Bryant 575B, 575C III. Liquid Line Solenoid, IV. Accumulator, Start-Up, II. Compressor Overload

Page 16

Before starting the unit, charge liquid refrigerant into the high side of the system through the liquid service valve. Allow high and low side pressures to equalize before starting compressor. If pressures do not equalize readily, charge vapor on low side of system to assure charge in the evapora- tor. Refer to GTAC II, Module 5, Charging, Recovery, Recy- cling, and Reclamation for liquid charging procedures.

III. LIQUID LINE SOLENOID

To minimize refrigerant migration to the compressor during the heat pump OFF cycle, the 575B,C unit must have a bi-flow liquid line solenoid valve (field supplied). The valve opens when the compressor is energized, and closes when the compressor is deenergized. This reduces compressor flooded starts, thus significantly increasing compressor life.

IV. ACCUMULATOR

The unit accumulator controls the rate of liquid refrigerant to the compressor during heat pump operation.

The 541A accumulator features a unique method for returning oil to the compressor. The oil return mechanism is external to the accumulator. The mixture of oil and refriger- ant is metered to the compressor by a brass orifice which is removable and cleanable. The oil return mechanism also contains a solenoid valve that opens when the compressor is ON and closes when the compressor is OFF. This keeps the liquid refrigerant stored in the accumulator from draining to the compressor during the heat pump OFF cycle, which further protects the compressor against flooded starts.

START-UP

CAUTION: Compressor crankcase heater must be on for 24 hours before start-up. After the heater has been on for 24 hours, the unit can be started.

CAUTION: Prior to starting compressor, a preliminary charge of refrigerant must be added to avoid possible compressor damage.

I. COMPRESSOR ROTATION (575B,C Units)

On 3-phase units with scroll compressors, it is important to be certain compressor is rotating in the proper direction. To determine whether or not compressor is rotating in the proper direction:

1.Connect service gages to suction and discharge pres- sure fittings.

2.Energize the compressor.

3.The suction pressure should drop and the discharge pressure should rise, as is normal on any start-up.

If the suction pressure does not drop and the discharge pressure does not rise to normal levels:

1.Note that the condenser fan is probably also rotating in the wrong direction.

2.Turn off power to the unit, tag disconnect.

3.Reverse any two of the unit power leads.

4.Reapply power to the compressor, verify correct pressures.

The suction and discharge pressure levels should now move to their normal start-up levels.

II. COMPRESSOR OVERLOAD

This overload interrupts power to the compressor when either the current or internal motor winding temperature

becomes excessive, and automatically resets when the internal temperature drops to a safe level. This overload usually resets within 60 minutes (or longer). If the internal overload is suspected of being open, disconnect the electrical power to the unit and check the circuit through the overload with an ohmmeter or continuity tester.

III.ADVANCED SCROLL TEMPERATURE PROTECTION (ASTP)

Advanced Scroll Temperature Protection (ASTP) is a form of internal discharge temperature protection that unloads the scroll compressor when the internal temperature reaches approximately 300 F. At this temperature, an internal bi- metal disk valve opens and causes the scroll elements to sep- arate, which stops compression. Suction and discharge pres- sures balance while the motor continues to run. The longer the compressor runs unloaded, the longer it must cool before the bi-metal disk resets. See Fig. 17.

To manually reset ASTP, the compressor should be stopped and allowed to cool. If the compressor is not stopped, the motor will run until the motor protector trips, which occurs up to 90 minutes later. Advanced Scroll Temperature Protec- tion will reset automatically before the motor protector resets, which may take up to 2 hours. A label located above the terminal box identifies Copeland Scroll compressor models (ZR94, 108 and 125) that contain this technology. See Fig. 18.

 

 

120

 

 

 

 

 

 

 

 

 

 

 

110

 

 

 

 

 

 

 

 

 

Time

 

100

 

 

 

 

 

 

 

 

 

 

90

 

 

 

 

 

 

 

 

 

Recommended Cooling

 

 

 

 

 

 

 

 

 

 

(Minutes)

80

 

 

 

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

 

 

40

 

 

 

 

 

 

 

 

 

30

 

 

 

 

 

 

 

 

 

20

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

0

10

20

30

40

50

60

70

80

90

 

 

 

 

Compressor Unloaded Run Time (Minutes)

 

 

*Times are approximate.

NOTE: Various factors, including high humidity, high ambient tempera- ture, and the presence of a sound blanket will increase cool-down times.

Fig. 17 — Recommended Minimum Cool-Down Time After

Compressor is Stopped*

Fig. 18 — Advanced Scroll Temperature Protection Label

16

Image 16
Contents Contents Safety ConsiderationsInstallation Complete PRE-INSTALLATION Checks GeneralLocate Unit Mount Unit575C090,120 Unit Dimensions Weight lb kg Unit180 803 158 244Component Locations 541A180 Shown Physical Data 575B072, 575C090,120 and 541A180 Units RefrigerantCompressor Outdoor FansIII. Complete Refrigerant Piping Connections Provide Safety Relief Vapor Line Piping ProcedureMinimum Outdoor Air Operating Temperature Refrigerant Specialties Part NumbersIV. Complete Electrical Connections RLA LRA MCA Mocp OptionSEN LP/HPTstat Equip GNDIFC IFMGND HTR PRE-START-UP Preliminary Checks→ Recommended Process for Checking for Leaks II. Preliminary ChargeIII. Advanced Scroll Temperature Protection Astp III. Liquid Line SolenoidIV. Accumulator START-UPVII. Adjust Refrigerant Charge IV. Compressor Lockout DevicePreliminary OIL Charge 541A VI. Start UnitSequence of Operation III A180 Units Heating IV. Duplex UnitsDuplex 575C120 Units with 524A-H240 See Fig Duplex 575C120 and 541A180 Units With 524A-H300 See FigRestart Service Compressor RemovalVI. Causes of Complete Unit Shutdown IV A180 Cooling Mode Operation See Fig 541A180 Heating Mode Operation See FigVI. Crankcase Heater VII. Outdoor Unit Fans575C090,120 Heating Mode Size 090 Shown Cleaning Standard Coils IX. Coil Cleaning and MaintenanceCleaning and Maintaining E-Coated Coils Coil Cleaning Typical Pivot and Support Top CoverTroubleshooting Chart Heating Cycle Thermostatic Expansion Valve CCH TXVPreliminary Information II. PRE-START-UP Outdoor UnitControls Indoor UnitIII. START-UP Cooling Heating

541A, 575B, 575C specifications

The Bryant 575B, 541A, and 575C heating and cooling units are part of the renowned Bryant lineup, designed to provide efficient and reliable climate control solutions for residential and commercial spaces. These models are particularly celebrated for their impressive performance, innovative technologies, and user-friendly operations.

Starting with the Bryant 575B, this model is a high-efficiency air conditioner that boasts a SEER rating of up to 20.5. It utilizes a variable-speed compressor that adjusts its output based on the temperature needs of the home, leading to enhanced energy savings and consistent indoor comfort. The 575B is equipped with a steel cabinet that resists corrosion and damage while also minimizing noise levels during operation. Additionally, its environmentally friendly R-410A refrigerant helps to reduce the system's ecological footprint.

Moving on to the Bryant 541A, this unit is a formidable gas furnace known for its exceptional heating capabilities. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 97.5%, the 541A efficiently transforms fuel into heat, ensuring lower energy bills during cold months. It incorporates advanced technologies such as a two-stage gas valve and a variable-speed blower motor, allowing it to respond dynamically to the heating demands of the home. The insulated cabinet construction further enhances energy efficiency by preventing heat loss and increasing comfort.

Lastly, the Bryant 575C model is a versatile heat pump that offers both heating and cooling functionalities, ideal for regions with moderate heating and cooling needs. It features a SEER rating of up to 20 and an HSPF (Heating Season Performance Factor) rating of up to 10.5, making it an energy-efficient choice year-round. The 575C comes with a streamlined design that integrates a variable-speed compressor, which helps maintain precise temperatures and minimizes energy consumption. Additionally, its quiet operation is enhanced by sound insulation, providing a serene indoor environment.

All three models are designed with durability in mind, featuring robust construction materials that withstand the elements. They can be easily integrated with smart thermostats, providing homeowners with greater control over their energy use. With exceptional efficiency ratings, durable designs, and advanced features, the Bryant 575B, 541A, and 575C represent a perfect blend of comfort and cutting-edge technology. Whether for heating or cooling, these units deliver outstanding performance to meet the needs of today's energy-conscious consumers.