Toshiba TCB-AX21UL HOW to SET the Room Temperature Sensor, Wireless remote controller kit

Page 11

Wireless remote controller kit

Installation Manual

 

To operate a group control of multiple indoor units by 2 remote controllers

MAIN and SUB remote controllers are operable even if they are installed to any indoor unit. (Total cable length: Within 656’2” (200 m))

Wireless remote controller kit

Signal receiving unit

Remote controller inter-unit cable for group control (Field procurement) (AWG20 (0.5 mm2))

(UL wires rated 300 V)

Wired remote controller (SUB)

(Sold separately)

Terminal block for

 

remote controller

Indoor unit

cable

No.1

Ground

Indoor unit

No.2

Ground

Indoor unit

No.3

Ground

Indoor unit

No.4

Ground

7 HOW TO SET THE ROOM TEMPERATURE SENSOR

The room temperature sensors are equipped in the indoor unit and the wireless remote controller.

One of two sensors works.

The room temperature sensor is set to the indoor unit side as factory default.

To select the sensor in the remote controller, push the SENSOR button (figure below) inside of the remote controller cover and check “” disappears from LCD.

NOTE

If the room temperature data from the remote controller is not transmitted to the unit for 10 minutes or more, the sensor at indoor unit side is automatically selected even if the sensor at the remote controller side is selected.

Fix the remote controller toward the unit as possible.

SENSOR button

EN

– 10 –

10-EN

Image 11
Contents TCB-AX21UL Contents Accessory Parts Address selector switch Switch Location of Signal Receiving UnitInstallation Location of Signal Receiving Unit Fig. a HOW to Install the Signal Receiving UnitFig.B Fig.E Provided wire joint WHT HOW to Perform Cabling of the Signal Receiving UnitConnection diagram Requirement To operate an indoor unit by 2 remote controllersWireless remote controller kit HOW to SET the Room Temperature SensorSlide Switch HOW to SET the Address SwitchSELF-DIAGNOSIS Table and Measures Lamp indication of Signal receiving unitReplacement of battery Case using remote controller mounting to the wall, etcBefore test run How to conduct a Test RUNTest RUN 85464369216000 EH99677601