REQUIRED CLEARANCES TO COMBUSTIBLE MATERIAL Ð in. (mm)
Unit Top . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 (356) Duct Side of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 (51) Side Opposite Ducts . . . . . . . . . . . . . . . . . . . . . . . . 14 (356) Bottom of Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 Vertical Discharge First 12 in. (305) of Supply Duct . . . . . . . 1 (25)
NECESSARY REQUIRED CLEARANCES Ð in. (mm)
Between Units, Control Box Side . . . . . . . . . . . . . . . . 42 (1067) Unit and Ungrounded Surfaces, Control Box Side . . . . . . 36 (914) Unit and Block or Concrete Walls and Other Grounded
Surfaces, Control Box Side . . . . . . . . . . . . . . . . . . . 42 (1067)
REQUIRED CLEARANCES FOR SERVICING Ð in. (mm) |
|
Evaporator Coil Access Side | |
Control Box Access Side | . 30 (762) |
(Except for Necessary Requirements) |
|
Unit Top | . 36 (914) |
Side Opposite Ducts | . 30 (762) |
NOTES:
1.Clearances must be maintained to prevent recirculation of air from
2. Dimensions in ( | ) are in millimeters. |
| |||
|
|
|
|
|
|
| UNIT |
| CENTER OF GRAVITY (in./mm) | ||
| 50SX |
| X | Y | Z |
| 024 |
| 21.5/546 | 20.8/528 | 15.0/380 |
030 |
| 21.7/550 | 20.7/527 | 15.0/380 | |
| 036 |
| 20.6/524 | 20.1/510 | 15.0/380 |
|
|
| LEGEND |
|
|
CG | Ð Center of Gravity | NEC | Ð | National Electrical Code | |
COND | Ð | Condenser | REQ'D | Ð | Required |
MAT'L | Ð | Material |
|
|
|
UNIT | ELECTRICAL |
| UNIT WT |
| CORNER WT (Lb/Kg) |
| ||
50SX | CHARACTERISTICS | Lb |
| Kg | A | B | C | D |
024 | 290 |
| 132 | 72/33 | 67/30 | 104/47 | 47/21 | |
030 | 293 |
| 133 | 71/32 | 69/31 | 105/48 | 48/22 | |
036 | 311 |
| 142 | 85/39 | 59/27 | 117/53 | 50/23 |
Fig. 7 Ð Dimensions; Units 50SX024-036 With Optional Base Rail
7