11-6. In Case Refrigerant is Leaking

CAUTION

Never attempt to charge additional refrigerant when refrigerant has been leaking from the unit. Follow the procedure described below to locate points of leaks and carry out repairs, then recharge the refrigerant.

(1) Detecting Leaks

Use the detector for R410A to locate refrigerant leak points.

(2) Recovering refrigerant

Never release the gas to the atmosphere; recover residual refrigerant using the refrigerant recovery unit for R410A, instead.

Do not reuse the recovered refrigerant because its composition will have been altered.

(3) Welding leaking points

Confirm again that no residual refrigerant exists in the unit before starting welding.

Weld securely using flux and wax for R410A.

Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen (N2) in the refrigerant circuit of the unit. Leave ends of tubes open during welding.

(4) Checking for sealing

Use nitrogen gas for the pressurized gas, and never use a refrigerant other than R410A. Also do not use oxygen or any flammable gas.

(5) Evacuation

Use a solenoid valve-installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption, the valve will prevent the pump oil from flowing back.

The equipment may be damaged if moisture remains in the tubing, thus carry out the evacuation thoroughly.

When using a vacuum pump with exhaust air volume more than 0.883 cu.ft./min. and ultimate vacuum pressure rate of 50 micron Hg.

(1) Detect leaks

OK

(2)Recover refrigerant

OK

(3)Weld leaking points

OK

(4)Check for sealing

OK

(5)Evacuation

OK

(6) Recharge

Standard time for evacuation

Length of tubing

Less than 33 ft. (10 m)

More than 33 ft. (10 m)

Evacuation time

More than 10 minutes

More than 15 minutes

(6) Recharging

Recharge unit in the same manner explained on the previous page "(5) Recharging."

59

Image 59
Contents Indoor Model No. Product Code No DC Inverter Split System AIR ConditionerPlease Read Before Starting Table of Contents Checking Electrical Components Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeCH1872 SpecificationsUnit Specifications KHS1872208V CH2472 KHS247212.1 13.5 Indoor Unit Major Component SpecificationsCB-KHS2472 Microprocessor 250V 3A External Finish Outdoor UnitOutdoor Unit CH1872 CompressorOutdoor Unit CH2472 Outdoor air temp sensor Other Component SpecificationsIndoor heat exchanger sensor Compressor temp sensorIndoor Unit KHS1872 Dimensional Data11-17/32 23-15/16 35-7/16900 After a tube has been insulated To break or crack Refrigerant Flow DiagramRefrigerant Flow Diagram Insulation of Refrigerant TubingIndoor discharge air performance chart Temperature ChartsLow pressure performance chart Operating current performance chartHigh pressure performance chart Wide 73F Cooling Capacity Power Supply 230V Single Phase 60Hz Cooling Capacity24,200 BTU/h Indoor Outdoor Cooling Capacity Low Ambient24,200 BTU/h TH Total Heating Capacity BTU/h Power Supply 230V Single Phase 60Hz Heating CapacityHeating Capacity 29,000 BTU/h Heating Vertical distance ft Air Throw Distance ChartsCooling Vertical distance ft Room air temp F 26.7C Fan speed High Horizontal distance ftHeating Voltage208V Cooling Electrical CharacteristicsElectrical Data CH1872 Voltage230V CoolingCH2472 Voltage230V Cooling 8FA2-5257-70500-0 Electric Wiring DiagramsIndoor Unit KHS1872 KHS2472 WHT WHT YEL YEL Button Operation HR.TIMER button ACL Reset button MaintenanceAddress Setting of the Remote Control Unit How to Connect How to DisconnectAuto cooling/heating operation FunctionsOperation Functions Emergency operationLamp colors Timer backupFreeze prevention Compressor discharge temperature controlProtective Functions Overload prevention during heatingReverse-Cycle Defrosting Defrost detection and releaseCT Peak current cut-off control Method of Self-Diagnostics TroubleshootingPrecautions before Performing Inspection or Repair Self-diagnostics Lamps Replace the circuit board or the fuse NormalReplace the controller Checking the indoor unit Control Check items unit operation Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Condition E01 Serial Communication Error Identification ProcedureOff Blinking Illuminated Before the OperationTerminal board Outdoor Unit Condition E12 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Locations most susceptible to noise Trouble Correction Noise Malfunction and Electromagnetic InterferenceNoise malfunction Electromagnetic interferenceMeasurement of Insulation Resistance for Electrical Parts Power Supply CordChecking Electrical Components Measurement of Insulation ResistanceChecking Continuity of Fuse on PCB Assy Characteristics Refrigerant R410A Special Precautions When Servicing UnitCharacteristics of New Refrigerant R410A What is New Refrigerant R410A?Checklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorExample Never charge a large amountUnit. This may cause Damage to the compressorRecharging Case Refrigerant is LeakingWelding leaking points Use of Existing Units When Tubes are ExtendedCharging Additional Refrigerant Retro-Fitting Existing SystemsOI-852-6-4180-801-00-2 Features Product Information ContentsAlert Symbols Electrical Requirements Installation LocationSafety Instructions Names of Parts Quiet lamp Unit Display and Operation ButtonRemote Control Unit Display Transmitter Remote Control UnitHR. Timer button Advance buttonFAN Speed selector button Quiet buttonButton Time Display Selector button Using the Remote Control UnitTemperature Display Selector How to Install BatteriesUsing the Remote Control Unit Press the ON/OFF operation button Operation with the Remote Control UnitSet the FAN Speed selector button to the setting you want Operation with the Remote Control UnitPress the Mode selector button and select the desired mode Press the TEMP. setting buttons to change the temperatureAdjusting the Fan Speed Night Setback Mode is used for saving energy Cooling and DRY ModeQuiet Mode Special Remarks Operation Indication Setting the TimerExample To set to 1030 pm 1030 pm 710 am 1100 am Present time Setting the TimerHow to set the on time Example To start operation at 710 am To cancel a timer program Press the Cancel buttonOperation together with the Daily ON/OFF Repeat Timer Using the 1-Hour OFF TimerSetting procedure Cancellation procedureSweep function Adjusting the Airflow DirectionSetting the airflow manually HorizontalWhen the air conditioner is not running Operation without the Remote Control UnitCare and Cleaning Intake grille Care and CleaningCleaning Grasp both ends of the airNegative ion generator metal electrodes inside plastic case Follow the steps below when the generator has become dirtyMax DB / 71 F WB Min DB / 57 F WB TroubleshootingOperating Range Trouble Possible Cause RemedyAppendix B Installation Instructions Contents Installation InstructionsPlease Read Before Starting Optional Copper Tubing Kit Tools Required for Installation not suppliedAccessories Supplied with Unit Table GeneralAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate Make a Hole How to Install the Indoor UnitTrical wiring or conduits are Remove the Rear Panel from the UnitIf Block, Brick, Concrete or Similar Type Wall Install the Rear Panel on the WallIf Wooden Wall How to replace the grille Remove the Grille to Install the Indoor UnitHow to remove the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringAWG Recommended Wire Length and DiameterWiring Instructions for Inter-unit Connections For stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit For solid core wiring or F-cable Right-side tubing MountingDrain cap Switching drain hose and drain capLeft-side tubing Unit or operate it until all Do not supply power toTubing and wiring to the out To unmount indoor unitWiring Instructions for the Outdoor Unit How to Install the Outdoor UnitFirst refer to . Installation Site Selection Use of the Flaring Method Flaring Procedure with a Flare ToolTo 0.5 mm Adjust so that the amount of tube Refrigerant TubingTo prevent heat loss and wet floors due to dripping of con Connecting Tubing between Indoor and Outdoor UnitsFinishing the Installation Insulation of Refrigerant TubingAir Purging Attempting to turn the valve Be sure to completely insertHex wrench before How to Test Run the Air Conditioner Pump Down Basic Functions of the Service ValvesWhen opening or clos Ing the service valve Stem, use the accessoryMounting on a Wall Remote Control Unit Installation PositionAddress Setting of the Remote Control Unit Address Switch