defrost), the defrost relay is energized and defrost begins. The factory setting is 60 minutes. However, if frost accumulation is easily cleared, the optimum efficiency setting is 90 minutes.

Outdoor Unit Defrost Control Board

Defrost Control Timing Pins

Each timing pin selection provides a different accumulated compressor run time period for one defrost cycle. This time period must occur before a defrost cycle is initiated. The defrost interval can be adjusted to 30 (/T1), 60 (T2), or 90 (T3) minutes. The defrost timing jumper is factory-installed to provided a 90-minute defrost interval. If the timing selector jumper is not in place the control defaults to a 90-minute defrost interval. The maximum defrost period is 14 minutes and cannot be adjusted.

A TEST option is provided for troubleshooting. The

TEST mode may be started any time the unit is in the heating mode and the defrost thermostat is closed or jumpered. If the jumper is in the TEST position at power- up, the control will ignore the test pins. When the jumper is placed across the TEST pins for 2 seconds, the control will enter the defrost mode. If the jumper is removed before an additional 5 second period has elapsed ( 7 seconds total), the unit will remain in defrost mode until the defrost thermostat opens or 14 minutes have passed. If the jumper is not removed until after the additional 5 second period has elapsed, the defrost will terminate and the test option will not function again until the jumper is removed and re-applied.

Compressor Delay

The defrost board has a field-selectable function to reduce occasional sounds that may occur while the unit is cycling in and out of the defrost mode. The compressor will be cycled "off" for 30 seconds going in and out of the defrost mode when the compressor delay jumper is

removed.

NOTE: The 30 second "off" cycle is not functional when jumpering the TEST pins.

Time Delay

The timed-off delay is 5 minutes long. The delay help to protect the compressor from short-cycling in case the power to the unit is interrupted or a pressure switch opens. The delay is bypassed by placing the timer select jumper across the TEST pins for 0.5 seconds.

Pressure Switch Circuit

The defrost control incorporates 2 pressure switch circuits. The optional high pressure switch connects to the boards HI PS terminals. The low pressure switch is factory installed.

During a single demand cycle, the defrost control will lock out the unit after the fifth time that the circuit is interrupted by any pressure switch wired to the control board. In addition, the diagnostic LEDs will indicate a locked-out pressure switch after the fifth occurrence of an open pressure switch. The unit will remain locked out until power to the board is interrupted, then re-established or until the jumper is applied to the TEST pins for 0.5 seconds.

NOTE: The defrost control board ignores input from the

low-pressure switch terminals as follows:

!During the TEST mode,

!During the defrost cycle,

!During the 90 second start-up period,

!and for the first 90 seconds each time the reversing valve switches heat/cool modes. If the TEST pins are jumpered and the 5 minute delay is being by- passed, the LO PS terminal signal is not ignored during the 90 second start-up period.

Diagnostic LEDS

The defrost board uses 2 LEDs for diagnostics. The LEDs flash a specific sequence according to the condition.

Defrost Control board Diagnostic LED

Mode

Green LED (DS2)

Red LED (DS1)

No power to control

OFF

OFF

Normal operation/

Simultaneous Slow FLASH

power to control

 

 

Anti-short cycle

Alternating Slow FLASH

lockout

 

 

Low pressure switch

OFF

Slow FLASH

fault (Optional)

 

 

Low pressure switch

OFF

ON

lockout (Optional)

 

 

High pressure switch

Slow FLASH

OFF

fault (Optional)

 

 

High pressure Switch

ON

OFF

lockout (Optional)

 

 

100402-07

Issue 0733

Page 8 of 18

Image 8
Contents Table of Contents Outdoor Section Unit Location & InstallationInstall on a Solid, Level Mounting Pad Do Locate the Unit Do not Locate the UnitInstallation of Line Sets Recommended Liquid & Vapor Tube DiametersLeak Check Evacuating And Charging InstructionsOpening Service Valves Install Electrical AccessoriesControl Wiring Electrical ConnectionsStart-Up Procedure Adjusting ChargeRefrigeration Charge Adjustment Emergency Heat heating heat pumpSystem Operation Time Delay Pressure Switch CircuitDiagnostic Leds Defrost Control board Diagnostic LEDSingle Phase Wiring Diagram 3 Phase Wiring Diagram Required Superheat for 2HP13 B,L24P-1A Heating Mode Pressures 2HP13B,L24P-1ARequired Superheat for 2HP13 B,L18P-1A Heating Mode Pressures 2HP13B,L30P-1A Heating Mode Pressures 2HP13B,L36P-1ARequired Superheat for 2HP13 B,L30P-1A Required Superheat for 2HP13 B,L36P-1AHeating Mode Pressures 2HP13B,L42P-1A Heating Mode Pressures 2HP13B,L48P-1ARequired Superheat for 2HP13 B,L42P-1A Required Superheat for 2HP13 B,L48P-1AHeating Mode Pressures 2HP13B,L60P-1A Required Superheat for 2HP13 B,L60P-1ACase of extended power outage Temperature Setting LeversFan Switch System SwitchRegular Maintenance Requirements Important System InformationAir Filter Indoor CoilThese Warranties Apply only Company will not be Responsible forIssue

2HP13 specifications

Ducane, a well-respected name in the HVAC industry, offers a range of innovative heating, ventilation, and air conditioning solutions. One standout model in their lineup is the Ducane 2HP13, a 13 SEER central air conditioning unit that combines efficiency, reliability, and advanced technology to create comfortable indoor climates.

One of the main features of the Ducane 2HP13 is its efficient 13 SEER rating, which stands for Seasonal Energy Efficiency Ratio. This rating indicates that the unit consumes less energy compared to standard models, resulting in lower utility bills and a reduced environmental footprint. The 2HP13 is built for both cooling and heating applications, making it a versatile addition to any home or commercial space.

The Ducane 2HP13 utilizes a durable, all-aluminum coil that offers superior heat transfer capabilities and corrosion resistance. This enhances the unit's efficiency and longevity, ensuring that it continues to perform optimally over the years. The cabinet is constructed from heavy-duty steel with a baked-on powder coat finish, which provides an extra layer of protection against the elements and ensures that the unit maintains its aesthetic appeal.

In terms of indoor comfort, the Ducane 2HP13 employs a high-efficiency scroll compressor. This technology reduces noise levels and improves overall performance, ensuring that your indoor environment remains quiet and comfortable. Additionally, the compressor is equipped with built-in protective features that help safeguard it from potential operational issues, extending its lifespan.

The 2HP13 model also includes a reliable multi-speed blower motor that enhances airflow within the system. This allows for adjustable performance levels which can be tailored to the specific needs of the space, contributing to improved energy efficiency. The unit also supports diagnostic capabilities, allowing for easy maintenance and repair, minimizing downtime in case of any issues.

Furthermore, the Ducane 2HP13 is designed with a user-friendly interface that makes it easy for homeowners to operate. It also integrates seamlessly with various smart thermostats to enhance system control and contribute to even greater energy savings.

In summary, the Ducane 2HP13 embodies a perfect balance of efficiency, reliability, and user-friendly features. Its durable construction, advanced compressor technology, and high-performance capabilities make it an excellent choice for anyone looking to enhance their indoor climate while minimizing their energy consumption. With its strong reputation in the HVAC industry, Ducane ensures that the 2HP13 meets the needs of modern homeowners and businesses alike.