Carrier 50SS018-060, 50SX024-060 owner manual Troubleshooting Cooling Chart

Page 43

TROUBLESHOOTING COOLING CHART (cont)

SYMPTOM

CAUSE

REMEDY

Integrated control motor

Blower wheel not secured to shaft.

Properly tighten blower wheel to shaft.

(units 50SX048 208/230 v

 

 

Insufficient voltage at motor

Determine cause and correct.

and 50SX060)

 

 

IFM does not run.

Power connectors not properly seated

Connectors should snap easily; do not force.

Integrated control motor (units

Motor programmed with a delay pro®le

Allow a few minutes for motor to shut off.

50SX048 208/230 v

 

 

With thermostat in OFF the voltage on

If measured voltage is more than 1¤2, the ther-

and 50SX060)

G,Y1,Y/Y2,W with respect to common,

mostat is incompatible with motor. If voltage is

IFM runs when it should be off.

should be less than 1¤2 of actual low

less than 1¤2, the motor has failed.

 

voltage supply

 

Integrated control motor (units

Water dripping into motor

Verify proper drip loops in connector wires.

50SX048 208/230 v

 

 

Connectors not ®rmly seated

Gently pull wires individually to be sure they

and 50SX060)

 

are crimped into the housing.

IFM operation is intermittent.

 

 

 

IFM Ð Indoor (Evaporator) Fan Motor

 

 

43

Image 43
Contents Safety Considerations ContentsUnit Dimensions Units 50SS018-042 with Optional Base Rail Dimensions Units 50SS048,060 Without Base Rail Dimensions Units 50SS048,060 With Optional Base Rail Dimensions Units 50SX024-036 Without Base Rail Dimensions Units 50SX024-036 With Optional Base Rail Dimensions Units 50SX042-060 Without Base Rail Unit Electrical Unit WT CharacteristicsCond Ð MatlDimensions Units 50SX042-060 With Optional Base Rail Corner WT Lb/Kg 50SX ``A Part NumberCurb Check Equipment Receiving and InstallationProvide Unit Support Suggested Rigging for Units Without Base Rail Physical Data Ð Unit 50SX Physical Data Ð Unit 50SSSize Area Not To Be DrilledEvaporator Coil Access Panel Indoor Blower Access Panel Field-Fabricated Duct Cover Filler Bracket and Blower Shelf Provide for Condensate DisposalCondensate Trap Install Electrical ConnectionsÐ Electrical Data Ð 50SS Units Ð Electrical Data Ð 50SX Units Typical Duct Panel Knockouts ICM CTDIFO Tran PRE-START-UPSTART-UP Start-Up Cooling Section and Make AdjustmentsAIR ENT Ð Superheat Charging Table, 50SS018Ð Superheat Charging Table, 50SS024 Temp F Evap AIR Ð CFM1000 Ð Superheat Charging Table, 50SS030Ð Superheat Charging Table, 50SS036 Ð Superheat Charging Table, 50SS0421600 Ð Superheat Charging Table, 50SX030 Ð Superheat Charging Table, 50SX0241995 1200 Ð Superheat Charging Table, 50SX036Ð Superheat Charging Table, 50SX042 Ð Superheat Charging Table, 50SX048Temp F Required Suction-Tube Temperature FÐ Superheat Charging Table, 50SX060 SuperheatTerminal Mode FAN Cooling HeatingOption Description Sequence of Operation Ð STD NON-ICM Units Size Speed Unit Motor 460 V Horizontal DischargeUnit Motor AIR 460 Volt Horizontal Discharge Unit 50SX FAN only Cooling Unit Motor AIR 460 Volt Vertical Discharge SizeSpeed Delivery 048²Wet Coil Pressure Drop Accessory Electric Heater Pressure Drop in. wgFilter Pressure Drop in. wg Evaporator Blower and Motor MaintenanceAir Filter Unit Top RemovalCondenser Fan Condenser Coil, Evaporator Coil, and CondenSymptom Cause Remedy Troubleshooting Cooling ChartTroubleshooting Cooling Chart Page Page Packaged Service Training Page Preliminary Information Remove and Store in Job FileIII. START-UP