Maintenance

concentrations. This stabilization of contaminant concentrations is usually accomplished by blowdown, which is the constant discharge of a portion of

Cooling Range

 

 

Number of Concentrations

 

 

 

 

 

 

 

 

 

1.5X

2.0X

2.5X

3.0X

4.0X

5.0X

6.0X

 

 

 

 

 

 

 

 

 

5° F (2.78° C)

.78

.38

.25

.18

.11

.08

.06

10° F (5.56° C)

1.58

.78

.51

.38

.25

.18

.14

 

 

 

 

 

 

 

 

15° F (8.33° C)

2.38

1.18

.78

.58

.38

.28

.22

20° F (11.11° C)

3.18

1.58

1.05

.78

.51

.38

.30

 

 

 

 

 

 

 

 

25° F (13.89° C)

3.98

1.98

1.32

.98

.64

.48

.38

Multipliers are based on drift of 0.02% of the circulating water rate.

the circulating water to waste. As a rule, acceptable levels on which to base a treatment schedule will be in the range of 2-4 concentrations. The following table shows the minimum amount of blowdown (percent of flow) required to maintain different concentrations with various cooling ranges*:

*Range = Difference between hot water temperature coming to tower and cold water temperature leaving tower.

EXAMPLE: 700 GPM (44.2 L/s) circulating rate, 18°F (10°C) cooling range. To maintain 4 concentrations, the required blowdown is 0.458% or .00458 times 700 GPM (44.2 L/s), which is 3.2 GPM (0.2 L/s).

If tower is operated at 4 concentrations, circulating water will contain four times as much dissolved solid as the makeup water, assuming none of the solids form scale or are otherwise removed from the system.

When water treatment chemicals are added, they should not be in-

Notetroduced into the circulating water system via the cold water basin of the cooling tower. Water velocities are lowest at that point, which results in inadequate mixing.

Belt Tensioning

The belts are adjusted by turning the jacking screw at the motor support. Ideal tension is the lowest tension at which the belt will not slip under peak load conditions. Check tension frequently during the first 24-48 hours of run-in operation. Overtensioning shortens belt and bearing life. Keep belts free from foreign material which may cause slip. Never apply belt dressing as this will damage the belt and cause early failure. A Dodge® V-Belt Tension Tester is an alternate method for tensioning

V-belts. Check with you local belt supplier.

 

21

Image 21
Contents Marley AV Cooling Tower Contents Preparation Safety FirstTower Location Tower Shipment Receiving and HoistingReceiving Tower Hoisting TowerTower Installation InstallationInstallation When using a starter Motor WiringWhen using a VFD When using a two-speedstarterMechanical Equipment Installation Operation Tower Start-UpWater System Operation General Tower OperationAcceleration time of 30 seconds per hour Wintertime Operation Operation Intermittent Wintertime Operation Maintaining Water Quality Tower Cleaning, Water Treatment and BlowdownMaintenance Cooling Tower CleaningBlowdown Belt Tensioning Sheave Alignment Bushing Fastener Torque ValuesSchedule of Tower Maintenance Maintenance Seasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies’ ServicesMaintenance Schedule Trouble Cause Remedy TroubleshootingRepresentative Additional Information Page Manual 98-1514E