Miller Electric OM-494 manual Power Required To Start Motor, How Much Power Can Generator Supply?

Page 59

11-8. Power Required To Start Motor

4

 

 

 

 

 

 

 

AC MOTOR

 

2

1

 

 

 

 

VOLTS

230

AMPS

2.5

 

 

3

 

CODE

M

Hz

60

 

 

 

HP

1/4

PHASE 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-Phase Induction Motor Starting Requirements

Motor Start

G

 

H

J

K

L

M

 

N

 

P

Code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA/HP

6.3

 

7.1

8.0

9.0

10.0

11.2

 

12.5

 

14.0

 

 

 

 

 

 

 

 

 

 

 

kVA/HP x HP x 1000 = STARTING AMPERAGE

 

 

 

 

VOLTS

 

 

 

 

 

 

 

 

EXAMPLE: Calculate the starting amperage required for a 230 V, 1/4

 

HP motor with a motor start code of M.

 

 

 

 

 

 

Volts = 230

HP = 1/4 Using Table, Code M results in kVA/HP = 11.2

11.2 x 1/4 x 1000

= 12.2 A

Starting the motor requires 12.2 amperes.

230

 

 

 

 

 

 

 

 

 

 

 

1Motor Start Code

2Running Amperage

3Motor HP

4Motor Voltage

To find starting amperage:

Step 1: Find code and use table to find kVA/HP. If code is not listed, multiply running amperage by six to find starting amperage.

Step 2: Find Motor HP and Volts.

Step 3: Determine starting amper- age (see example).

Welding generator amperage out- put must be at least twice the motor’s running amperage.

S-0624

11-9. How Much Power Can Generator Supply?

1

2

1Limit Load To 90% Of Generator Output

Always start non-resistive (motor) loads in order from largest to small- est, and add resistive loads last.

2 5 Second Rule

If motor does not start within 5 seconds, turn off power to prevent motor damage. Motor requires more power than generator can supply.

Ref. ST-800 396-A / S-0625

OM-494 Page 55

Image 59
Contents Dual-Operator Engine Driven Welding Generator ProcessesDescription Visit our website at OM-494191 862P JanuaryFrom Miller to You Table of Contents Options and Accessories Warranty Arc Welding Hazards Symbol UsageEngine Hazards Compressed Air Hazards Radiation can cause interference Principal Safety StandardsCalifornia Proposition 65 Warnings EMF InformationLES Fumées ET LES GAZ peuvent être dangereux Signification des symboles− Consignes DE Sécurité − Lire Avant Utilisation UN Choc Électrique peut tuerLE Bruit peut affecter l’ouïe LE Soudage peut provoquer un in- cendie ou une explosionDES Particules Volantes peuvent blesser les yeux DES Pièces Chaudes peuvent provoquer des brûlures graves’AIR Comprimé peut provoquer des blessures ’EXPLOSION DE LA Batterie peutDES Organes Mobiles peuvent provoquer des blessures LA Chaleur DU Moteur peut pro- voquer un incendieInformation sur les champs électromagnétiques Principales normes de sécurité− Definitions Symbols And DefinitionsDescription − SpecificationsWeld, Power, And Engine Specifications Dimensions, Weights, And Operating AnglesFuel Consumption AC Generator PowerReduce Duty Cycle Minutes Exceeding duty cycle can damage unit and void warrantyDuty Cycle And Overheating OverheatingVolt-Ampere Curves CC/DC − Single ModeCC/DC − Dual Mode CV/DC ModeInstalling Welding Generator − InstallationCharger Activating The Dry Charge BatteryDo not overfill battery cells Read and follow all instrucTop View Tools Needed 1/2 Connecting The BatteryInstalling Exhaust Pipe Connect − Cable LastOil Engine Prestart ChecksFuel Do not use gasoline. Gaso Line will damage engine Welder a Left Side Welder B Right Side Safety Information For Connecting To Weld Output TerminalsWeld Output Terminals Unexpected Weld Output can cause injury or fireDo not exceed machine duty cycle Welder a Left SideConnect electrode holder cables to Elec- trode receptacles Stop engine Do not exceed machine duty cycleSwitches are set correctly. See Section Place optional Polarity switches in ReVerse position when using CV weld re When switch is in Straight positionConnect wire feeder cables to CV recep- tacles Connect wire feeder cables to Negative − terminalsBe sure Process Selector switches are Place optional Polarity switch in Re Making Single Operator CC Weld Connections Put terminals Selecting Weld Cable Sizes150 ft 200 ft 250 ft 350 ft 400 ft 45 m 60 m 70 m 90 m 105 m 120 mSocket Information Installing Ether Cylinder Optional Ether Starting AidAfter installing cylinder, wait at Remote 14 Receptacle InformationDual Operator Operation Remote 14 Receptacle ConnectionsIf light goes on, stop engine and check engine belt − Operating the Welding GeneratorEngine Controls See -3for weld control descriptionsWeld Controls See Section CV weld output for MIG is only available Do not switch under load or with out- put onDo not switch under load Weld Control Descriptions See Section− Operating Auxiliary Equipment − Maintenance & TroubleshootingEvery 500 h Every 100 hEvery 200 h Every 250 hMaintenance Label Do not clean housing with air hose Servicing Air CleanerBy the warranty To clean air filterServicing Fuel And Lubrication Systems Cylinder Adjusting Engine SpeedWeld/Power 1850 Servicing Optional Ether Starting AidStop engine To check belt tension To adjust belt tensionChecking And Replacing Alternator Belt Max Tools Needed 11/16Resetting Fan Belt Safety Shutdown Reinstall cleanout plug Tools Needed 3/8 Inspecting And Cleaning Optional Spark Arrestor MufflerThermostats TP3 And TP4 Internal − Not Shown Circuit ProtectionWelding TroubleshootingFormers T5 thru T10, and control board PC1 or PC5 Factory Authorized Service Agent check main rectifier SR2Factory Authorized Service Agent check main rectifier SR3 Repair or replace wire feederEngine Generator PowerOM-494 Circuit Diagram For Welding Generator − Electrical Diagrams210 657-A Ment damage may occur − RUN-IN ProcedureWetstacking Ing run-in add oil if needed Run-In Procedure Using Load Bank4exceed duty cycle or equip- ment damage may occur Check oil level frequently durFrom flammables Run-In Procedure Using Resistance GridProcedure at less than Bank/gridGrounding Generator To Truck Or Trailer Frame − Generator Power GuidelinesHas this symbol Selecting Equipment Use ground device as stated Electrical codes Grounding When Supplying Building Systems How Much Power Does Equipment Require? Earth ground if supplyingFarm/Home Equipment Rating Starting Watts Running Watts Approximate Power Requirements For Industrial MotorsApproximate Power Requirements For Farm/Home Equipment Industrial Motors Rating Starting Watts Running WattsContractor Rating Starting Watts Running Watts Approximate Power Requirements For Contractor EquipmentKVA/HP x HP x 1000 = Starting Amperage Power Required To Start MotorHow Much Power Can Generator Supply? Single-Phase Induction Motor Starting RequirementsTypical Connections To Supply Standby Power Current Load Watts Amperes Selecting Extension Cord Use Shortest Cord Possible311 103 96−SEE -2 101 25−SEE FIG 910 − Parts List4748 57−SEE FIG 78−SEE FIG Item Dia Part Description Quantity Mkgs 189 Front Panel Front Panel -1Item Side Control Panels − Welder B Right Side Shown Side Control Panels -1Item Side Control Panels Generator Rectifier Assembly OM-494 Page Support ServiceYour distributor also gives Your distributor and/or equipment manufacturer’s To locate a Distributor or Service Agency visitMiller Electric Mfg. Co For assistance in filing or settling claims, contact