Siemens 600 brochure Inverter type Input DC PVS630 PVS1260 PVS1890 PVS2520

Page 9

© Siemens AG 2012

Technical data of the SINVERT PVS630 inverter (according to IEC)1)

Inverter type

Input DC

PVS630

PVS1260

PVS1890

PVS2520

MPP voltage

V

570 ... 750

570 ... 750

570 ... 750

570 ... 750

Maximum input voltage2)

V

820

820

820

820

Minimum input voltage

V

570

570

570

570

Rated input power

kW

643

1 286

1 929

2 572

Maximum input current

A

1 104

2 208

3 312

4 416

Number of DC inputs

 

3

6

9

12

Maximum current per DC input

A

368

368

368

368

Surge arrester

 

Type 2

Type 2

Type 2

Type 2

Output AC

 

 

 

 

 

 

 

 

 

 

 

Grid connection

 

50/60 Hz 370 V 3 AC

50/60 Hz 370 V 3 AC

50/60 Hz 370 V 3 AC

50/60 Hz 370 V 3 AC

Rated power

kW

630

1 260

1 890

2 520

Maximum output current

A

985

1 970

2 955

3 940

Line voltage

V

314.5 ... 407

314.5 ... 407

314.5 ... 407

314.5 ... 407

Power factor, inductive

 

0.8

0.8

0.8

0.8

Power factor, capacitive

 

0.8

0.8

0.8

0.8

Efficiency

 

 

 

 

 

 

 

 

 

 

 

European efficiency factor

%

98.3

98.5

98.5

98.5

CEC efficiency factor

%

98.4

98.5

98.5

98.5

Maximum efficiency factor

%

98.7

98.7

98.7

98.7

Further data

 

 

 

 

 

 

 

 

 

 

 

Number of subunits

 

1

2

3

4

Dimensions (H/W/D) per subunit

mm

2 100 x 2 700 x 730

2 100 x 2 700 x 730

2 100 x 2 700 x 730

2 100 x 2 700 x 730

Weight per subunit

kg

2 085

2 085

2 085

2 085

Ambient temperature

 

 

 

 

 

- during operation

°C

0 ... +50

0 ... +50

0 ... +50

0 ... +50

- during storage and transport

°C

-25 ... +70

-25 ... +70

-25 ... +70

-25 ... +70

Relative humidity

%

0 ... 95

0 ... 95

0 ... 95

0 ... 95

Installation altitude

 

 

 

 

 

- maximum permissible

m

2 000

2 000

2 000

2 000

- at rated power

m

0 ... 1 000

0 ... 1 000

0 ... 1 000

0 ... 1 000

Data interface

 

Ethernet

Ethernet

Ethernet

Ethernet

Order number

 

 

 

 

 

 

 

 

 

 

 

Order number (grid frequency 50 Hz)

 

6AG3111-1AH00-

6AG3111-1AH10-

6AG3111-1AH20-

6AG3111-1AH30-

 

 

8AB0

8AB0

8AB0

8AB0

Order number (grid frequency 60 Hz)

 

6AG3111-2AH00-

6AG3111-2AH10-

6AG3111-2AH20-

6AG3111-2AH30-

 

 

8AB0

8AB0

8AB0

8AB0

 

 

 

 

 

 

1)Detailed technical information can be found at: http://support.automation.siemens.com

2)With the 1 000 V option, expandable to 1 000 V (see page 10 and 24).

SINVERT PVS 600Series central inverters 9

Image 9
Contents Sinvert Sunny prospects for photovoltaic plants Sunny prospects for photovoltaic plantsContents Transformerless, 3-phase Sinvert PVS inverters are Features and advantages at a glanceCost-effectiveness ReliabilitySinvert PVS 600Series Output AC Inverter type Input DC PVS500 PVS1000 PVS1500 PVS2000 Efficiency Further dataInverter type Input DC PVS585 PVS1170 PVS1755 PVS2340 Inverter type Input DC PVS600 PVS1200 PVS1800 PVS2400 Inverter type Input DC PVS630 PVS1260 PVS1890 PVS2520 Options for Sinvert PVS 600Series inverters Sinvert PVS inverters for industrial roof systems Sinvert PVS inverters for solar power plantsLink between solar power and public AC grid How solar power is fed into the AC gridSinvert PVS CombinerBoxes for bundling partial currents Sinvert PVS CombinerBox 108 120 124 204 IEC-compliant inverter stations See diagram onMaster-slave system with Sinvert PVS Medium-voltage switchgearIndividual components of the inverter stations Medium-voltage transformerEstablishing communication with PVS and system components Sinvert PVS ComBoxSinvert PVS ControlBox Generating Plants in the Medium-Voltage Grid Bdew Sinvert PVS ComBox Sinvert puts sunshine into the grid. Worldwide Some examples of solar power plants using Sinvert invertersPV plant dimensioning with Sinvert Select For fast and easy dimensioningPV plant monitoring with WinCC For an instant, up-to-date overview and rapid interventionSinvert WebMonitor MobileApp PV plant monitoring with Sinvert WebMonitorFor devices and accessories Sinvert PVS 600Series invertersSelection and ordering data Options for Sinvert PVS 600Series inverters Options for Sinvert PVS 600Series invertersFuses for Sinvert PVS CombinerBox Unique range of complete services for the entire life cycle Service & SupportSpare parts service Service callsService contracts Tailored program of services for Sinvert PVS Spare parts serviceService calls 100 200 300 Service contractsExtends the period of the standard warranty Sinvert PVS WarrantyExtensionSinvert PVS WarrantyExtension offers Sinvert PVS SparesContractRoutine maintenance by Siemens Sinvert PVS MaintenanceContractSinvert PVS MaintenanceContract offers Sinvert PVS FullServiceContract offersGet more information