Bryant 575C, 575B Pre-Start-Up, Preliminary Checks, → Recommended Process for Checking for Leaks

Page 15

PRE-START-UP

IMPORTANT: Before beginning Pre-Start-Up or Start-Up, review Start-Up Checklist at the back of this book. The checklist assures proper start-up of the system and provides a record of unit condition, application requirements, system information, and operation at initial start-up.

CAUTION: Do not attempt to start the heat pump system, even momentarily, until the following steps have been completed. Compressor damage may result.

I.PRELIMINARY CHECKS

1.Check all air handler and other equipment auxiliary components. Consult manufacturer’s instructions re- garding any other equipment attached to unit. If unit has field-installed accessories, be sure all are properly installed and correctly wired. If used, airflow switch must be properly installed. See Fig. 14 for typical field wiring.

2.As shipped, compressor is held down by 4 bolts. After unit is installed, loosen each bolt and locknut until flat washer or snubber can be moved with finger pres- sure. Be sure compressor floats freely on the mount- ing springs (541A units only). See Fig. 15A and 15B for compressor mounting.

3.Check tightness of all electrical connections.

4.Electrical power source must agree with nameplate rating.

5.Turn on crankcase heater for 24 hours before starting the unit to be sure all refrigerant is out of the oil. To energize crankcase heater, perform the following steps:

a.Set the space thermostat system switch to OFF, or adjust the temperature so there is no demand for cooling.

b.Close the field disconnect.

c.Leave the compressor circuit breaker off. The crankcase heater is now energized.

6.Leak test the field refrigerant piping, connections and joints, and indoor coil. To perform leak test, com- plete the following steps:

a.Pressurize refrigerant piping; do not exceed 150 psi.

b.Using soap bubbles and/or an electronic leak detector, test refrigerant piping, connections and joints, and the indoor coil. See Fig. 16.

c.Check for leaks.

Evacuate and dehydrate entire refrigerant system.

7.541A180 only — compressor oil level should be visible in sight glass. Adjust the oil level as required. No oil should be removed unless the crankcase heater has been energized for at least 24 hours. See Start-Up section, Preliminary Oil Charge.

NOTE: The 575B, 575C units do not have a compres- sor oil level sight glass. These units are factory charged with the required amount of oil. If required, use the following oil for replacement: For 575B units use Zerol 150, part number P903-2001. For 575C units use RCD, part number P903-0101.

8.Backseat (open) compressor suction and discharge valves. Now close valves one turn to allow refrigerant pressure to reach test gages.

SNUBBER WASHER

SELF-LOCKING

BOLT

NEOPRENE

SNUBBER

COMPRESSOR FOOT

Fig. 15A — Compressor Mounting — 575B072 and

575C090,120 Units

Fig. 15B — Compressor Mounting — 541A180 Units

 

150 PSI MAX

 

 

 

DRY

 

 

 

NITROGEN

 

 

 

 

LIQUID LINE

INDOOR

 

SUCTION LINE

SOLENOID VALVE

COIL

 

 

 

OUTDOOR

 

 

 

UNIT

LIQUID LINE

TXV

 

 

 

SOAP

Fig. 16 — Recommended Process for Checking for Leaks

II.PRELIMINARY CHARGE

CAUTION: The 575C090 and 575C120 units contain a 9 lb charge of refrigerant. Add remainder of preliminary charge and allow pressure to equalize before starting compressor. Failure to do so WILL cause the compressor to overheat in a few minutes, possibly causing permanent compressor damage. The amount of refrigerant added must be at least 80% of the operating charge listed in the Physical Data table (Table 1).

15

Image 15
Contents General ContentsSafety Considerations Installation Complete PRE-INSTALLATION ChecksMount Unit Locate Unit575C090,120 Unit Dimensions 244 Weight lb kgUnit 180 803 158Component Locations 541A180 Shown Outdoor Fans Physical Data 575B072, 575C090,120 and 541A180 UnitsRefrigerant CompressorIII. Complete Refrigerant Piping Connections Refrigerant Specialties Part Numbers Provide Safety ReliefVapor Line Piping Procedure Minimum Outdoor Air Operating TemperatureIV. Complete Electrical Connections MCA Mocp Option RLA LRALP/HP SENTstat IFM EquipGND IFCGND HTR II. Preliminary Charge PRE-START-UPPreliminary Checks → Recommended Process for Checking for LeaksSTART-UP III. Advanced Scroll Temperature Protection AstpIII. Liquid Line Solenoid IV. AccumulatorVI. Start Unit VII. Adjust Refrigerant ChargeIV. Compressor Lockout Device Preliminary OIL Charge 541ASequence of Operation Duplex 575C120 and 541A180 Units With 524A-H300 See Fig III A180 Units HeatingIV. Duplex Units Duplex 575C120 Units with 524A-H240 See FigService Compressor Removal RestartVI. Causes of Complete Unit Shutdown VII. Outdoor Unit Fans IV A180 Cooling Mode Operation See Fig541A180 Heating Mode Operation See Fig VI. Crankcase Heater575C090,120 Heating Mode Size 090 Shown IX. Coil Cleaning and Maintenance Cleaning Standard CoilsCleaning and Maintaining E-Coated Coils Pivot and Support Top Cover Coil Cleaning TypicalTroubleshooting Chart Heating Cycle CCH TXV Thermostatic Expansion ValveIndoor Unit Preliminary InformationII. PRE-START-UP Outdoor Unit ControlsCooling Heating III. START-UP

541A, 575B, 575C specifications

The Bryant 575B, 541A, and 575C heating and cooling units are part of the renowned Bryant lineup, designed to provide efficient and reliable climate control solutions for residential and commercial spaces. These models are particularly celebrated for their impressive performance, innovative technologies, and user-friendly operations.

Starting with the Bryant 575B, this model is a high-efficiency air conditioner that boasts a SEER rating of up to 20.5. It utilizes a variable-speed compressor that adjusts its output based on the temperature needs of the home, leading to enhanced energy savings and consistent indoor comfort. The 575B is equipped with a steel cabinet that resists corrosion and damage while also minimizing noise levels during operation. Additionally, its environmentally friendly R-410A refrigerant helps to reduce the system's ecological footprint.

Moving on to the Bryant 541A, this unit is a formidable gas furnace known for its exceptional heating capabilities. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 97.5%, the 541A efficiently transforms fuel into heat, ensuring lower energy bills during cold months. It incorporates advanced technologies such as a two-stage gas valve and a variable-speed blower motor, allowing it to respond dynamically to the heating demands of the home. The insulated cabinet construction further enhances energy efficiency by preventing heat loss and increasing comfort.

Lastly, the Bryant 575C model is a versatile heat pump that offers both heating and cooling functionalities, ideal for regions with moderate heating and cooling needs. It features a SEER rating of up to 20 and an HSPF (Heating Season Performance Factor) rating of up to 10.5, making it an energy-efficient choice year-round. The 575C comes with a streamlined design that integrates a variable-speed compressor, which helps maintain precise temperatures and minimizes energy consumption. Additionally, its quiet operation is enhanced by sound insulation, providing a serene indoor environment.

All three models are designed with durability in mind, featuring robust construction materials that withstand the elements. They can be easily integrated with smart thermostats, providing homeowners with greater control over their energy use. With exceptional efficiency ratings, durable designs, and advanced features, the Bryant 575B, 541A, and 575C represent a perfect blend of comfort and cutting-edge technology. Whether for heating or cooling, these units deliver outstanding performance to meet the needs of today's energy-conscious consumers.