GUIDE SPECIFICATIONS — 542J150,180 UNITS

542J150,180

PACKAGED ROOFTOP AIR-TO-AIR HEAT PUMP — CON- STANT VOLUME APPLICATION

HVAC GUIDE SPECIFICATIONS

SIZE RANGE: 12 to 15 TONS, NOMINAL (COOLING) 136,000 to 172,000 BTUH, NOMINAL (INPUT HEATING)

BRYANT MODEL NUMBER: 542J

PART 1 — GENERAL

1.01SYSTEM DESCRIPTION

Outdoor rooftop mounted, electrically controlled air-to-air heat pump unit utilizing reciprocating, semi-hermetic com- pressor(s) for cooling duty and electric resistance coils for heating duty. Unit shall discharge supply air vertically or horizontally (with horizontal supply/return adapter assem- bly or roof curb) as shown on contract drawings.

1.02QUALITY ASSURANCE

A.Unit shall be rated in accordance with ARI Standard 340. Designed in accordance with UL Standard 1995.

B.Unit shall be designed to conform to ASHRAE 15, latest revision.

C.Unit shall be UL-tested and certified in accordance with ANSI Z21.47 Standards and UL-listed and certified under Canadian standards as a total package for safety requirements.

D.Roof curb shall be designed to conform to NRCA Standards.

E.Insulation and adhesive shall meet NFPA 90A require- ments for flame spread and smoke generation.

F.Unit casing shall be capable of withstanding 500-hour salt spray exposure per ASTM B117 (scribed specimen).

G.Unit shall be designed in accordance with ISO 9001, and shall be manufactured in a facility registered to ISO 9002/ BS5750, Part 2.

H.Each unit shall be subjected to a completely automated run testing on the assembly line. Units contain a factory- supplied printout indicating tested pressures, amperages, data, and inspectors; providing certification of the unit status at the time of manufacture.

1.03 DELIVERY, STORAGE, AND HANDLING

Unit shall be stored and handled per manufacturer’s recommendations.

PART 2 — PRODUCTS

2.01EQUIPMENT (STANDARD)

A.General:

Factory assembled, single-piece heat pump unit. Con- tained within the unit enclosure shall be all factory wiring, piping, controls, refrigerant charge (R-22), and special features required prior to field start-up.

B.Unit Cabinet:

1.Unit cabinet shall be constructed of galvanized steel, and shall be bonderized and coated with a pre- painted baked enamel finish on all externally exposed surfaces.

2.Indoor fan compartment interior cabinet surfaces shall be insulated with a minimum 1/2-in. thick, 1 lb. density, flexible fiberglass insulation, neoprene coated on the air side.

3.Cabinet panels shall be easily removable for servicing.

4.Holes shall be provided in the base rails for rigging shackles to facilitate maneuvering and overhead rigging.

5.Unit shall have a factory-installed, sloped conden- sate drain pan made of a non-corrosive material, pro- viding a minimum 3/4-in. 14 NPT connection with both vertical and horizontal drains, and shall comply with ASHRAE Standard 62.

6.Unit shall have a factory-installed filter access panel to provide filter access with tool-less removal.

7.Unit shall have standard thru-the-bottom power con- nection capability (accessory kit is required).

C.Fans:

1.Indoor Fan:

a.Fan shall be belt driven with an adjustable-pitch motor pulley. The standard fan drive shall have a factory-installed low-medium static pressure fan drive. The alternate fan drive option shall have a factory-installed high static pressure fan drive.

b.Fan wheel shall be double-inlet type with forward- curved blades.

c.Bearings shall be sealed, permanently lubricated ball-bearing type for longer life and lower maintenance.

d.Bearings shall be pillow block type (180 only).

2.Indoor fan shall be made from steel with a corrosion- resistant finish and shall be dynamically balanced.

3.Outdoor fan shall be of the direct-driven (with totally enclosed motors) propeller type and shall discharge air vertically.

4.Outdoor fan shall have aluminum blades riveted to corrosion-resistant steel spiders and shall be dynam- ically balanced.

D.Compressor(s):

1.Reciprocating semi-hermetic compressors with factory-installed crankcase heaters.

2.Factory mounted on rubber grommets and internally spring mounted for vibration isolation.

3.On independent circuits (180).

4.The size 150 unit semi-hermetic compressor shall be equipped with an electric unloader for capacity control.

E.Coils:

1.Standard indoor and outdoor coils shall have copper or aluminum plate fins mechanically bonded to seamless internally grooved copper tubes with all joints brazed.

2.Coils:

a.Copper-fin coils shall be constructed of copper fins mechanically bonded to copper tubes and copper tube sheets. Galvanized steel tube sheets shall not be acceptable. A polymer strip shall pre- vent coil assembly from contacting the sheet metal coil pan to minimize potential for galvanic corrosion between coil and pan. All copper con- struction shall provide protection in moderate coastal environments.

118

Image 118
Contents 542J150,180 FEATURES/BENEFITS548F036-072 548F090-120 549B036-072 549B090-120 Table of Contents Integrated ECONOMI$ERS and Outdoor AIR Service OptionsINDOOR-AIR Quality Begins with Bryant Rooftops Options and Accessories Option ACCESSORY†LOW Ambient Controls Options and AccessoriesBarometric RELIEF/POWER Exhaust Emergency Heat Control PackageElectric Heaters DURA-SHIELDOUTDOOR Coil OptionsOutdoor Coil Protection Applications ECONOMI$ER Microprocessor ControllerConvenience Outlet Glycol Coil 150,180 onlyCompressor Hinged Panel Option Hail GuardBryant Commercial Programmable Thermostat Control BOX Hinged Panel OptionOptions and Accessories Controls Cooling, Units With EconoMi$er 548F036-072 and 549B036Controls Sequence of Operation 542J150,180Controls Typical Smoke Control/Fire Shutdown Wiring 542J150,180 Operating ModesApplication Data Concentric Duct Distribution 542J150,180 Application DataConcentric Duct Details 542J150,180 Horizontal Discharge Ducting 548F036-120 and 549B036-120 Typical Piping and WiringVertical Discharge Ducting 548F036-120 and 549B036-120 Typical Piping and Wiring ODS Model Number Model Number Nomenclature 548F UnitsARI* Capacity Ratings Physical Data 548F036-072Physical Data 548F090-120072-548F036 Base Unit Dimensions Roof Curb Unit Size Accessory CRRFCURB001A00 Accessory DimensionsConnector ALT GAS Power Control PKG. Accy Drain Hole CRRFCURB002A00Accessory Dimensions II Select Unit Based on Required Cooling Capacity Selection Procedure with 548F048 ExampleDetermine Cooling and Heating Loads AT Design Conditions III Select Electric HeatSHC Performance DataCooling Capacities Entering AIR DRY-BULB Temp FCooling Capacities Performance DataEntering AIR DRY-BULB Temp F Bypass 4100/0.18 4700/0.21 Air Temperature Entering Outdoor Coil FInstantaneous and Integrated Heating Ratings UnderInstantaneous and Integrated Heating Ratings 3000 Cap 1800 Cap2400 Cap 2600 Cap3600 Cap CfmStandard Air 2400 Cap 4000 CapESP FAN Performance Vertical Discharge Units548F036 3 Tons Standard Motor Direct Drive 548F036 3 Tons Alternate Motor Belt DriveFAN Performance Vertical Discharge Units 548F048 4 Tons Alternate Motor Belt DriveESP 548F060 5 Tons Standard Motor Direct Drive548F060 5 Tons Alternate Motor Belt Drive 548F060 5 Tons HIGH-STATIC Motor Belt Drive 548F072 6 Tons HIGH-STATIC Motor Belt Drive 518 562 Rpm Bhp Watts511 539 534 607548F090 71/2 Tons HIGH-STATIC Motor Belt Drive 548F102 8 TONS* Standard Motor Belt Drive 548F102 81/2 Tons HIGH-STATIC Motor Belt Drive 963 2651 548F120 10 TonsRpm Bhp 973 2782Airflow Low Speed High Speed Cfm 208 230, 460, 575 FAN Performance Horizontal Discharge UnitsCfm Rpm Bhp Watts FAN Performance Horizontal Discharge Units 548F048 4 Tons Alternate Motor Belt Drive729 388 787 450 895 593 658 276 722 337 840 470693 327 754 388 867 531 765 460 821 521548F060 5 Tons HIGH-STATIC Motor Belt Drive 548F072 6 Tons Standard Motor Belt Drive1900 982 779 1084 932 1160 1006 Rpm Bhp Watts 1800 942 700 1047 835 1139 9561031 1276 11142400 482 524 569 684 Rpm Bhp Watts 2250 465 473 554 6302300 471 487 559 646 2500 494 554 581 7232400 528 600 606 779 674 965 738 1199 795 Rpm Bhp Watts 2250 507 547 586 700 658 891 722 1097 7832300 513 562 592 723 663 916 727 1131 786 2500 542 648 619 835 686 1022 748 1258 806548F102 81/2 Tons Standard Motor Belt Drive 3100 636 1006 704 1241 764 1499 818 1744 Rpm Bhp Watts 2550 669 627 867 692 1056 754 1292 8122900 604 867 676 1089 737 1318 794 1560 848 3200 652 1089 718 1327 778 1595 831 1849General Notes for FAN Performance Tables FAN RPM AT Motor Pulley SETTINGS* 548F036-120 ACCESSORY/FIOP Static PRESSURE* in. wg 548F036-072ACCESSORY/FIOP Static PRESSURE* in. wg 548F090-120 Component CFMPower Requirements Optional Power ExhaustEconoMi$er Barometric Relief Damper Characteristics Mocp SizeHeater Rating Electric Heating CapacitiesMultiplication Factors DistributionOperating Watts AMP Draw Efficiency % INDOOR-FAN Motor Performance 548F UnitsUnit INDOOR-FAN Maximum Acceptable Motor 090Electrical Data Units Without Electrical Convenience OutletElectrical Data Units Without Electrical Convenience OutletOFM IFM SIZE† Voltage Compressor Electric Heat Power Supply DisconnectNominal IFM Range Tons81/2 Tons Units with Electrical Convenience Outlet Units with Electrical Convenience Outlet 40.4 45†† 195/195 13.6/15.6 57.4 59.9 60†† 208/211 Voltage Compressor Electric Power Supply Disconnect Unbalanced 3-Phase Supply Voltage Typical Wiring Schematic SW4Typical Wiring Schematic Outdoor-Fan Motor549B036-060 Model Number Nomenclature549B E X 090 000 AA 549B072-120549B036-072 Base Unit 549B549B090,120 Base Unit Dimensions 549B036-120 549B090,120 549B036-072 ′-2 ″′-0 ″ ″ 19 NPT 827 583 44.5 12.7 NPT Capacity Selection Procedure with 549B048 ExampleII Select Unit Based on Required Cooling Enter Cooling Capacities table at outdoor entering temperEntering AIR DRY-BULB Temp F Bypass SHCFactor 549B090 71/2 Tons Temp F 549B072 6 Tons Temp F1800/0.06 2100/0.066 2400/0.071 3000/0.088 Entering Air 2250/0.12 3000/0.15 3750/0.18 Entering Air900 Cap 549B036 3 Tons549B048 4 Tons 549B072 6 Tons 549B060 5 Tons2100 Cap 549B090 71/2 Tons Temperature Air Entering Outdoor Coil F db at 70% rh549B120 10 Tons 709 782 835 900 937 1100 Rpm Bhp 900673 736 805 865 911 1000 746 806 867 929 964 1200549B060 5 Tons Standard Motor Belt Drive 549B072 6 Tons Standard Motor Belt Drive549B090 71/2 Tons Standard Motor Belt Drive 549B120 10 Tons Standard Motor Belt Drive 670 758 812 863 914 1200 584 656 734 818 875 1000627 738 800 848 895 1100 710 780 840 889 938 13001372 Cfm Rpm Bhp 1500 1108 1187 1202 10792100 1252 1320 1388 1448 Airflow External Static Pressure in. wg635 699 Rpm Bhp 2250630 695 645 708615 679 734 787 595 657 716 770605 667 725 779 625 691 744 796FAN RPM AT Motor Pulley SETTINGS* 549B036-120 ACCESSORY/FIOP Static PRESSURE* in. wg 549B036-072ACCESSORY/FIOP Static PRESSURE* in. wg 549B090,120 549B 036INDOOR-FAN Motor Data 549B036-120 Outdoor Sound Power Total Unit Electric Heating CapacitiesRLA LRA Nominal Voltage Electric Power Minimum Unit Compressor OFMDisconnect Voltage Range Heat Supply FLA MCA Mocp LRAPh-Hz Min Max Nominal Voltage Electric Power Minimum Unit CompressorIFM Disconnect Voltage Range Heat Supply RLA LRA FLA30.4 106/106 43.0 247/247 10.4 21.7 25.0 70.1 74.3 269/272 Typical Wiring Schematic Potter & Brunfield Amps MustRating HFG. PT. no Trip RVSPart 1 General Guide Specifications 548F and 549B036-120 UnitsPart 2 Products Guide Specifications 548F and 549B036-120 Units Guide Specifications 548F and 549B036-120 Units 100 Model Number Nomenclature 542J150,180 Units 542J E X 150 000 AB H B542J150,180 Units Weight Distribution and Center of GravityUnit Weight Weight of Corner Dimensions Cooling HEATING-HIGH Temp HEATING-LOW Temp Sound UnitALT Unit 542JSTD STD ALTUnit Weight of Corner Unit Maximum Shipping WeightUnit Dimensions 542J 150 1895 860 180 2205 1000CRRFCURB011A00 DIMENSIONS* degrees and inchesPKG NO. REF Curb Description Height CRRFCURB010A00 CRRFCURB012A00Convenience Outlet 542J150,180 Horizontal Adapter Installation 542J150,180Accessory Curb Description HeightPower Exhaust 542J150,180 Non-Fused Disconnect 542J150,180Selection Procedure with 542J180 Example Capacity TC of 180,800 Btuh, a sensible heat capacity542J150 Temp F Air Entering Indoor Coil Cfm/BF 542J1805625 Integrated Heating CapacitiesCFM General Notes for FAN Performance Tables Fan Performance Using Accessory Power Exhaust ACCESSORY/FIOP Static PRESSURE* in. wg 542J150,180FAN RPM AT Motor Pulley SETTINGS* 542J150,180 ACCESSORY/FIOP Unit Size Unit Voltage CFMGlycol Coil Data Electric Heating Capacities 542J150,180Glycol Coil Ratings INDOOR-FAN Motor Performance 542J150,180 542J180, 460-3-60 Shown LPS BKR W/ATLOR CAPOptional Non-Fused Disconnect 542J150,180 Part 1 General Guide Specifications 542J150,180 UnitsPart 2 Products Guide Specifications 542J150,180 Units 120 121 Index 95,96
Related manuals
Manual 4 pages 35.17 Kb

549B, 548F, 542J specifications

Bryant 542J is a high-efficiency gas furnace that stands out for its reliability and advanced heating technologies. Designed to deliver consistent warmth and comfort in residential settings, it combines innovative engineering with energy-efficient features.

One of the key characteristics of the Bryant 542J is its two-stage heating capability. This means that the furnace can adjust its heat output according to the heating demands of your home. During milder weather, it operates at a lower stage, consuming less energy while still maintaining a comfortable environment. When the temperatures drop, the furnace shifts to its higher capacity, providing the necessary warmth efficiently. This not only enhances comfort but also contributes to lower energy bills.

In addition to its two-stage operation, the Bryant 542J also incorporates a variable-speed blower motor. This technology allows the furnace to adjust the airflow depending on the heating requirements, ensuring an even distribution of warm air throughout the home. The variable-speed blower also operates more quietly than conventional fixed-speed motors, creating a serene indoor environment.

Energy efficiency is a hallmark of the Bryant 542J, boasting an Annual Fuel Utilization Efficiency (AFUE) rating of up to 96.5%. This impressive rating means that a significant portion of the energy consumed is effectively converted into usable heat, resulting in substantial savings on heating costs over time. Furthermore, the furnace is equipped with a sealed combustion system that draws air from outside the home, minimizing energy waste and improving indoor air quality.

Diagnostic features are another highlight of the Bryant 542J, which come equipped with SmartEvap technology. This allows the unit to self-diagnose potential issues, providing homeowners with peace of mind and simplifying maintenance procedures.

Durability is also a key feature of the Bryant 542J. It is constructed with high-quality materials designed to withstand harsh winter conditions, ensuring a long lifespan and reliable performance. Its compact design also allows for flexible installation, making it suitable for various residential layouts.

In summary, the Bryant 542J is more than just a gas furnace; it is a sophisticated heating solution that combines efficiency, comfort, and reliability. With features such as two-stage heating, a variable-speed blower, high AFUE ratings, and advanced diagnostics, it is an excellent choice for homeowners seeking an efficient and effective heating system.