Operation
order to prevent damage to the tower components.
4.Air flow rate: Reducing air flow through the tower causes the cold water temperature to rise. This is the approved method by which to control leaving water temperature.
If your tower is equipped with a
Caution | When operating in this mode care must be taken not to exceed a total |
acceleration time of 30 seconds per hour. |
Fan cycling limits: From a dead stop, determine the number of sec- onds it takes the fan to arrive at full speed. Divide this number into 30 to determine the allowable number of starts per hour. Considering the normal fan and motor sizes utilized on AV Series towers, anticipate that approximately 4 to 5 starts per hour are allowable.
If your tower is equipped with a
If your tower consists of two or more cells, cycling of motors may be shared between cells, increasing your steps of operation accordingly.
For greater insight on cold water temperature control, please read “Cooling Tower Energy and its Management”, Marley Technical
Report