Carrier 50SX024-060, 50SS018-060 owner manual Dimensions Units 50SS048,060 Without Base Rail

Page 4

REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm)

 

Unit Top

. . 14 (356)

Duct Side of Unit

. . . . 2 (51)

Side Opposite Ducts

. . 14 (356)

Bottom of Unit

. . . . . . 0

Vertical Discharge First 12 in. (305) of Supply Duct

. . . . 1 (25)

NECESSARY REQUIRED CLEARANCES Ð in. (mm)

 

 

Between Units, Control Box Side

. . 42 (1067)

Unit and Ungrounded Surfaces, Control Box Side

. . 36 (914)

Unit and Block or Concrete Walls and Other Grounded

 

Surfaces, Control Box Side

. . 42 (1067)

REQUIRED CLEARANCES FOR SERVICING Ð in. (mm)

 

 

Evaporator Coil Access Side

. . 30 (762)

Control Box Access Side

. . 30 (762)

(Except for Necessary Requirements)

 

Unit Top

. . 36 (914)

Side Opposite Ducts

. . 30 (762)

UNIT

 

 

 

CENTER OF GRAVITY (in./mm)

50SS

 

 

X

 

 

Y

 

Z

048

 

 

21.9/555

 

19.6/498

 

13.4/341

060

 

 

22.2/565

 

19.8/503

 

13.4/340

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

 

 

CG

Ð

Center of Gravity

 

NEC

Ð

National Electrical Code

COND

Ð

Condenser

 

REQ'D

Ð

Required

MAT'L

Ð

Material

 

 

 

 

 

NOTES:

1.

Clearances must be maintained to prevent recirculation of air from outdoor-fan dis-

 

charge.

2.

Dimensions in ( ) are in millimeters.

UNIT

ELECTRICAL

 

UNIT WT

 

CORNER WT (Lb/Kg)

 

50SS

CHARACTERISTICS

Lb

 

Kg

A

B

C

D

 

 

 

 

 

 

 

 

 

048

208/230-1-60, 208/230-3-60, 460-3-60

332

 

151

82/37

68/31

131/60

51/23

060

208/230-1-60, 208/230-3-60, 460-3-60

359

 

163

65/30

99/45

120/55

75/34

Fig. 4 Ð Dimensions; Units 50SS048,060 Without Base Rail

4

Image 4
Contents Contents Safety ConsiderationsUnit Dimensions Units 50SS018-042 with Optional Base Rail Dimensions Units 50SS048,060 Without Base Rail Dimensions Units 50SS048,060 With Optional Base Rail Dimensions Units 50SX024-036 Without Base Rail Dimensions Units 50SX024-036 With Optional Base Rail Dimensions Units 50SX042-060 Without Base Rail Characteristics Cond ÐMatl Unit Electrical Unit WTDimensions Units 50SX042-060 With Optional Base Rail Corner WT Lb/Kg 50SX ``A Part NumberCurb Check Equipment Receiving and InstallationProvide Unit Support Suggested Rigging for Units Without Base Rail Physical Data Ð Unit 50SS Physical Data Ð Unit 50SXArea Not To Be Drilled SizeEvaporator Coil Access Panel Indoor Blower Access Panel Field-Fabricated Duct Cover Provide for Condensate Disposal Filler Bracket and Blower ShelfInstall Electrical Connections Condensate TrapÐ Electrical Data Ð 50SS Units Ð Electrical Data Ð 50SX Units Typical Duct Panel Knockouts ICM CTDIFO PRE-START-UP TranStart-Up Cooling Section and Make Adjustments START-UPÐ Superheat Charging Table, 50SS018 Ð Superheat Charging Table, 50SS024Temp F Evap AIR Ð CFM AIR ENTÐ Superheat Charging Table, 50SS030 Ð Superheat Charging Table, 50SS036Ð Superheat Charging Table, 50SS042 10001600 Ð Superheat Charging Table, 50SX030 Ð Superheat Charging Table, 50SX0241995 Ð Superheat Charging Table, 50SX036 Ð Superheat Charging Table, 50SX042Ð Superheat Charging Table, 50SX048 1200Required Suction-Tube Temperature F Ð Superheat Charging Table, 50SX060Superheat Temp FTerminal Mode FAN Cooling HeatingOption Description Sequence of Operation Ð STD NON-ICM Units Unit Motor 460 V Horizontal Discharge Size SpeedUnit Motor AIR 460 Volt Horizontal Discharge Unit Motor AIR 460 Volt Vertical Discharge Size Speed Delivery048² Unit 50SX FAN only CoolingWet Coil Pressure Drop Accessory Electric Heater Pressure Drop in. wgFilter Pressure Drop in. wg Maintenance Air FilterUnit Top Removal Evaporator Blower and MotorCondenser Coil, Evaporator Coil, and Conden Condenser FanTroubleshooting Cooling Chart Symptom Cause RemedyTroubleshooting Cooling Chart Page Page Packaged Service Training Page Preliminary Information Remove and Store in Job FileIII. START-UP