Thermo Products OHFA199DV5B, OHFA199DV5R Air Filter Mounted External to Furnace, Examples

Page 18

SIZING THE DUCT WORK FOR A COMBINATION HEATING AND COOLING SYSTEM:

Two formulas must be used in determining the CFM requirements of a combustion heating and cooling system.

1.HEATING CFM:

HEAT OUTPUT OF FURNACE (BTUH)

1.1 X TR (TEMPERATURE RISE, °F) = HEATING(CFM)

EXAMPLES:

A. 110,000 BTUH OUTPUT

1.1X 85°F TR = 1176 CFM FOR HEATING B. 110,000 BTUH OUTPUT

1.1X 70°F TR = 1429 CFM FOR HEATING

2.COOLING CFM: 400 CFM X COOLING TONNAGE (12,000 BTUH PER TON)=AIRFLOW FOR COOLING(CFM)

EXAMPLES:

A.400 CFM X 3 TON (12,000 BTUH) = 1,200 CFM FOR COOLING 1TON

B.400 CFM X 2.5 TON (12,000 BTUH) = 1,000 CFM FOR COOLING 1 TON

IMPORTANT: SIZE THE DUCT SYSTEM FOR THE LARGER OF THE TWO AIRFLOW REQUIREMENTS.

E. Air Filter Mounted External to Furnace:

On highboy furnaces, it is necessary to cut the return air opening in the side, rear casing or base, depending upon the needs of the specific installation.

The filter rack provided with the furnace, refer to Fig. 10a & 10b, will serve as a template to scribe a mark for the return air opening on the casing. Place the filter rack on a side casing approximately one inch up from the bottom of the furnace and centered from side to side. Place the securing flange against the casing when locating the return air opening. For your convenience, (4) locator knockouts have been placed at the proper locations on both the left and right side casings.

PLEASE NOTE: While scribing the return air opening, the filter rack can be held in position by tape or similar temporary means.

Position the open end of the filter rack so as to provide access for filter replacement. Once the filter rack is positioned correctly, scribe a line along the inside of the securing flange on three of the sides. To scribe a line on the fourth side (the open end), use the open-end support as a guide.

Remove the filter rack and cut the return air opening in the casing. Now the filter rack can be anchored to the furnace with screws or pop-rivets through the securing flange of the filter rack.

15

Image 18
Contents OH6FA072DV4B OH6FA072DV4ROH6FA072DV4N OH6FX072DV4R Contents = Highboy D = Downflow = FrontSafety Section WARNING and CautionsCAUTION do not Attempt to Start the Burner When Page Codes and Clearances Combustible materialNon-combustible material II. General Instructions Read Before Start of Installation HighboyChimney Prevention of Chimney CondensingProper Vent Connector PIPE/CHIMNEY Connection Proper Chimney HeightNo Interconnected Chimney Flues Tight CLEAN-OUT Doors and ConnectionsTight Joints Flue Pipe CLEARANCES, Sizing and TypeReduction of Clearances with Specified Forms of Protection Venting Draft Regulators Duct WORK/AIR ConditioningAirflow Requirements and Sizing of Duct Work Page Page Supply air duct sizing Example Air Filter Mounted External to Furnace ExamplesA typical filter rack and dimensions for the OH6 furnace Limit Position and Location Maximum Filter Type Air Velocity Model Number Ft/minOH6 OH8 Burner Installation Do not remove this retainer when installing burnerBurner Specifications and Applications Do not Change Position of the ChamberBeckett Riello BTU/HRMounting the 2-STAGE Riello Burner BTU/HR Heating CapacityOIL Tank and Piping OIL Filter Electrical WiriingElectronic Air Cleaner EAC and Humidifier Installation OH6FA072DV5OH8FA119DV5 Thermostat Anticipator Setting Fan Control ModulePreferred method of adjustment Heat Anticipator Adjustment ScaleBlower Motor Speed Selection Furnace Motor Current Heating Speed Set-upsOH6FA072DV4 Draw Amps/ / Watts vs1A ECM blower motor speed chart Heating Speed Set-ups 2 Stage OH6FX072DV4Cooling blower motor speed chart Cooling Speed Set-ups Draw Amps/Watts vsOH6FA072D48 HighHTG Speed by Input Terminal Definitions & Field Wiring Blower Controller Information for PSC MotorInputs OutputsOperating Modes On and OFF Blower Delay Time Switch Settings PSC Trouble Shooting Diagnostic FeaturesStartup Procedures STOP! Read the safety information aboveOperating Instructions Adjustment of Burner Combustion To Turn Off Oil to ApplianceCombustion Head Setting for 2-STAGE Riello Burner Preliminary Adjustment of Burner Air Band and Air ShutterAIR Damper Adjustment Turn to the Right Sign +Turn to the Left Sign 1st Stage Adjustment 2nd Stage AdjustmentAdjustment Of Heat Input Rate Page Checkout Procedure III. Users Information Section Inspection Areas Caution do not Attempt to Make Repairs Yourself Filter Cleaning and Location Starting the BurnerIV. Installers Instructions to User Dealer Maintenance Safety During Servicing and InspectionGeneral Inspection Heat Exchanger OH6 8FT OH8 8FT SUPPLY/RETURN AIR Blower Filter maintenance procedureElectrical System SUPPLY/RETURN AIR FilterFilter replacement Extended Appliance ShutdownOn Shutdown VI. HOMEOWNER/USER Information and Routine Maintenance On StartupLocation of oil primary control reset button Beckett BurnerPage CAD Cell Checkout Procedure DiagnosticsDiagnostic Features Number of flashes Cad Cell Resistance in ohms Model R7184BPage VIII. Sequence of Operations Flow Chart Page IX. Trouble Shooting Flow Chart Page Page Page Page Customer Appendix a Replacement Parts Replacement Parts for OH8FA119D Appendix B Wiring Diagrams OH6FA072DV4 ECM Wiring Diagram OH6FX072DV4 ECM 2-Stage Wiring Diagram OH8FA1119D60 PSC Wiring Diagram OH8FA1119DV5 ECM Wiring Diagram