Troubleshooting

Trouble

Cause

Remedy

 

Loose bolts and cap screws

Tighten all bolts and cap screws on all mechanical equipment

 

and supports.

 

 

 

 

Make certain all blades are as far from center of fan as safety

Unusual Fan Drive

Fan

devices permit. All blades must be pitched the same. See

 

Fan User Manual. Clean off deposit build-up on blades.

Vibration

 

 

Worn fan shaft bearings

Check fan shaft endplay. Replace bearings as necessary.

 

 

 

 

 

Unbalanced motor

Disconnect load and operate motor. If motor still vibrates,

 

rebalance rotor.

 

 

 

Blade rubbing inside of fan cylinder

Adjust cylinder to provide blade tip clearance.

Fan Noise

Loose bolts in blade clamps

Check and tighten if necessary.

 

Fan shaft bearings

Grease bearings.

Scale or foreign substance Insufficient blowdown

See "Water Treatment" section of this manual

in circulating water system

Water treatment deficiency

Consult competent water treating specialist. See "Water

 

 

Treatment" section of this manual

 

 

 

 

 

 

 

Check to see if local heat sources are affecting tower. See if

 

Entering wet bulb temp. is above design

surrounding structures are causing recirculation of tower

 

 

discharge air. Discuss remedy with Marley representative.

Cold Water Temperature

Too Warm

(See "Tower Operation")

Design wet bulb temp. was too low

May have to increase tower size. Discuss remedy with Marley

representative.

 

Actual process load greater than design

May have to increase tower size. Discuss remedy with Marley

representative.

 

Overpumping

Reduce water flow rate over tower to design conditions.

 

Check motor current and voltage to be sure of correct contract

 

horsepower. Re-pitch fan blades if necessary. Clean louvers,

Tower starved for air

fill and eliminators. Check to see if nearby structures or

 

enclosing walls are obstructing normal airflow to tower.

 

Discuss remedy with Marley representative.

 

Distribution basins overflowing

Reduce water flow rate over tower to design conditions. Be

 

sure hot water basin nozzles are in place and not plugged.

 

 

Excessive Drift Exiting

Check to see that integral fill, louvers, and eliminators are

Tower

clean, free of debris, and installed correctly. If drift eliminators

 

Faulty drift elimination

are separate from fill, make sure they are correctly installed in

 

 

place. Clean if necessary. Replace damaged or worn out

 

 

components.

29

Image 29
Contents Marley AV Cooling Tower Contents Preparation Safety FirstTower Location Tower Shipment Receiving and HoistingReceiving Tower Hoisting TowerTower Installation InstallationInstallation When using a starter Motor WiringWhen using a VFD When using a two-speedstarterMechanical Equipment Installation Water System OperationTower Start-Up Operation General Tower OperationAcceleration time of 30 seconds per hour Wintertime Operation Operation Intermittent Wintertime Operation Maintaining Water Quality Tower Cleaning, Water Treatment and BlowdownBlowdown MaintenanceCooling Tower Cleaning Belt Tensioning Sheave Alignment Bushing Fastener Torque ValuesSchedule of Tower Maintenance Maintenance Seasonal Shutdown Instructions Prolonged Shutdown SPX Cooling Technologies’ ServicesMaintenance Schedule Trouble Cause Remedy TroubleshootingRepresentative Additional Information Page Manual 98-1514E