Bryant 575C, 575B, 541A dimensions Sequence of Operation

Page 18

LIQUID TEMPERATURE AT LIQUID VALVE (C)

60

54

49

43

38

32

27

21

16

10

Fig. 19A — 575B072 Charging Chart

 

140

(F)

130

ADD CHARGE IF ABOVE CURVE

VALVE

120

 

AT LIQUID

110

100

TEMPERATURE

90

80

 

LIQUID

70

REDUCE CHARGE IF BELOW CURVE

 

60

 

50

50

100

150

200

250

300

350

400

 

 

 

LIQUID PRESSURE AT LIQUID VALVE (PSIG)

 

 

 

344

689

1034

1379

1724

2069

2414

 

 

 

 

 

LIQUID PRESSURE AT LIQUID VALVE (Kilopascals)

 

 

 

Fig. 19B — 575C090,120 Charging Chart

Fig. 19C — 541A180 Charging Chart

SEQUENCE OF OPERATION

I. 575B072 UNITS

When power is supplied to unit, the transformer (TRAN) and crankcase heater (CCH) are energized.

A. Cooling

On a call for cooling, the thermostat completes the following circuits: R-G, R-Y, and R-O. If the compressor recycle delay of 3 minutes is complete, the compressor and outdoor fan start. The reversing valve is energized for cooling and the indoor- fan motor starts.

When the thermostat is satisfied, the circuits are opened, and the compressor, outdoor-fan motor, and indoor-fan motor stop. The reversing valve is deenergized.

B. Heating

On a call for heating, the thermostat completes the following circuits: R-G and R-Y. If the compressor recycle delay of 3 minutes is complete, the compressor and outdoor fan start. The indoor-fan motor will also start.

If room temperature continues to fall, the thermostat completes circuit R-W. If the optional electric heat package is used, the heat relay is energized, and the electric heaters are energized.

When the thermostat is satisfied, the circuits are opened, and the compressor, outdoor-fan motor, heaters, and indoor- fan motor stop.

C. Defrost

Defrost board (DB) is a time and temperature control, which includes a field-selectable time period between checks for frost (30, 50, and 90 minutes). Electronic timer and defrost cycle start only when contactor is energized and defrost ther- mostat (DFT) is closed (below 28 F).

Defrost mode is identical to Cooling mode, except outdoor-fan motor (OFM) stops and a bank of supplemental electric heat turns on to warm air supplying the conditioned space. Defrost mode is terminated when the DFT reaches 65 F.

D. Air Circulation

When the fan switch is at FAN ON, the indoor-air fans oper- ate continuously to provide ventilation. The thermostat operates the other components as described above.

E. Emergency Heat Cycle

If the compressor is inoperative due to a tripped safety device, the second stage of the thermostat automatically energizes the indoor-air fan and the electric resistance heat- ers (if equipped).

II. 575C090,120 UNITS

When power is supplied to unit, the transformer (TRAN) is energized. The crankcase heater is also energized.

A. Cooling

With the thermostat subbase in the cooling position, and when the space temperature comes within 2° F of the cooling set point, the thermostat makes circuit R-O. This energizes the reversing valve solenoid (RVS) and places the unit in standby condition for cooling.

As the space temperature continues to rise, the second stage of the thermostat makes, closing circuit R-Y. When compres- sor time delay (5 ± 2 minutes) is completed, a circuit is made to contactor (C), starting the compressor (COMP) and outdoor-fan motor (OFM). Circuit R-G is made at the same time, energizing the indoor-fan contactor (IFC) and starting the indoor-fan motor (IFM) after one-second delay.

18

Image 18
Contents Installation Complete PRE-INSTALLATION Checks ContentsSafety Considerations GeneralLocate Unit Mount Unit575C090,120 Unit Dimensions 180 803 158 Weight lb kgUnit 244Component Locations 541A180 Shown Compressor Physical Data 575B072, 575C090,120 and 541A180 UnitsRefrigerant Outdoor FansIII. Complete Refrigerant Piping Connections Minimum Outdoor Air Operating Temperature Provide Safety ReliefVapor Line Piping Procedure Refrigerant Specialties Part NumbersIV. Complete Electrical Connections RLA LRA MCA Mocp OptionLP/HP SENTstat IFC EquipGND IFMGND HTR → Recommended Process for Checking for Leaks PRE-START-UPPreliminary Checks II. Preliminary ChargeIV. Accumulator III. Advanced Scroll Temperature Protection AstpIII. Liquid Line Solenoid START-UPPreliminary OIL Charge 541A VII. Adjust Refrigerant ChargeIV. Compressor Lockout Device VI. Start UnitSequence of Operation Duplex 575C120 Units with 524A-H240 See Fig III A180 Units HeatingIV. Duplex Units Duplex 575C120 and 541A180 Units With 524A-H300 See FigService Compressor Removal RestartVI. Causes of Complete Unit Shutdown VI. Crankcase Heater IV A180 Cooling Mode Operation See Fig541A180 Heating Mode Operation See Fig VII. Outdoor Unit Fans575C090,120 Heating Mode Size 090 Shown IX. Coil Cleaning and Maintenance Cleaning Standard CoilsCleaning and Maintaining E-Coated Coils Coil Cleaning Typical Pivot and Support Top CoverTroubleshooting Chart Heating Cycle Thermostatic Expansion Valve CCH TXVControls Preliminary InformationII. PRE-START-UP Outdoor Unit Indoor UnitIII. START-UP Cooling Heating

541A, 575B, 575C specifications

The Bryant 575B, 541A, and 575C heating and cooling units are part of the renowned Bryant lineup, designed to provide efficient and reliable climate control solutions for residential and commercial spaces. These models are particularly celebrated for their impressive performance, innovative technologies, and user-friendly operations.

Starting with the Bryant 575B, this model is a high-efficiency air conditioner that boasts a SEER rating of up to 20.5. It utilizes a variable-speed compressor that adjusts its output based on the temperature needs of the home, leading to enhanced energy savings and consistent indoor comfort. The 575B is equipped with a steel cabinet that resists corrosion and damage while also minimizing noise levels during operation. Additionally, its environmentally friendly R-410A refrigerant helps to reduce the system's ecological footprint.

Moving on to the Bryant 541A, this unit is a formidable gas furnace known for its exceptional heating capabilities. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 97.5%, the 541A efficiently transforms fuel into heat, ensuring lower energy bills during cold months. It incorporates advanced technologies such as a two-stage gas valve and a variable-speed blower motor, allowing it to respond dynamically to the heating demands of the home. The insulated cabinet construction further enhances energy efficiency by preventing heat loss and increasing comfort.

Lastly, the Bryant 575C model is a versatile heat pump that offers both heating and cooling functionalities, ideal for regions with moderate heating and cooling needs. It features a SEER rating of up to 20 and an HSPF (Heating Season Performance Factor) rating of up to 10.5, making it an energy-efficient choice year-round. The 575C comes with a streamlined design that integrates a variable-speed compressor, which helps maintain precise temperatures and minimizes energy consumption. Additionally, its quiet operation is enhanced by sound insulation, providing a serene indoor environment.

All three models are designed with durability in mind, featuring robust construction materials that withstand the elements. They can be easily integrated with smart thermostats, providing homeowners with greater control over their energy use. With exceptional efficiency ratings, durable designs, and advanced features, the Bryant 575B, 541A, and 575C represent a perfect blend of comfort and cutting-edge technology. Whether for heating or cooling, these units deliver outstanding performance to meet the needs of today's energy-conscious consumers.