SELECTION PROCEDURE (WITH 549B048 EXAMPLE)

I DETERMINE COOLING AND HEATING REQUIRE- MENTS AT DESIGN CONDITIONS.

Given:

Required Cooling Capacity (TC). . . . . . . . . . . 38,000 Btuh Sensible Heat Capacity (SHC) . . . . . . . . . . . . 24,000 Btuh Required Heating Capacity. . . . . . . . . . . . . . . 35,000 Btuh Outdoor Entering-Air Temperature . . . . . . . . . . . . . . . 95 F Outdoor-Air Winter Design Temperature . . . . . . . . . . 0° F Indoor-Air Winter Design Temperature . . . . . . . . . . . . 70 F Indoor Entering-Air

Temperature . . . . . . . . 80 F edb (entering air, dry bulb), 67 F ewb (entering air, wet bulb)

Indoor-Air Quantity . . . . . . . . . . . . . . . . . . . . . . . 1600 cfm External Static Pressure . . . . . . . . . . . . . . . . . . 0.45 in. wg Electrical Characteristics (V-Ph-Hz) . . . . . . . . . . 230-3-60

II SELECT UNIT BASED ON REQUIRED COOLING

CAPACITY.

Enter Cooling Capacities table at outdoor entering temper-

IV DETERMINE FAN SPEED AND POWER REQUIRE- MENTS AT DESIGN CONDITIONS.

Before entering Fan Performance tables, calculate the total static pressure required based on unit components. From the given and the Pressure Drop tables, find:

External static pressure

.45 in. wg

Durablade economizer

.05 in. wg

Electric heat

.09 in. wg

Total static pressure

.59 in. wg

Enter the Fan Performance table for 549B048 vertical dis- charge. At 1600 cfm and 230-v, the standard motor will deliver 1.2 in. wg static pressure and 1.15 brake horse- power (bhp). This will adequately handle job requirements.

NOTE: Convert bhp to Watts using the formula below and the motor efficiency found in the Indoor-Fan Motor Data table.

For this example:

ature of 95 F, indoor air entering at 1600 cfm and 67 F

Watts =

746 x Bhp

549B036-120

ewb. The 549B048 unit will provide a total cooling

capacity of 47,400 Btuh and a sensible heat capacity of

32,800 Btuh.

For indoor-air temperature other than 80 F edb, calculate

sensible heat capacity correction, as required, using the

formula found in Note 3 following the cooling capacities

tables.

NOTE: Unit ratings are gross capacities and do not include

the effect of indoor-fan motor heat. To calculate net capac-

ities, see Step V.

III SELECT ELECTRIC HEAT.

Enter the Instantaneous and Integrated Heating Ratings

table at 1600 cfm. At 70 F return indoor air and 0° F air

entering outdoor coil, the integrated heating capacity is

20,400 Btuh. (Select integrated heating capacity value

since deductions for outdoor-coil frost and defrosting have

already been made. No correction is required.)

The required heating capacity is 35,000 Btuh. Therefore,

14,600 Btuh (35,000 – 20,400) additional electric heat is

required.

Determine additional electric heat capacity in kW.

14,600 Btuh

= 4.3 kW of heat required.

3413 Btuh/kW

Enter the Electric Heating Capacities table for 549B048 at 208/230, 3 phase. The 6.5-kW heater at 240 v most closely satisfies the heating required. To calculate kW at 230 v, use the Multiplication Factors table.

6.5 kW x .92 = 5.98 kW

6.5 kW x .92 x 3413 = 20,410 Btuh

Total unit heating capacity is 40,810 Btuh (20,400 + 20,410).

Motor Efficiency

746 x 1.15

Watts =

.75

Watts = 1144

VDETERMINE NET CAPACITIES.

Capacities are gross and do not include the effect of indoor-fan motor (IFM) heat.

Determine net cooling capacity as follows:

Net capacity = Total capacity – IFM heat

=47,400 Btuh – (1144 Watts x 3.413 Btuh/Watts)

=47,400 Btuh – 3904 Btuh

=43,496

Net sensible capacity = 32,800 Btuh – 3904 Btuh = 28,896 Btuh

Integrated heating capacity is maximum (instantaneous) capacity less the effect of frost on the outdoor coil and the heat required to defrost it. Therefore, net capacity is equal to 40,810 Btuh, the total heating capacity determined in Step III.

74

Image 74
Contents 548F036-072 548F090-120 549B036-072 549B090-120 FEATURES/BENEFITS542J150,180 Table of Contents INDOOR-AIR Quality Begins with Bryant Rooftops Service OptionsIntegrated ECONOMI$ERS and Outdoor AIR Options and Accessories Option ACCESSORY†LOW Ambient Controls Options and AccessoriesBarometric RELIEF/POWER Exhaust Emergency Heat Control PackageElectric Heaters DURA-SHIELDOUTDOOR Coil OptionsOutdoor Coil Protection Applications ECONOMI$ER Microprocessor ControllerConvenience Outlet Glycol Coil 150,180 onlyCompressor Hinged Panel Option Hail GuardBryant Commercial Programmable Thermostat Control BOX Hinged Panel OptionOptions and Accessories Controls Cooling, Units With EconoMi$er 548F036-072 and 549B036Controls Sequence of Operation 542J150,180Controls Typical Smoke Control/Fire Shutdown Wiring 542J150,180 Operating ModesApplication Data Concentric Duct Details 542J150,180 Application DataConcentric Duct Distribution 542J150,180 Vertical Discharge Ducting 548F036-120 and 549B036-120 Typical Piping and WiringHorizontal Discharge Ducting 548F036-120 and 549B036-120 Typical Piping and Wiring ARI* Capacity Ratings Model Number Nomenclature 548F UnitsODS Model Number Physical Data 548F036-072Physical Data 548F090-120072-548F036 Base Unit Dimensions Roof Curb Unit Size Accessory CRRFCURB001A00 Accessory DimensionsConnector ALT GAS Power Control PKG. Accy Drain Hole CRRFCURB002A00Accessory Dimensions II Select Unit Based on Required Cooling Capacity Selection Procedure with 548F048 ExampleDetermine Cooling and Heating Loads AT Design Conditions III Select Electric HeatSHC Performance DataCooling Capacities Entering AIR DRY-BULB Temp FEntering AIR DRY-BULB Temp F Bypass Performance DataCooling Capacities 4100/0.18 4700/0.21 Air Temperature Entering Outdoor Coil FInstantaneous and Integrated Heating Ratings UnderInstantaneous and Integrated Heating Ratings 3000 Cap 1800 Cap2400 Cap 2600 Cap3600 Cap CfmStandard Air 2400 Cap 4000 CapESP FAN Performance Vertical Discharge Units548F036 3 Tons Standard Motor Direct Drive 548F036 3 Tons Alternate Motor Belt DriveFAN Performance Vertical Discharge Units 548F048 4 Tons Alternate Motor Belt Drive548F060 5 Tons Alternate Motor Belt Drive 548F060 5 Tons Standard Motor Direct DriveESP 548F060 5 Tons HIGH-STATIC Motor Belt Drive 548F072 6 Tons HIGH-STATIC Motor Belt Drive 518 562 Rpm Bhp Watts511 539 534 607548F090 71/2 Tons HIGH-STATIC Motor Belt Drive 548F102 8 TONS* Standard Motor Belt Drive 548F102 81/2 Tons HIGH-STATIC Motor Belt Drive 963 2651 548F120 10 TonsRpm Bhp 973 2782Cfm Rpm Bhp Watts FAN Performance Horizontal Discharge UnitsAirflow Low Speed High Speed Cfm 208 230, 460, 575 FAN Performance Horizontal Discharge Units 548F048 4 Tons Alternate Motor Belt Drive729 388 787 450 895 593 658 276 722 337 840 470693 327 754 388 867 531 765 460 821 521548F060 5 Tons HIGH-STATIC Motor Belt Drive 548F072 6 Tons Standard Motor Belt Drive1900 982 779 1084 932 1160 1006 Rpm Bhp Watts 1800 942 700 1047 835 1139 9561031 1276 11142400 482 524 569 684 Rpm Bhp Watts 2250 465 473 554 6302300 471 487 559 646 2500 494 554 581 7232400 528 600 606 779 674 965 738 1199 795 Rpm Bhp Watts 2250 507 547 586 700 658 891 722 1097 7832300 513 562 592 723 663 916 727 1131 786 2500 542 648 619 835 686 1022 748 1258 806548F102 81/2 Tons Standard Motor Belt Drive 3100 636 1006 704 1241 764 1499 818 1744 Rpm Bhp Watts 2550 669 627 867 692 1056 754 1292 8122900 604 867 676 1089 737 1318 794 1560 848 3200 652 1089 718 1327 778 1595 831 1849General Notes for FAN Performance Tables FAN RPM AT Motor Pulley SETTINGS* 548F036-120 ACCESSORY/FIOP Static PRESSURE* in. wg 548F036-072ACCESSORY/FIOP Static PRESSURE* in. wg 548F090-120 Component CFMPower Requirements Optional Power ExhaustEconoMi$er Barometric Relief Damper Characteristics Mocp SizeHeater Rating Electric Heating CapacitiesMultiplication Factors DistributionOperating Watts AMP Draw Efficiency % INDOOR-FAN Motor Performance 548F UnitsUnit INDOOR-FAN Maximum Acceptable Motor 090Electrical Data Units Without Electrical Convenience OutletElectrical Data Units Without Electrical Convenience OutletOFM IFM SIZE† Voltage Compressor Electric Heat Power Supply DisconnectNominal IFM Range Tons81/2 Tons Units with Electrical Convenience Outlet Units with Electrical Convenience Outlet 40.4 45†† 195/195 13.6/15.6 57.4 59.9 60†† 208/211 Voltage Compressor Electric Power Supply Disconnect Unbalanced 3-Phase Supply Voltage Typical Wiring Schematic SW4Typical Wiring Schematic Outdoor-Fan Motor549B036-060 Model Number Nomenclature549B E X 090 000 AA 549B072-120549B036-072 Base Unit 549B549B090,120 Base Unit Dimensions 549B036-120 549B090,120 ′-0 ″ ′-2 ″549B036-072 ″ 19 NPT 827 583 44.5 12.7 NPT Capacity Selection Procedure with 549B048 ExampleII Select Unit Based on Required Cooling Enter Cooling Capacities table at outdoor entering temperFactor SHCEntering AIR DRY-BULB Temp F Bypass 549B090 71/2 Tons Temp F 549B072 6 Tons Temp F1800/0.06 2100/0.066 2400/0.071 3000/0.088 Entering Air 2250/0.12 3000/0.15 3750/0.18 Entering Air549B048 4 Tons 549B036 3 Tons900 Cap 2100 Cap 549B060 5 Tons549B072 6 Tons 549B120 10 Tons Temperature Air Entering Outdoor Coil F db at 70% rh549B090 71/2 Tons 709 782 835 900 937 1100 Rpm Bhp 900673 736 805 865 911 1000 746 806 867 929 964 1200549B060 5 Tons Standard Motor Belt Drive 549B072 6 Tons Standard Motor Belt Drive549B090 71/2 Tons Standard Motor Belt Drive 549B120 10 Tons Standard Motor Belt Drive 670 758 812 863 914 1200 584 656 734 818 875 1000627 738 800 848 895 1100 710 780 840 889 938 13001372 Cfm Rpm Bhp 1500 1108 1187 1202 10792100 1252 1320 1388 1448 Airflow External Static Pressure in. wg635 699 Rpm Bhp 2250630 695 645 708615 679 734 787 595 657 716 770605 667 725 779 625 691 744 796FAN RPM AT Motor Pulley SETTINGS* 549B036-120 ACCESSORY/FIOP Static PRESSURE* in. wg 549B036-072ACCESSORY/FIOP Static PRESSURE* in. wg 549B090,120 549B 036INDOOR-FAN Motor Data 549B036-120 Outdoor Sound Power Total Unit Electric Heating CapacitiesRLA LRA Nominal Voltage Electric Power Minimum Unit Compressor OFMDisconnect Voltage Range Heat Supply FLA MCA Mocp LRAPh-Hz Min Max Nominal Voltage Electric Power Minimum Unit CompressorIFM Disconnect Voltage Range Heat Supply RLA LRA FLA30.4 106/106 43.0 247/247 10.4 21.7 25.0 70.1 74.3 269/272 Typical Wiring Schematic Potter & Brunfield Amps MustRating HFG. PT. no Trip RVSPart 2 Products Guide Specifications 548F and 549B036-120 UnitsPart 1 General Guide Specifications 548F and 549B036-120 Units Guide Specifications 548F and 549B036-120 Units 100 Model Number Nomenclature 542J150,180 Units 542J E X 150 000 AB H B542J150,180 Units Weight Distribution and Center of GravityUnit Weight Weight of Corner Dimensions Cooling HEATING-HIGH Temp HEATING-LOW Temp Sound UnitALT Unit 542JSTD STD ALTUnit Weight of Corner Unit Maximum Shipping WeightUnit Dimensions 542J 150 1895 860 180 2205 1000CRRFCURB011A00 DIMENSIONS* degrees and inchesPKG NO. REF Curb Description Height CRRFCURB010A00 CRRFCURB012A00Convenience Outlet 542J150,180 Horizontal Adapter Installation 542J150,180Accessory Curb Description HeightPower Exhaust 542J150,180 Non-Fused Disconnect 542J150,180Selection Procedure with 542J180 Example Capacity TC of 180,800 Btuh, a sensible heat capacity542J150 Temp F Air Entering Indoor Coil Cfm/BF 542J180CFM Integrated Heating Capacities5625 General Notes for FAN Performance Tables Fan Performance Using Accessory Power Exhaust ACCESSORY/FIOP Static PRESSURE* in. wg 542J150,180FAN RPM AT Motor Pulley SETTINGS* 542J150,180 ACCESSORY/FIOP Unit Size Unit Voltage CFMGlycol Coil Ratings Electric Heating Capacities 542J150,180Glycol Coil Data INDOOR-FAN Motor Performance 542J150,180 542J180, 460-3-60 Shown LPS BKR W/ATLOR CAPOptional Non-Fused Disconnect 542J150,180 Part 2 Products Guide Specifications 542J150,180 UnitsPart 1 General Guide Specifications 542J150,180 Units 120 121 Index 95,96
Related manuals
Manual 4 pages 35.17 Kb

549B, 548F, 542J specifications

Bryant 542J is a high-efficiency gas furnace that stands out for its reliability and advanced heating technologies. Designed to deliver consistent warmth and comfort in residential settings, it combines innovative engineering with energy-efficient features.

One of the key characteristics of the Bryant 542J is its two-stage heating capability. This means that the furnace can adjust its heat output according to the heating demands of your home. During milder weather, it operates at a lower stage, consuming less energy while still maintaining a comfortable environment. When the temperatures drop, the furnace shifts to its higher capacity, providing the necessary warmth efficiently. This not only enhances comfort but also contributes to lower energy bills.

In addition to its two-stage operation, the Bryant 542J also incorporates a variable-speed blower motor. This technology allows the furnace to adjust the airflow depending on the heating requirements, ensuring an even distribution of warm air throughout the home. The variable-speed blower also operates more quietly than conventional fixed-speed motors, creating a serene indoor environment.

Energy efficiency is a hallmark of the Bryant 542J, boasting an Annual Fuel Utilization Efficiency (AFUE) rating of up to 96.5%. This impressive rating means that a significant portion of the energy consumed is effectively converted into usable heat, resulting in substantial savings on heating costs over time. Furthermore, the furnace is equipped with a sealed combustion system that draws air from outside the home, minimizing energy waste and improving indoor air quality.

Diagnostic features are another highlight of the Bryant 542J, which come equipped with SmartEvap technology. This allows the unit to self-diagnose potential issues, providing homeowners with peace of mind and simplifying maintenance procedures.

Durability is also a key feature of the Bryant 542J. It is constructed with high-quality materials designed to withstand harsh winter conditions, ensuring a long lifespan and reliable performance. Its compact design also allows for flexible installation, making it suitable for various residential layouts.

In summary, the Bryant 542J is more than just a gas furnace; it is a sophisticated heating solution that combines efficiency, comfort, and reliability. With features such as two-stage heating, a variable-speed blower, high AFUE ratings, and advanced diagnostics, it is an excellent choice for homeowners seeking an efficient and effective heating system.