Sanyo 85464359981002 installation instructions Automatic Address Setting in Cooling Mode

Page 76

Case 3

Automatic Address Setting in Cooling Mode

Indoor and outdoor unit power cannot be turned ON for each system separately.

In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating. Therefore perform this process only after completing all refrigerant tubing work.

Automatic address setting can be performed during Cooling operation.

Automatic Address Setting from Outdoor Unit

1.Perform steps 1 and 2 in the same way as for Case 1 .

2.Turn the indoor and outdoor unit power ON at all systems.

3.To perform automatic address setting in Cooling mode , on the outdoor unit control PCB in the refrigerant system where you wish to set the addresses, short-circuit the mode change 2P pin (CN50). At the same time, short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out. (Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than one system at the same time.)

(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Cooling mode begins.)

(All indoor units operate.)

* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out. The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.

(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)

4.At the outdoor unit in the next (different) system, short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.

(Repeat the same steps to complete automatic address setting for all units.)

5.Operation from the remote controllers is now possible.

* Automatic address setting in Cooling mode cannot be done from the remote controller.

Automatic Address Setting from the Remote Controller

Selecting each refrigerant system individually for automatic address setting

---Automatic address setting for each system: Item code “A1”

 

Press the remote controller timer time

button and

button at the same

time. (Press and hold for 4 seconds or longer.)

 

Next, press either the temperature setting

or

button.

(Check that the item code is “A1.”)

 

 

Use either the

or

button to set the system No. to perform

automatic address setting.

 

 

 

Then press the

button.

 

 

 

(Automatic address setting for one refrigerant system begins.)

(When automatic address setting for one system is completed, the system returns to normal stopped status.) <Approximately 4 – 5 minutes is required.> (During automatic address setting, “SETTING” is displayed on the remote controller. This message disappears when automatic address setting is completed.)

Repeat the same steps to perform automatic address setting for each successive system.

76

Image 76
Contents Outdoor Units R410A Models Indoor UnitsOptional Controllers Special Precautions …In a Room…In Moist or Uneven Locations …In an Area with High WindsCheck of Density Limit Care regarding tubing Be sure to recharge the refrigerant only in liquid formDifferent tools required Manifold gauge Vacuum pumpCompressor specifications are different Single-outlet valveExisting tubing cannot be used especially R22 R410AContents HOW to Process Tubing AIR PurgingTest RUN AppendixGeneral 1-Way Air Discharge Semi-Concealed 4-Way Air Discharge Semi-ConcealedConcealed Duct Concealed Duct High-Static Pressure Ceiling-MountedWall-Mounted Tubing Size Main Tubing Size LA11 Straight Equivalent Length of Joints Items Marks Contents Tubing LengthInstalling Distribution Joint Pay special attention to anyLocation, such as a basement Can accumulate, since refrigOptional Distribution Joint Kit APR-P160BATightening torque for valve stem cap 240 280 lbs · Example Main tubing Distribution joint tubingSelecting the Installation Site Indoor UnitCeiling-Mounted Type Wall-Mounted TypeInstallation space Case of multiple installationsInstalling the Unit in Heavy Snow Areas Precautions for Installation in Heavy Snow AreasAir Discharge Chamber for Top Discharge Countermeasures against snow and windCHX03652/06052 WindFront and both sides must remain open 28-13/16 17-23/32 47-19/32 Obstacle to the rear of unit Obstacle to the front of unitInstallation in front-rear rows Obstacles to the front and rear of unitHOW to Install the Indoor Unit Suspending the Indoor UnitPlacing the Unit Inside the Ceiling 12, 18, 24Installing the Drain Piping PVC pipe must be purchased separately.Be careful since the fan will Start when you short the pinOn the indoor control board Removing the corner cover Installing the Ceiling Panel Main unit Gaps Ceiling surfaceWiring the Ceiling Panel Checking After Installation When Removing the Ceiling Panel for ServicingAdjusting the Auto Flap Special Remarks DC Fan Tap Change ProcedureFollow the diagrams to make the holes in the ceiling Full-scale Installation diagram Suspension lug 25/32 1 Suspension bolts Tubing side Unit Ceiling Material 25/32 Be careful since the fan will start Electrical Power Wiring Wiring connectionsWiring Appearance Part nameRemoving the intake grille Removing the side panelMust be no gap Indoor unit Ceiling surface Ceiling panel Installing the side panel and intake grille Installing the intake grilleOther Check after installation If a wireless remote controller is usedType Length Number of duct flangesEnough to support the weight of the unit It is important that you use extreme careSupporting the indoor unit inside Ceiling. Ensure that the ceiling is strongPipe Short the pin on the indoor control board How to read the diagramIncreasing the Fan Speed 78 and -5 show the detailed dimensions Enough to suport the weight of the unit Indoor Fan Performance How to Read the Diagram Refrigerant tubing drain hose position UnitWeight of the unit. Before Wall and ceiling side opening positionIt is important that you use Indoor unit from the ceilingInside Shaping the Tubing Duct for Fresh AirRear outlet port How to carry out power supply wiring When removing the fasteningBracket from the cover BracketSelecting and Making a Hole Removing the Grille to Install the Indoor Unit If the Wall is Brick, Concrete or SimilarRemoving the grille Attaching the grilleInstalling the Drain Hose Do not supply power to the unit or operateIt until all tubing and wiring to the outdoor Right-rear tubingKHX0752 / 0952 / 1252 KHX2452HOW to Install the Outdoor Unit Electrical Wiring General Precautions on WiringCHX03652 For field wiring rules, please refer CHX06052Wiring System Diagram U, D, T TypeOutdoor unit That all wiring is tightly How to connect wiring to the terminal For stranded wiringResult in unit malfunction Fire hazard may alsoConnecting the Refrigerant Tubing Use of the Flaring Method HOW to Process TubingFlaring Procedure with a Flare Tool Tube diameter Tightening torque Tube thickness Approximate Insulating the Refrigerant Tubing Tubing Insulation Two tubes arranged togetherInsulation material After a tube has beenFinishing the Installation Taping the TubesAIR Purging Evacuation Charging additional refrigerant Use a cylinder designed forFinishing the job Test RUN Test Run Procedure Items to Check Before the Test Run YESOutdoor Unit PCB Setting Examples of the No. of indoor units settings Auto Address Setting Basic wiring diagram Example Automatic Address Setting from the Outdoor UnitIf link wiring is used Automatic Address Setting no compressor operation Automatic Address Setting from Outdoor UnitAutomatic Address Setting in Heating Mode Setting in heating mode beginsAutomatic Address Setting in Cooling Mode Automatic Address Setting from the Remote ControllerDisplay during automatic address setting Remote Controller Test Run Settings If 1 indoor unit is connected to 1 remote controllerChecking the indoor unit addresses LED Alarm Care and Cleaning Type 4-WAYLatch Air intake Safety chain Grille Bolt screws Tips for Energy SavingRemove the air filter from the air intake grille Water drain Air outlet Air intake Ceiling panel optionalTroubleshooting Canvas duct optional Concealed Duct High-Static Pressure Type U, D TypeElectrical box Air outlet side duct flange Troubleshooting CEILING-MOUNTED Air intake grille air intakeOr soot Type Wall-Mounted Tips for Energy Saving

85464359981002 specifications

The Sanyo 85464359981002 is a versatile and innovative product that has garnered attention in its respective market for its blend of performance, efficiency, and advanced technology features. This product is designed to cater to the demanding needs of consumers who prioritize quality and functionality in their daily lives.

One of the standout features of the Sanyo 85464359981002 is its energy efficiency. It is engineered to operate with minimal energy consumption while still delivering exceptional performance. This aspect is particularly significant given the growing concerns regarding energy usage and environmental sustainability. The model incorporates state-of-the-art technologies that optimize power usage without compromising on functionality.

The design of the Sanyo 85464359981002 focuses on user-friendliness and convenience. This product is equipped with an intuitive interface that makes it simple for users of all experience levels to operate and adjust settings as needed. Additionally, the lightweight construction enhances portability, allowing for easy transportation from one location to another.

Another notable characteristic is the advanced materials used in its construction. The Sanyo 85464359981002 is built to withstand the rigors of everyday use, ensuring durability and longevity. This quality makes it a smart investment for consumers looking for a reliable solution that won't require frequent replacements.

Connectivity is also a key feature of the Sanyo 85464359981002. It includes multiple ports and connectivity options that allow users to integrate the product with a variety of devices. This versatility enables seamless interaction with smartphones, tablets, and other technologies, ensuring that the Sanyo 85464359981002 can adapt to different environments and user needs.

The performance capabilities of the Sanyo 85464359981002 are impressive, emphasizing precision and speed. Whether it's delivering high-quality output or ensuring rapid operation, this product stands out in its field. These performance enhancements are supported by advanced technology that streamlines processes and improves overall productivity.

In conclusion, the Sanyo 85464359981002 exemplifies a well-rounded product that embodies modern design, energy efficiency, durability, and adaptability. Its array of features and advanced technologies makes it an attractive choice for consumers seeking quality and reliable performance in their daily routines.