3-7. Electrical Service Guide
NOTE
Actual input voltage should not exceed ± 10% of indicated required input voltage. If actual input voltage is outside of this range, output may not be available.
Input Voltage | 460 |
|
|
Input Amperes At Rated Output | 18.5 |
|
|
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes | 30 |
|
|
Reference: 1996 National Electrical Code (NEC). | |
|
|
3-8. Connecting Input Power
Check input voltage available at site.
1 Input And Grounding
Conductors
2 Line Disconnect Device
Select type and size of overcurrent protection using Section
Y Always connect green/yel- low wire to supply ground- ing terminal, never to a line terminal.
2
L1
L2
L3
Green
1
YAlways connect grounding conductor first.
1
= GND/PE
Tools Needed:
Input_9_99 / Ref.