Technical data of the SINVERT PVS600 inverter (according to IEC)1)

Inverter type

Input DC

PVS600

PVS1200

PVS1800

PVS2400

MPP voltage

V

570 ... 750

570 ... 750

570 ... 750

570 ... 750

Maximum input voltage2)

V

820

820

820

820

Minimum input voltage

V

570

570

570

570

Rated input power

kW

613

1 226

1 839

2 452

Maximum input current

A

1 104

2 208

3 312

4 416

Number of DC inputs

 

3

6

9

12

Maximum current per DC input

A

368

368

368

368

Surge arrester

 

Type 2

Type 2

Type 2

Type 2

Output AC

 

 

 

 

 

 

 

 

 

 

 

Grid connection

 

50/60 Hz 370 V 3 AC

50/60 Hz 370 V 3 AC

50/60 Hz 370 V 3 AC

50/60 Hz 370 V 3 AC

Rated power

kW

600

1 200

1 800

2 400

Maximum output current

A

936

1 872

2 808

3 744

Line voltage

V

314.5 ... 407

314.5 ... 407

314.5 ... 407

314.5 ... 407

Power factor, inductive

 

0.8

0.8

0.8

0.8

Power factor, capacitive

 

0.8

0.8

0.8

0.8

Efficiency

 

 

 

 

 

 

 

 

 

 

 

European efficiency factor

%

98.4

98.6

98.6

98.6

CEC efficiency factor

%

98.5

98.6

98.6

98.6

Maximum efficiency factor

%

98.7

98.7

98.7

98.7

Further data

 

 

 

 

 

 

 

 

 

 

 

Number of subunits

 

1

2

3

4

Dimensions (H/W/D) per subunit

mm

2 100 x 2 700 x 730

2 100 x 2 700 x 730

2 100 x 2 700 x 730

2 100 x 2 700 x 730

Weight per subunit

kg

2 085

2 085

2 085

2 085

Ambient temperature

 

 

 

 

 

- during operation

°C

0 ... +50

0 ... +50

0 ... +50

0 ... +50

- during storage and transport

°C

-25 ... +70

-25 ... +70

-25 ... +70

-25 ... +70

Relative humidity

%

0 ... 95

0 ... 95

0 ... 95

0 ... 95

Installation altitude

 

 

 

 

 

- maximum permissible

m

2 000

2 000

2 000

2 000

- at rated power

m

0 ... 1 000

0 ... 1 000

0 ... 1 000

0 ... 1 000

Data interface

 

Ethernet

Ethernet

Ethernet

Ethernet

Order number

 

 

 

 

 

 

 

 

 

 

 

Order number (grid frequency 50 Hz)

 

6AG3111-1AH00-

6AG3111-1AH10-

6AG3111-1AH20-

6AG3111-1AH30-

 

 

0AB0

0AB0

0AB0

0AB0

Order number (grid frequency 60 Hz)

 

6AG3111-2AH00-

6AG3111-2AH10-

6AG3111-2AH20-

6AG3111-2AH30-

 

 

0AB0

0AB0

0AB0

0AB0

 

 

 

 

 

 

1)Detailed technical information can be found at: http://support.automation.siemens.com

2)With the 1 000 V option, expandable to 1 000 V (see page 10 and 24).

8SINVERT PVS 600Series central inverters

Image 8
Contents Sinvert Sunny prospects for photovoltaic plants Sunny prospects for photovoltaic plantsContents Features and advantages at a glance Transformerless, 3-phase Sinvert PVS inverters areCost-effectiveness Reliability Sinvert PVS 600Series Inverter type Input DC PVS500 PVS1000 PVS1500 PVS2000 Output ACEfficiency Further dataInverter type Input DC PVS585 PVS1170 PVS1755 PVS2340 Inverter type Input DC PVS600 PVS1200 PVS1800 PVS2400 Inverter type Input DC PVS630 PVS1260 PVS1890 PVS2520 Options for Sinvert PVS 600Series inverters Sinvert PVS inverters for solar power plants Sinvert PVS inverters for industrial roof systemsSinvert PVS CombinerBoxes for bundling partial currents Link between solar power and public AC gridHow solar power is fed into the AC grid Sinvert PVS CombinerBox 108 120 124 204 See diagram on IEC-compliant inverter stationsMedium-voltage switchgear Master-slave system with Sinvert PVSIndividual components of the inverter stations Medium-voltage transformerSinvert PVS ControlBox Establishing communication with PVS and system componentsSinvert PVS ComBox Generating Plants in the Medium-Voltage Grid Bdew Sinvert PVS ComBox Some examples of solar power plants using Sinvert inverters Sinvert puts sunshine into the grid. WorldwideFor fast and easy dimensioning PV plant dimensioning with Sinvert SelectFor an instant, up-to-date overview and rapid intervention PV plant monitoring with WinCCPV plant monitoring with Sinvert WebMonitor Sinvert WebMonitor MobileAppSelection and ordering data For devices and accessoriesSinvert PVS 600Series inverters Options for Sinvert PVS 600Series inverters Options for Sinvert PVS 600Series invertersFuses for Sinvert PVS CombinerBox Service & Support Unique range of complete services for the entire life cycleService contracts Spare parts serviceService calls Service calls Tailored program of services for Sinvert PVSSpare parts service Service contracts 100 200 300Sinvert PVS WarrantyExtension Extends the period of the standard warrantySinvert PVS WarrantyExtension offers Sinvert PVS SparesContractSinvert PVS MaintenanceContract Routine maintenance by SiemensSinvert PVS MaintenanceContract offers Sinvert PVS FullServiceContract offersGet more information