REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm) |
| ||
Unit Top | . . 14 (356) | ||
Duct Side of Unit | . . . . 2 (51) | ||
Side Opposite Ducts | . . 14 (356) | ||
Bottom of Unit | . . . . . . 0 | ||
Vertical Discharge First 12 in. (305) of Supply Duct | . . . . 1 (25) | ||
NECESSARY REQUIRED CLEARANCES Ð in. (mm) |
|
| |
Between Units, Control Box Side | . . 42 (1067) | ||
Unit and Ungrounded Surfaces, Control Box Side | . . 36 (914) | ||
Unit and Block or Concrete Walls and Other Grounded |
| ||
Surfaces, Control Box Side | . . 42 (1067) | ||
REQUIRED CLEARANCES FOR SERVICING Ð in. (mm) |
|
| |
Evaporator Coil Access Side | . . 30 (762) | ||
Control Box Access Side | . . 30 (762) | ||
(Except for Necessary Requirements) |
| ||
Unit Top | . . 36 (914) | ||
Side Opposite Ducts | . . 30 (762) |
UNIT |
|
|
| CENTER OF GRAVITY (in./mm) | ||||
50SS |
|
| X |
|
| Y |
| Z |
048 |
|
| 21.9/555 |
| 19.6/498 |
| 13.4/341 | |
060 |
|
| 22.2/565 |
| 19.8/503 |
| 13.4/340 | |
|
|
|
|
|
|
|
|
|
|
|
|
| LEGEND |
|
|
| |
CG | Ð | Center of Gravity |
| NEC | Ð | National Electrical Code | ||
COND | Ð | Condenser |
| REQ'D | Ð | Required | ||
MAT'L | Ð | Material |
|
|
|
|
|
NOTES:
1. | Clearances must be maintained to prevent recirculation of air from |
| charge. |
2. | Dimensions in ( ) are in millimeters. |
UNIT | ELECTRICAL |
| UNIT WT |
| CORNER WT (Lb/Kg) |
| ||
50SS | CHARACTERISTICS | Lb |
| Kg | A | B | C | D |
|
|
|
|
|
|
|
|
|
048 | 332 |
| 151 | 82/37 | 68/31 | 131/60 | 51/23 | |
060 | 359 |
| 163 | 65/30 | 99/45 | 120/55 | 75/34 |
Fig. 4 Ð Dimensions; Units 50SS048,060 Without Base Rail