REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm)
Unit Top | . 14 (356) | |
Duct Side of Unit | . . 2 (51) | |
Side Opposite Ducts | . 14 (356) | |
Bottom of Unit | . . . . . 0 | |
Vertical Discharge First 12 in. (305) of Supply Duct | . . 1 (25) | |
NECESSARY REQUIRED CLEARANCES Ð in. (mm) |
|
|
Between Units, Control Box Side | 42 (1067) | |
Unit and Ungrounded Surfaces, Control Box Side | . 36 (914) | |
Unit and Block or Concrete Walls and Other Grounded |
| |
Surfaces, Control Box Side | 42 (1067) |
REQUIRED CLEARANCES FOR SERVICING Ð in. (mm)
Evaporator Coil Access Side . . . . . . . . . . . . . . . . . . . . . . . 30 (762) Control Box Access Side . . . . . . . . . . . . . . . . . . . . . . . . . 30 (762)
(Except for Necessary Requirements)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 (914) Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 (762)
UNIT |
|
|
| CENTER OF GRAVITY (in./mm) | ||||
50SS |
|
| X |
|
| Y |
| Z |
048 |
|
| 21.7/550 |
| 19.7/501 |
| 15.7/400 | |
060 |
|
| 22.0/560 |
| 19.9/506 |
| 15.7/399 | |
|
|
|
|
|
|
|
|
|
|
|
|
| LEGEND |
|
|
| |
CG | Ð | Center of Gravity |
| NEC | Ð | National Electrical Code | ||
COND | Ð | Condenser |
| REQ'D | Ð | Required | ||
MAT'L | Ð | Material |
|
|
|
|
|
NOTES:
1.Clearances must be maintained to prevent recirculation of air from
2. Dimensions in ( ) are in millimeters.
UNIT | ELECTRICAL | UNIT WT |
| CORNER WT (Lb/Kg) |
| |||
50SS | CHARACTERISTICS | Lb | Kg | A | B | C |
| D |
|
|
|
|
|
|
|
|
|
048 | 352 | 160 | 87/40 | 73/33 | 136/62 |
| 56/25 | |
060 | 379 | 172 | 70/32 | 104/47 | 125/57 |
| 80/36 |
Fig. 5 Ð Dimensions; Units 50SS048,060 With Optional Base Rail
5