Sanyo 85464359981002 installation instructions Example, Main tubing Distribution joint tubing

Page 16

Example:

L1

LA

 

 

 

 

 

L2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main tube of unit

 

LB

 

LC

 

LN

 

n

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1st branch

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

2

 

 

3

 

 

 

 

model 1852

 

 

 

 

 

 

 

 

 

Unit distribution tube

 

 

 

 

 

 

n–1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

model 0752

model 0952

model 1252

model 1852

Example of each tubing length

Main tubing

Distribution joint tubing

LA = 131 ft.

Indoor side

 

LB = 16 ft.

1

= 16 ft.

4 = 20 ft.

LC = 16 ft.

2

= 16 ft.

5 = 16 ft.

LD = 49 ft.

3

= 7 ft.

 

Obtain charge amount for each tubing size

Note that the charge amounts per 3.3 ft. are different for each liquid tubing size.

ø3/8" (ø9.52)

LA

+

LB

+

LC + LD

: 212 ft. 0.602 oz/ft.

=

127 oz

ø1/4" (ø6.35)

1

+

2

+

3 + 4 +

5 : 75 ft. 0.279 oz/ft.

=

20 oz

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total

 

147 oz

Additional refrigerant charge amount is 147 oz.

CAUTION

Be sure to check the limit density for the room in which the indoor unit is installed.

Checking of limit density

Density limit is determined on the basis of the size of a room using an indoor unit of minimum capacity. For instance, when an indoor unit is used in a room (floor area 80 ft2 ceiling height 8.8 ft. = room volume 704 ft.3), the graph at right shows that the minimum room volume should be 497 ft.3 (floor area 56 ft.2) for refrigerant of 147 oz. Accordingly, openings such as louvers are required for this room.

<Determination by calculation>

Overall refrigerant charge amount for the air conditioner: oz

(Minimum room volume for indoor unit: ft.3)

=147 (oz) + 123 (oz) = 0.38 (oz/ft.3) > 0.3 (oz/ft.3) 704 (ft.3)

Therefore, openings such as louvers are required for this room.

Min. indoor volume

ft.3

4000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3500

 

Range below

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

the density limit of

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

 

 

 

 

 

 

 

2500

 

(countermeasures

 

 

 

 

 

not needed)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

 

 

 

 

1500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Range above

 

 

 

 

 

 

1000

 

 

 

 

 

the density limit of

 

 

 

 

 

500

 

 

 

 

 

0.3 oz/ft.3

 

 

 

 

 

 

 

(countermeasures

 

 

 

 

 

0

 

 

 

 

 

needed)

 

 

 

 

 

 

 

 

 

 

 

 

 

0

200

400

600

800

1000

 

 

Total amount of refrigerant

ft.2

454

398

341

area

 

284

floor

227

indoor

170

 

114

Min.

 

 

57

 

 

 

0

 

1200

 

 

oz

 

(when the ceiling is 8.8 ft. high)

16

Image 16
Contents Outdoor Units R410A Models Indoor UnitsOptional Controllers Special Precautions …In a Room…In Moist or Uneven Locations …In an Area with High WindsCheck of Density Limit Care regarding tubing Be sure to recharge the refrigerant only in liquid formDifferent tools required Manifold gauge Vacuum pumpCompressor specifications are different Single-outlet valveExisting tubing cannot be used especially R22 R410AContents HOW to Process Tubing AIR PurgingTest RUN AppendixGeneral 1-Way Air Discharge Semi-Concealed 4-Way Air Discharge Semi-ConcealedConcealed Duct Concealed Duct High-Static Pressure Ceiling-MountedWall-Mounted Tubing Size Main Tubing Size LA11 Straight Equivalent Length of Joints Items Marks Contents Tubing LengthInstalling Distribution Joint Pay special attention to anyLocation, such as a basement Can accumulate, since refrigOptional Distribution Joint Kit APR-P160BATightening torque for valve stem cap 240 280 lbs · Example Main tubing Distribution joint tubingSelecting the Installation Site Indoor UnitCeiling-Mounted Type Wall-Mounted TypeInstallation space Case of multiple installationsInstalling the Unit in Heavy Snow Areas Precautions for Installation in Heavy Snow AreasAir Discharge Chamber for Top Discharge Countermeasures against snow and windCHX03652/06052 WindFront and both sides must remain open 28-13/16 17-23/32 47-19/32 Obstacle to the rear of unit Obstacle to the front of unitInstallation in front-rear rows Obstacles to the front and rear of unitHOW to Install the Indoor Unit Suspending the Indoor UnitPlacing the Unit Inside the Ceiling 12, 18, 24Installing the Drain Piping PVC pipe must be purchased separately.Be careful since the fan will Start when you short the pinOn the indoor control board Removing the corner cover Installing the Ceiling Panel Main unit Gaps Ceiling surfaceWiring the Ceiling Panel Checking After Installation When Removing the Ceiling Panel for ServicingAdjusting the Auto Flap Special Remarks DC Fan Tap Change ProcedureFollow the diagrams to make the holes in the ceiling Full-scale Installation diagram Suspension lug 25/32 1 Suspension bolts Tubing side Unit Ceiling Material 25/32 Be careful since the fan will start Electrical Power Wiring Wiring connectionsWiring Appearance Part nameRemoving the intake grille Removing the side panelMust be no gap Indoor unit Ceiling surface Ceiling panel Installing the side panel and intake grille Installing the intake grilleOther Check after installation If a wireless remote controller is usedType Length Number of duct flangesEnough to support the weight of the unit It is important that you use extreme careSupporting the indoor unit inside Ceiling. Ensure that the ceiling is strongPipe Short the pin on the indoor control board How to read the diagramIncreasing the Fan Speed 78 and -5 show the detailed dimensions Enough to suport the weight of the unit Indoor Fan Performance How to Read the Diagram Refrigerant tubing drain hose position UnitWeight of the unit. Before Wall and ceiling side opening positionIt is important that you use Indoor unit from the ceilingInside Shaping the Tubing Duct for Fresh AirRear outlet port How to carry out power supply wiring When removing the fasteningBracket from the cover BracketSelecting and Making a Hole Removing the Grille to Install the Indoor Unit If the Wall is Brick, Concrete or SimilarRemoving the grille Attaching the grilleInstalling the Drain Hose Do not supply power to the unit or operateIt until all tubing and wiring to the outdoor Right-rear tubingKHX0752 / 0952 / 1252 KHX2452HOW to Install the Outdoor Unit Electrical Wiring General Precautions on WiringCHX03652 For field wiring rules, please refer CHX06052Wiring System Diagram U, D, T TypeOutdoor unit That all wiring is tightly How to connect wiring to the terminal For stranded wiringResult in unit malfunction Fire hazard may alsoConnecting the Refrigerant Tubing Use of the Flaring Method HOW to Process TubingFlaring Procedure with a Flare Tool Tube diameter Tightening torque Tube thickness Approximate Insulating the Refrigerant Tubing Tubing Insulation Two tubes arranged togetherInsulation material After a tube has beenFinishing the Installation Taping the TubesAIR Purging Evacuation Charging additional refrigerant Use a cylinder designed forFinishing the job Test RUN Test Run Procedure Items to Check Before the Test Run YESOutdoor Unit PCB Setting Examples of the No. of indoor units settings Auto Address Setting Basic wiring diagram Example Automatic Address Setting from the Outdoor UnitIf link wiring is used Automatic Address Setting no compressor operation Automatic Address Setting from Outdoor UnitAutomatic Address Setting in Heating Mode Setting in heating mode beginsAutomatic Address Setting in Cooling Mode Automatic Address Setting from the Remote ControllerDisplay during automatic address setting Remote Controller Test Run Settings If 1 indoor unit is connected to 1 remote controllerChecking the indoor unit addresses LED Alarm Care and Cleaning Type 4-WAYLatch Air intake Safety chain Grille Bolt screws Tips for Energy SavingRemove the air filter from the air intake grille Water drain Air outlet Air intake Ceiling panel optionalTroubleshooting Canvas duct optional Concealed Duct High-Static Pressure Type U, D TypeElectrical box Air outlet side duct flange Troubleshooting CEILING-MOUNTED Air intake grille air intakeOr soot Type Wall-Mounted Tips for Energy Saving

85464359981002 specifications

The Sanyo 85464359981002 is a versatile and innovative product that has garnered attention in its respective market for its blend of performance, efficiency, and advanced technology features. This product is designed to cater to the demanding needs of consumers who prioritize quality and functionality in their daily lives.

One of the standout features of the Sanyo 85464359981002 is its energy efficiency. It is engineered to operate with minimal energy consumption while still delivering exceptional performance. This aspect is particularly significant given the growing concerns regarding energy usage and environmental sustainability. The model incorporates state-of-the-art technologies that optimize power usage without compromising on functionality.

The design of the Sanyo 85464359981002 focuses on user-friendliness and convenience. This product is equipped with an intuitive interface that makes it simple for users of all experience levels to operate and adjust settings as needed. Additionally, the lightweight construction enhances portability, allowing for easy transportation from one location to another.

Another notable characteristic is the advanced materials used in its construction. The Sanyo 85464359981002 is built to withstand the rigors of everyday use, ensuring durability and longevity. This quality makes it a smart investment for consumers looking for a reliable solution that won't require frequent replacements.

Connectivity is also a key feature of the Sanyo 85464359981002. It includes multiple ports and connectivity options that allow users to integrate the product with a variety of devices. This versatility enables seamless interaction with smartphones, tablets, and other technologies, ensuring that the Sanyo 85464359981002 can adapt to different environments and user needs.

The performance capabilities of the Sanyo 85464359981002 are impressive, emphasizing precision and speed. Whether it's delivering high-quality output or ensuring rapid operation, this product stands out in its field. These performance enhancements are supported by advanced technology that streamlines processes and improves overall productivity.

In conclusion, the Sanyo 85464359981002 exemplifies a well-rounded product that embodies modern design, energy efficiency, durability, and adaptability. Its array of features and advanced technologies makes it an attractive choice for consumers seeking quality and reliable performance in their daily routines.