Bryant 575C, 575B IV A180 Cooling Mode Operation See Fig, 541A180 Heating Mode Operation See Fig

Page 21

IV. 541A180 COOLING MODE OPERATION (See Fig. 22)

1.High pressure, high temperature refrigerant vapor from the compressor flows through the reversing valve and is directed to the outdoor coil vapor header.

2.At the outdoor coil vapor header, the high pressure, high temperature refrigerant vapor flows up to check valve “A” that blocks the flow. All the refrigerant is then directed to flow into the coil circuits.

3.Subcooled refrigerant liquid leaves the coil circuits entering the portion of the vapor header which is above check valve “A”. Check valve “C” is closed, therefore, the liquid refrigerant passes through check valve “B,” which is open, and enters the liquid line and goes to the indoor coil.

4.The liquid refrigerant is expanded and evaporated in the indoor coil resulting in low pressure vapor. This low pressure vapor returns to the outdoor unit through the system vapor line, reversing valve, and accumulator, reentering the compressor at the suc- tion connection.

V.541A180 HEATING MODE OPERATION (See Fig. 23)

1.High pressure, high temperature refrigerant vapor from the compressor flows through the reversing valve and is directed through the system vapor line to the indoor coil. Refrigerant is condensed and subcooled in the indoor coil and returns to the outdoor unit through the system liquid line.

2.Check valve “B” blocks the flow of liquid and the refrigerant is then directed to flow through check valve “C” (which is open), through the filter drier, and into the liquid header assembly.

3.The liquid refrigerant is expanded as it passes through the capillary tubes into outdoor coil circuits. The refrigerant evaporates as it passes through the coil circuits resulting in low pressure vapor.

4.The low pressure vapor leaves the coil circuits and enters the vapor header, check valve “A” is open, and returns to the compressor through the vapor line, reversing valve, and accumulator, reentering the compressor at the suction connection.

VI. CRANKCASE HEATER

The crankcase heater prevents refrigerant migration and compressor oil dilution during shutdown when compressor is not operating.

Close both compressor service valves when crankcase heater is deenergized for more than 6 hours.

VII. OUTDOOR UNIT FANS

Each fan is supported by a formed-wire mount bolted to the fan deck and covered with a wire guard. On the 541A180, the exposed end of the motor shaft is covered with a rubber boot. In case a fan motor must be repaired or replaced, be sure the rubber boot is put back on when the fan is reinstalled and be sure the fan guard is in place before starting the unit.

VIII. LUBRICATION

Fan motors have permanently sealed bearings. No further lubrication is required.

COMPRESSOR

REVERSING VALVE

 

 

VAPOR LINE

 

FROM

 

 

INDOOR

ACCUMULATOR

BALL

UNIT

 

VALVE

 

 

 

CK VALVE B

CK VALVE A

CK VALVE C

FILTER

FILTER

DRIER

DRIER

FIXED ORIFICE

 

LIQUID LINE

 

 

TO

 

 

 

 

INDOOR

METERING DEVICE

 

 

 

 

 

 

 

BALL

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

 

VALVE

 

Fig. 20 — 575C090,120 Cooling Mode (Size 090 Shown)

21

Image 21
Contents Safety Considerations ContentsInstallation Complete PRE-INSTALLATION Checks GeneralMount Unit Locate Unit575C090,120 Unit Dimensions Unit Weight lb kg180 803 158 244Component Locations 541A180 Shown Refrigerant Physical Data 575B072, 575C090,120 and 541A180 UnitsCompressor Outdoor FansIII. Complete Refrigerant Piping Connections Vapor Line Piping Procedure Provide Safety ReliefMinimum Outdoor Air Operating Temperature Refrigerant Specialties Part NumbersIV. Complete Electrical Connections MCA Mocp Option RLA LRALP/HP SENTstat GND EquipIFC IFMGND HTR Preliminary Checks PRE-START-UP→ Recommended Process for Checking for Leaks II. Preliminary ChargeIII. Liquid Line Solenoid III. Advanced Scroll Temperature Protection AstpIV. Accumulator START-UPIV. Compressor Lockout Device VII. Adjust Refrigerant ChargePreliminary OIL Charge 541A VI. Start UnitSequence of Operation IV. Duplex Units III A180 Units HeatingDuplex 575C120 Units with 524A-H240 See Fig Duplex 575C120 and 541A180 Units With 524A-H300 See FigService Compressor Removal RestartVI. Causes of Complete Unit Shutdown 541A180 Heating Mode Operation See Fig IV A180 Cooling Mode Operation See FigVI. Crankcase Heater VII. Outdoor Unit Fans575C090,120 Heating Mode Size 090 Shown IX. Coil Cleaning and Maintenance Cleaning Standard CoilsCleaning and Maintaining E-Coated Coils Pivot and Support Top Cover Coil Cleaning TypicalTroubleshooting Chart Heating Cycle CCH TXV Thermostatic Expansion ValveII. PRE-START-UP Outdoor Unit Preliminary InformationControls Indoor UnitCooling Heating III. START-UP

541A, 575B, 575C specifications

The Bryant 575B, 541A, and 575C heating and cooling units are part of the renowned Bryant lineup, designed to provide efficient and reliable climate control solutions for residential and commercial spaces. These models are particularly celebrated for their impressive performance, innovative technologies, and user-friendly operations.

Starting with the Bryant 575B, this model is a high-efficiency air conditioner that boasts a SEER rating of up to 20.5. It utilizes a variable-speed compressor that adjusts its output based on the temperature needs of the home, leading to enhanced energy savings and consistent indoor comfort. The 575B is equipped with a steel cabinet that resists corrosion and damage while also minimizing noise levels during operation. Additionally, its environmentally friendly R-410A refrigerant helps to reduce the system's ecological footprint.

Moving on to the Bryant 541A, this unit is a formidable gas furnace known for its exceptional heating capabilities. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 97.5%, the 541A efficiently transforms fuel into heat, ensuring lower energy bills during cold months. It incorporates advanced technologies such as a two-stage gas valve and a variable-speed blower motor, allowing it to respond dynamically to the heating demands of the home. The insulated cabinet construction further enhances energy efficiency by preventing heat loss and increasing comfort.

Lastly, the Bryant 575C model is a versatile heat pump that offers both heating and cooling functionalities, ideal for regions with moderate heating and cooling needs. It features a SEER rating of up to 20 and an HSPF (Heating Season Performance Factor) rating of up to 10.5, making it an energy-efficient choice year-round. The 575C comes with a streamlined design that integrates a variable-speed compressor, which helps maintain precise temperatures and minimizes energy consumption. Additionally, its quiet operation is enhanced by sound insulation, providing a serene indoor environment.

All three models are designed with durability in mind, featuring robust construction materials that withstand the elements. They can be easily integrated with smart thermostats, providing homeowners with greater control over their energy use. With exceptional efficiency ratings, durable designs, and advanced features, the Bryant 575B, 541A, and 575C represent a perfect blend of comfort and cutting-edge technology. Whether for heating or cooling, these units deliver outstanding performance to meet the needs of today's energy-conscious consumers.