. |
Ewb Ð Entering Wet Bulb |
|
SPH Ð Superheat at Compressor (F) |
|
Table 6E Ð Superheat Charging Table, 50SX048
TEMP (F) |
|
|
|
|
|
| EVAP AIR Ð CFM |
|
|
|
|
| |||||
|
|
|
|
|
|
| 1600 |
|
|
|
|
|
| ||||
AIR ENT |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
| Evap Air Ð Ewb (F) |
|
|
|
|
| |||||||
| COND |
|
|
|
|
|
|
|
|
|
| ||||||
|
|
| 54 | 56 | 58 | 60 | 62 |
| 64 |
| 66 |
| 68 | 70 | 72 | 74 | 76 |
65 |
| SPH | 27.2 | 27.2 | 27.2 | 27.2 | 27.0 |
| 26.7 |
| 26.5 |
| 26.0 | 25.6 | 25.1 | 24.5 | 24.0 |
70 |
| SPH | 25.0 | 25.0 | 25.0 | 25.0 | 24.8 |
| 24.6 |
| 24.5 |
| 24.5 | 24.5 | 24.6 | 23.8 | 23.1 |
75 |
| SPH | 22.8 | 22.8 | 22.8 | 22.8 | 22.7 |
| 22.5 |
| 22.4 |
| 22.9 | 23.5 | 24.0 | 23.1 | 22.2 |
80 |
| SPH | 20.6 | 20.6 | 20.6 | 20.6 | 20.5 |
| 20.4 |
| 20.3 |
| 21.4 | 22.4 | 23.5 | 22.4 | 21.4 |
85 |
| SPH | 18.3 | 18.3 | 18.3 | 18.3 | 18.3 |
| 18.3 |
| 18.3 |
| 19.8 | 21.4 | 22.9 | 21.8 | 20.6 |
90 |
| SPH | 13.3 | 13.3 | 13.3 | 13.3 | 14.2 |
| 15.2 |
| 16.3 |
| 17.8 | 19.3 | 20.9 | 20.4 | 19.9 |
95 |
| SPH | 8.2 | 8.2 | 8.2 | 8.2 | 10.2 |
| 12.2 |
| 14.2 |
| 15.7 | 17.3 | 18.8 | 19.0 | 19.2 |
100 |
| SPH | * | * | * | * | 6.3 |
| 8.4 |
| 10.6 |
| 12.9 | 15.2 | 17.5 | 18.1 | 18.7 |
105 |
| SPH | * | * | * | * | * |
| * |
| 7.1 |
| 10.1 | 13.1 | 16.1 | 17.1 | 18.2 |
110 |
| SPH | * | * | * | * | * |
| * |
| * |
| 7.1 | 10.5 | 14.0 | 15.3 | 16.6 |
115 |
| SPH | * | * | * | * | * |
| * |
| * |
| * | 8.0 | 12.0 | 13.5 | 15.0 |
LEGEND | *Do not attempt to charge system under these conditions Ð refrigerant slugging may occur. |
Ewb Ð Entering Wet Bulb |
|
SPH Ð Superheat at Compressor (F) |
|
32