Siemens 600 brochure Inverter type Input DC PVS585 PVS1170 PVS1755 PVS2340

Page 7

© Siemens AG 2012

Technical data of the SINVERT PVS585 inverter (according to IEC)1)

Inverter type

Input DC

PVS585

PVS1170

PVS1755

PVS2340

MPP voltage

V

530 ... 750

530 ... 750

530 ... 750

530 ... 750

Maximum input voltage2)

V

820

820

820

820

Minimum input voltage

V

530

530

530

530

Rated input power

kW

598

1 196

1 794

2 392

Maximum input current

A

1 104

2 208

3 312

4 416

Number of DC inputs

 

3

6

9

12

Maximum current per DC input

A

368

368

368

368

Surge arrester

 

Type 2

Type 2

Type 2

Type 2

Output AC

 

 

 

 

 

 

 

 

 

 

 

Grid connection

 

50/60 Hz 340 V 3 AC

50/60 Hz 340 V 3 AC

50/60 Hz 340 V 3 AC

50/60 Hz 340 V 3 AC

Rated power

kW

585

1 170

1 755

2 340

Maximum output current

A

995

1 990

2 985

3 980

Line voltage

V

289 ... 374

289 ... 374

289 ... 374

289 ... 374

Power factor, inductive

 

0.8

0.8

0.8

0.8

Power factor, capacitive

 

0.8

0.8

0.8

0.8

Efficiency

 

 

 

 

 

 

 

 

 

 

 

European efficiency factor

%

98.2

98.4

98.4

98.4

CEC efficiency factor

%

98.3

98.3

98.4

98.4

Maximum efficiency factor

%

98.6

98.6

98.6

98.6

Further data

 

 

 

 

 

 

 

 

 

 

 

Number of subunits

 

1

2

3

4

Dimensions (H/W/D) per subunit

mm

2 100 x 2 700 x 730

2 100 x 2 700 x 730

2 100 x 2 700 x 730

2 100 x 2 700 x 730

Weight per subunit

kg

2 085

2 085

2 085

2 085

Ambient temperature

 

 

 

 

 

- during operation

°C

0 ... +50

0 ... +50

0 ... +50

0 ... +50

- during storage and transport

°C

-25 ... +70

-25 ... +70

-25 ... +70

-25 ... +70

Relative humidity

%

0 ... 95

0 ... 95

0 ... 95

0 ... 95

Installation altitude

 

 

 

 

 

- maximum permissible

m

2 000

2 000

2 000

2 000

- at rated power

m

0 ... 1 000

0 ... 1 000

0 ... 1 000

0 ... 1 000

Data interface

 

Ethernet

Ethernet

Ethernet

Ethernet

Order number

 

 

 

 

 

 

 

 

 

 

 

Order number (grid frequency 50 Hz)

 

6AG3111-1AH00-

6AG3111-1AH10-

6AG3111-1AH20-

6AG3111-1AH30-

 

 

7AB0

7AB0

7AB0

7AB0

Order number (grid frequency 60 Hz)

 

6AG3111-2AH00-

6AG3111-2AH10-

6AG3111-2AH20-

6AG3111-2AH30-

 

 

7AB0

7AB0

7AB0

7AB0

 

 

 

 

 

 

1)Detailed technical information can be found at: http://support.automation.siemens.com

2)With the 1 000 V option, expandable to 1 000 V (see page 10 and 24).

SINVERT PVS 600Series central inverters 7

Image 7
Contents Sinvert Sunny prospects for photovoltaic plants Sunny prospects for photovoltaic plantsContents Reliability Features and advantages at a glance Transformerless, 3-phase Sinvert PVS inverters are Cost-effectivenessSinvert PVS 600Series Further data Inverter type Input DC PVS500 PVS1000 PVS1500 PVS2000Output AC EfficiencyInverter type Input DC PVS585 PVS1170 PVS1755 PVS2340 Inverter type Input DC PVS600 PVS1200 PVS1800 PVS2400 Inverter type Input DC PVS630 PVS1260 PVS1890 PVS2520 Options for Sinvert PVS 600Series inverters Sinvert PVS inverters for industrial roof systems Sinvert PVS inverters for solar power plantsHow solar power is fed into the AC grid Link between solar power and public AC gridSinvert PVS CombinerBoxes for bundling partial currents Sinvert PVS CombinerBox 108 120 124 204 IEC-compliant inverter stations See diagram onMedium-voltage transformer Medium-voltage switchgearMaster-slave system with Sinvert PVS Individual components of the inverter stationsSinvert PVS ComBox Establishing communication with PVS and system componentsSinvert PVS ControlBox Generating Plants in the Medium-Voltage Grid Bdew Sinvert PVS ComBox Sinvert puts sunshine into the grid. Worldwide Some examples of solar power plants using Sinvert invertersPV plant dimensioning with Sinvert Select For fast and easy dimensioningPV plant monitoring with WinCC For an instant, up-to-date overview and rapid interventionSinvert WebMonitor MobileApp PV plant monitoring with Sinvert WebMonitorSinvert PVS 600Series inverters For devices and accessoriesSelection and ordering data Options for Sinvert PVS 600Series inverters Options for Sinvert PVS 600Series invertersFuses for Sinvert PVS CombinerBox Unique range of complete services for the entire life cycle Service & SupportService calls Spare parts serviceService contracts Spare parts service Tailored program of services for Sinvert PVSService calls 100 200 300 Service contractsSinvert PVS SparesContract Sinvert PVS WarrantyExtensionExtends the period of the standard warranty Sinvert PVS WarrantyExtension offersSinvert PVS FullServiceContract offers Sinvert PVS MaintenanceContractRoutine maintenance by Siemens Sinvert PVS MaintenanceContract offersGet more information
Related manuals
Manual 11 pages 10.26 Kb