Carrier 50SX024-060, 50SS018-060 owner manual Ð Electrical Data Ð 50SS Units

Page 22

Table 4A Ð Electrical Data Ð 50SS Units

 

 

 

 

 

 

OUTDOOR-

INDOOR-

 

 

AWG 60C

 

UNIT SIZE

 

VOLTAGE RANGE

COMPRESSOR

FAN

FAN

POWER SUPPLY

MAX WIRE

V-PH-Hz

MIN WIRE

50SS

 

 

 

 

MOTOR

MOTOR

 

 

LENGTH (ft)

 

 

 

 

 

 

 

SIZE

 

 

Min

Max

RLA

LRA

FLA

FLA

MCA

MOCP*

 

 

 

 

 

018

208/230-1-60

187

253

8.3

45.0

0.7

1.8

12.0

15

14

75

024

208/230-1-60

187

253

12.4

61.0

0.7

2.0

18.2

30

12

80

030

208/230-1-60

187

253

14.4

82.0

1.4

2.3

21.8

30

10

100

208/230-3-60

187

253

9.4

65.5

1.4

2.3

15.5

25

12

80

 

 

208/230-1-60

187

253

18.0

96.0

1.4

2.8

26.7

40

10

90

036

208/230-3-60

187

253

11.7

75.0

1.4

2.8

18.8

30

12

65

 

460-3-60

414

506

5.6

40.0

0.8

1.4

9.2

10

14

100

 

208/230-1-60

187

253

20.4

104.0

1.4

4.0

30.9

50

8

100

042

208/230-3-60

187

253

14.0

91.0

1.4

4.0

22.9

35

10

85

 

460-3-60

414

506

6.4

42.0

0.8

2.0

10.8

15

14

100

 

208/230-1-60²

187

253

21.8

124.0

2.1

5.0

40.1

60

6

100

 

208/230-1-60**

187

253

26.4

129.0

2.1

5.0

40.1

60

6

100

048

208/230-3-60²

187

253

12.8

93.0

2.1

5.0

23.1

35

10

75

208/230-3-60**

187

253

15.0

99.0

2.1

5.0

25.9

40

10

75

 

 

460-3-60²

414

506

16.0

125.0

2.1

6.8

33.0

40

8

90

 

460-3-60**

414

506

19.3

123.0

2.1

6.8

33.0

50

8

90

 

208/230-1-60²

187

253

28.9

165.0

2.1

6.8

49.0

60

6

100

 

208/230-1-60**

187

253

32.1

169.0

2.1

6.8

49.0

60

6

100

060

208/230-3-60²

187

253

6.4

46.5

1.1

2.3

11.4

15

14

100

208/230-3-60**

187

253

8.2

49.5

1.1

2.3

13.7

20

14

100

 

 

460-3-60²

414

506

8.0

66.5

1.1

3.2

16.8

20

12

100

 

460-3-60**

414

506

10.0

62.0

1.1

3.2

16.8

25

12

100

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

AWG

Ð American Wire Gage

BRKR

Ð Breaker

CUL

Ð Canadian Underwriters' Laboratories

FLA

Ð Full Load Amps

HACR

Ð Heating, Air Conditioning and

 

Refrigeration

LRA

Ð Locked Rotor Amps

MCA

Ð Minimum Circuit Amps

MOCP Ð Maximum Overcurrent Protection

NEC

Ð National Electrical Code

RLA

Ð Rated Load Amps

*Fuse or HACR Breaker. ²Carrier Scroll Compressor. **Copeland Scroll Compressor.

NOTES:

1.In compliance with NEC requirements for multimotor and combi- nation load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. The CUL units may be fuse or circuit breaker.

2.Minimum wire size is based on 60 C copper wire. If other than 60 C wire is used, or if length exceeds wire length in table, de- termine size from NEC.

3.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply volt- age is greater than 2%. Use the following formula to determine the percentage of voltage imbalance.

% Voltage Imbalance

EXAMPLE: Supply voltage is 460-3-60.

AB = 452 v

BC = 464 v

AC = 455 v

Average Voltage =

452 + 464 + 455

3

 

 

 

 

 

=

1371

 

 

 

 

3

 

=

457

Determine maximum deviation from average voltage.

(AB) 457 ± 452 = 5 v

 

 

 

 

(BC) 464 ± 457 = 7 v

 

 

 

 

(AC) 457 ± 455 = 2 v

 

 

 

 

Maximum deviation is 7 v.

 

 

 

 

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

 

7

 

 

457

 

= 1.53%

 

 

 

 

 

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

max voltage deviation from average voltage

= 100 x

average voltage

22

Image 22
Contents Contents Safety ConsiderationsUnit Dimensions Units 50SS018-042 with Optional Base Rail Dimensions Units 50SS048,060 Without Base Rail Dimensions Units 50SS048,060 With Optional Base Rail Dimensions Units 50SX024-036 Without Base Rail Dimensions Units 50SX024-036 With Optional Base Rail Dimensions Units 50SX042-060 Without Base Rail Matl CharacteristicsCond Ð Unit Electrical Unit WTDimensions Units 50SX042-060 With Optional Base Rail Corner WT Lb/Kg 50SX ``A Part NumberCurb Check Equipment Receiving and InstallationProvide Unit Support Suggested Rigging for Units Without Base Rail Physical Data Ð Unit 50SS Physical Data Ð Unit 50SXArea Not To Be Drilled SizeEvaporator Coil Access Panel Indoor Blower Access Panel Field-Fabricated Duct Cover Provide for Condensate Disposal Filler Bracket and Blower ShelfInstall Electrical Connections Condensate TrapÐ Electrical Data Ð 50SS Units Ð Electrical Data Ð 50SX Units Typical Duct Panel Knockouts ICM CTDIFO PRE-START-UP TranStart-Up Cooling Section and Make Adjustments START-UPTemp F Evap AIR Ð CFM Ð Superheat Charging Table, 50SS018Ð Superheat Charging Table, 50SS024 AIR ENTÐ Superheat Charging Table, 50SS042 Ð Superheat Charging Table, 50SS030Ð Superheat Charging Table, 50SS036 10001600 Ð Superheat Charging Table, 50SX030 Ð Superheat Charging Table, 50SX0241995 Ð Superheat Charging Table, 50SX048 Ð Superheat Charging Table, 50SX036Ð Superheat Charging Table, 50SX042 1200Superheat Required Suction-Tube Temperature FÐ Superheat Charging Table, 50SX060 Temp FTerminal Mode FAN Cooling HeatingOption Description Sequence of Operation Ð STD NON-ICM Units Unit Motor 460 V Horizontal Discharge Size SpeedUnit Motor AIR 460 Volt Horizontal Discharge 048² Unit Motor AIR 460 Volt Vertical Discharge SizeSpeed Delivery Unit 50SX FAN only CoolingWet Coil Pressure Drop Accessory Electric Heater Pressure Drop in. wgFilter Pressure Drop in. wg Unit Top Removal MaintenanceAir Filter Evaporator Blower and MotorCondenser Coil, Evaporator Coil, and Conden Condenser FanTroubleshooting Cooling Chart Symptom Cause RemedyTroubleshooting Cooling Chart Page Page Packaged Service Training Page Preliminary Information Remove and Store in Job FileIII. START-UP