Installation
Normally, one of the following two inlet arrangements is provided:
Standard distribution basin connections: There is a circular opening in the top deck of the tower near the air inlet face, drilled to accept standard 125#
Marley
12.Wire motor in accordance with wiring diagram on motor nameplate. Check motor connections and power supply voltage versus motor nameplate voltage.
Warning | For maintenance/safety purposes, SPX Cooling recommends a lockout |
type disconnect switch for all mechanical equipment. |
In addition to a disconnect switch, the motor should be wired to main power supply through short circuit protection, and a magnetic starter with overload protection.
Motor Wiring
Wire motor leads as shown on the motor nameplate matching the supply voltage. Do not deviate from the motor nameplate wiring.
Either of following symbols may be shown on the motor nameplate – Δ, Δ Δ, Y, or YY. These symbols represent how the motor is constructed on the inside and in no way have anything to do with a Delta or Wye electrical distribution system serving the motor.
When using a starter:
•Set motor overload protection to 110% of motor nameplate amps.
This setting allows the fan motor to operate during cooler weather. During cooler weather it is common for the motor to draw 6 to
8