TXV Stuck Open:
•Head pressure will be slightly to moderately low;
•Suction pressure will be slightly high to very high;
•Amperage (not a reliable indicator of this condition);
•Liquid
•Superheat will be minimal or nonexistent;
•Suction line, and possibly a large portion of compressor, will be very cold and possibly “sweating”. Explanation: Refrigerant is flowing through the system too quickly; enough heat cannot be added in the evaporator to boil off all the liquid refrigerant. The main effect is to flood the suction line and compressor with liquid refrigerant. The primary indicator of this condition is little or no suction line superheat. Also, as the TXV is not holding back the required amount of refrigerant, there may be flash gas
Insufficient Condenser Water Flow:
•Head pressure will moderately high to very high;
•Suction pressure my be normal to slightly high;
•Amperage will be higher than normal;
•Liquid
•Condenser
•Superheat will be
Explanation: Heat is not being removed in the condenser in quantities sufficient to produce appreciable amounts of liquid refrigerant. With no liquid seal occurring in the condenser, the liquid
INSTALLATION
Placement of Heater
Indoor Installation
Every indoor installation is unique, therefore, there are no specific guidelines for this type of installation. For assistance, please contact AquaCal’s Engineering or Technical department at (800)
Outdoor Installation
Service and Operational Clearances:
uRefer to recommended clearance drawings following this section. Allow 24" clearance between the heat collection surfaces and walls, fences, shrubs, or other objects. The heat pump requires large volumes of air moving over the heat collector.
uAllow 5 feet of vertical clearance between the top of the heat pump and any roof overhang or
other obstruction. This clearance prevents cold discharge air from recirculating back into the evaporator coils (recirculation would reduce the overall performance of the heat Pump).
uProvide at least 30” open area in front of the main access panel. The electrical panel will need to be accessed during installation and service, so avoid any plumbing obstructions that will restrict easy access.