Sanyo CH1872 Adjusting the Airflow Direction, Horizontal, Sweep function, Auto flap function

Page 81

Adjusting the Airflow Direction

1. Horizontal

CAUTION

The horizontal airflow can be adjusted by moving the vertical vanes with your hands to the left or right.

When the humidity is high, the vertical vanes should be in the front position during the cooling or dehumidifying operation. If the vertical vanes are positioned all of the way to the right or left, condensation may begin to form around the air vent and drip down.

2.Vertical The vertical airflow can be adjusted by moving the flap with the remote control unit. Do not move the flap with your hands. Confirm that the remote control unit has been turned on. Use the FLAP button to set either the sweep function or one of the six airflow direction settings.

A. Sweep function

The flap starts moving up and down to deliver air over the sweep range.

C. Auto flap function

The flap is set to the recommended position.

COOL

SWEEP

DRY

FAN

SWEEP

HEAT

B. Setting the airflow manually

Referring to the above illustration, use the FLAP button to set the airflow direction within the range used during the heating, cooling, or dehumidifying operation.

NOTE

CAUTION

The flap automatically closes when the unit is off.

During the heating operation, the fan speed will be very low and the flap will be in the horizontal position (position ) until the air being blown out of the unit begins to warm. Once the air warms up, the flap position and fan speed change to the settings specified with the remote control.

Use the FLAP button on the remote control to adjust the position of the flap. If you move the flap by hand, the flap position according to the remote control and the actual flap position may no longer match. If this should happen, shut off the unit, wait for the flap to close, and then turn on the unit again; the flap position will now be normal again.

Do not have the flap pointed down during cooling operation. Condensation may begin to form around the air vent and drip down.

OI-801-21EG

21

 

Image 81
Contents Indoor Model No. Product Code No DC Inverter Split System AIR ConditionerPlease Read Before Starting Table of Contents Checking Electrical Components Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeUnit Specifications SpecificationsKHS1872 CH1872208V CH2472 KHS247212.1 13.5 Indoor Unit Major Component SpecificationsCB-KHS2472 Microprocessor 250V 3A Outdoor Unit CH1872 Outdoor UnitCompressor External FinishOutdoor Unit CH2472 Indoor heat exchanger sensor Other Component SpecificationsCompressor temp sensor Outdoor air temp sensorIndoor Unit KHS1872 Dimensional Data11-17/32 23-15/16 35-7/16900 Refrigerant Flow Diagram Refrigerant Flow DiagramInsulation of Refrigerant Tubing After a tube has been insulated To break or crackLow pressure performance chart Temperature ChartsOperating current performance chart Indoor discharge air performance chartHigh pressure performance chart Wide 73F Cooling Capacity Power Supply 230V Single Phase 60Hz Cooling Capacity24,200 BTU/h Indoor Outdoor Cooling Capacity Low Ambient24,200 BTU/h Power Supply 230V Single Phase 60Hz Heating Capacity Heating CapacityTH Total Heating Capacity BTU/h 29,000 BTU/h Cooling Vertical distance ft Air Throw Distance ChartsRoom air temp F 26.7C Fan speed High Horizontal distance ft Heating Vertical distance ftHeating Electrical Data Electrical CharacteristicsCH1872 Voltage230V Cooling Voltage208V CoolingCH2472 Voltage230V Cooling Electric Wiring Diagrams Indoor Unit KHS1872 KHS24728FA2-5257-70500-0 WHT WHT YEL YEL Maintenance Address Setting of the Remote Control UnitButton Operation HR.TIMER button ACL Reset button How to Connect How to DisconnectOperation Functions FunctionsEmergency operation Auto cooling/heating operationLamp colors Timer backupProtective Functions Compressor discharge temperature controlOverload prevention during heating Freeze preventionDefrost detection and release CT Peak current cut-off controlReverse-Cycle Defrosting Troubleshooting Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Self-diagnostics Lamps Normal Replace the controllerReplace the circuit board or the fuse Using the TEST/T-RUN terminals Checking the Indoor and Outdoor UnitsChecking the indoor unit Control Check items unit operation Off Blinking Illuminated Serial Communication Error Identification ProcedureBefore the Operation Condition E01Terminal board Outdoor Unit Condition E12 Indoor Fan Motor Trouble Diagnosis of Fan MotorOutdoor Fan Motor Noise malfunction Noise Malfunction and Electromagnetic InterferenceElectromagnetic interference Locations most susceptible to noise Trouble CorrectionChecking Electrical Components Power Supply CordMeasurement of Insulation Resistance Measurement of Insulation Resistance for Electrical PartsChecking Continuity of Fuse on PCB Assy Characteristics of New Refrigerant R410A Refrigerant R410A Special Precautions When Servicing UnitWhat is New Refrigerant R410A? CharacteristicsChecklist before Servicing Tools Specifically for R410A Tubing Installation ProceduresCase of Compressor Malfunction Procedure for Replacing CompressorUnit. This may cause Never charge a large amountDamage to the compressor ExampleCase Refrigerant is Leaking Welding leaking pointsRecharging Charging Additional Refrigerant When Tubes are ExtendedRetro-Fitting Existing Systems Use of Existing UnitsOI-852-6-4180-801-00-2 Features Contents Alert SymbolsProduct Information Installation Location Safety InstructionsElectrical Requirements Names of Parts Quiet lamp Unit Display and Operation ButtonRemote Control Unit Display HR. Timer button Remote Control UnitAdvance button TransmitterFAN Speed selector button Quiet buttonTemperature Display Selector Using the Remote Control UnitHow to Install Batteries Button Time Display Selector buttonUsing the Remote Control Unit Press the ON/OFF operation button Operation with the Remote Control UnitPress the Mode selector button and select the desired mode Operation with the Remote Control UnitPress the TEMP. setting buttons to change the temperature Set the FAN Speed selector button to the setting you wantAdjusting the Fan Speed Night Setback Mode is used for saving energy Cooling and DRY ModeQuiet Mode Special Remarks Setting the Timer Example To set to 1030 pmOperation Indication How to set the on time Example To start operation at 710 am Setting the TimerTo cancel a timer program Press the Cancel button 1030 pm 710 am 1100 am Present timeSetting procedure Using the 1-Hour OFF TimerCancellation procedure Operation together with the Daily ON/OFF Repeat TimerSetting the airflow manually Adjusting the Airflow DirectionHorizontal Sweep functionOperation without the Remote Control Unit Care and CleaningWhen the air conditioner is not running Cleaning Care and CleaningGrasp both ends of the air Intake grilleNegative ion generator metal electrodes inside plastic case Follow the steps below when the generator has become dirtyOperating Range TroubleshootingTrouble Possible Cause Remedy Max DB / 71 F WB Min DB / 57 F WBAppendix B Installation Instructions Contents Installation InstructionsPlease Read Before Starting Accessories Supplied with Unit Table Tools Required for Installation not suppliedGeneral Optional Copper Tubing KitAdditional Materials Required for Installation Installation Site SelectionSolid base must not cover the hole of the bottom plate Trical wiring or conduits are How to Install the Indoor UnitRemove the Rear Panel from the Unit Make a HoleInstall the Rear Panel on the Wall If Wooden WallIf Block, Brick, Concrete or Similar Type Wall Remove the Grille to Install the Indoor Unit How to remove the grilleHow to replace the grille Shape the Indoor Side Tubing Wiring Instructions General precautions on wiringAWG Recommended Wire Length and DiameterWiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring Right-side tubing MountingSwitching drain hose and drain cap Left-side tubingDrain cap Tubing and wiring to the out Do not supply power toTo unmount indoor unit Unit or operate it until allHow to Install the Outdoor Unit First refer to . Installation Site SelectionWiring Instructions for the Outdoor Unit To 0.5 mm Adjust so that the amount of tube Flaring Procedure with a Flare ToolRefrigerant Tubing Use of the Flaring MethodFinishing the Installation Connecting Tubing between Indoor and Outdoor UnitsInsulation of Refrigerant Tubing To prevent heat loss and wet floors due to dripping of conAir Purging Be sure to completely insert Hex wrench beforeAttempting to turn the valve How to Test Run the Air Conditioner When opening or clos Ing the service valve Basic Functions of the Service ValvesStem, use the accessory Pump DownMounting on a Wall Remote Control Unit Installation PositionAddress Setting of the Remote Control Unit Address Switch