York 122, YLCC-h Limits of use,YLCC cooling only unit, Limits of use, YLCC-H heat pump unit

Page 10

Limits of use

 

Voltage limits

DB air intake temperature to coil

 

Water outlet temperature

 

Temperature

 

 

 

differential between

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operating

cycle

 

 

Operating

cycle

 

water discharge and

 

 

 

 

 

 

 

intake

Model

Nominal at 400 V

 

 

 

 

 

 

 

 

Minimum °C

Maximum °C

Minimum °C

Maximum °C

Minimum

Maximum

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum

Maximum

Cool

Heat

Cool

Heat

Cool

Heat

Cool

Heat

°C

°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YLCC

342

436

10

-

46

-

5*

-

15

-

3

7

 

 

 

 

 

 

 

 

 

 

 

 

 

YLCC-H

342

436

10

-10

46

20

5*

30

15

50

3

7

* At water temperatures below the nominal limits, it is always necessary to use glycol-type antifreeze mixtures.

Limits of use,YLCC (cooling only unit)

Water discharge temperature: +6° C to +15° C.

Brine discharge temperature: -5° C to +6° C.

Temperature difference in heat exchanger: 3 to 7° C.

Maximum air intake temperature: +46° C.

Minimum ambient temperature: +10° C (standard), -18° C low ambient temperature kit (optional).

Limits of use, YLCC-H (heat pump unit)

Cool mode

Water discharge temperature: +6° C to +15° C.

Brine discharge temperature: -5° C to +6° C.

Temperature difference in heat exchanger: 3 to 7° C.

Maximum air intake temperature: +46° C.

Minimum ambient temperature: +10° C (standard), -18° C low ambient temperature kit (optional).

Nominal flows, cool only

The cooling capacities on the corresponding tables are valid for the following nominal flows:

 

Nominal

Pressure

Nominal

Available

Model

water flow

drop

air flow

pressure fan

 

l/h

Kpa

m3/h

Pa

 

 

 

 

 

YLCC-42

6 760

16.1

13 268

50

 

 

 

 

 

YLCC-62

11 020

43.5

20 122

50

 

 

 

 

 

YLCC-82

12 285

57

23 304

50

 

 

 

 

 

YLCC-102

16 424

94

28 834

50

 

 

 

 

 

YLCC-122

19 404

20.4

33 247

50

 

 

 

 

 

YLCC-152

22 948

45,6

38 312

50

 

 

 

 

 

Heat mode

Water discharge temperature: +30° C to +50° C.

Ambient temperature: -10° C to +20° C.

Temperature difference in heat exchanger: 3 to 7° C.

Minimum air intake temperature: 0° C with maximum dis- charge water temperature of 50° C.

Minimum air intake temperature: -5° C with maximum dis- charge water temperature of 45° C.

Test conditions

 

Outdoor air

 

Water

Voltage

temperature °C

Water intake

discharge

 

 

temperature

temperature

400 V

 

 

 

 

 

 

°C

°C

 

DB

WB

 

 

 

 

 

 

 

 

Summer

35

24

12

7

 

 

 

 

 

Winter

7

6

40

45

 

 

 

 

 

Nominal flows, heat pump

The capacities on the corresponding tables are valid for the following nominal flows:

 

Nominal water

Pressure

Nominal

Available

 

flow l/h

pressure

Model

drop

air flow

 

 

fan

 

 

 

Kpa

m3/h

 

Cool

Heat

Pa

 

 

 

 

 

 

 

 

 

YLCC-H-42

7 107

6 829

16.4

13 268

50

 

 

 

 

 

 

YLCC-H-62

10 041

10 045

36.6

20 122

50

 

 

 

 

 

 

YLCC-H-82

12 211

13 629

56.6

23 304

50

 

 

 

 

 

 

YLCC-H-102

16 165

16 103

91

28 834

50

 

 

 

 

 

 

YLCC-H-122

17 977

18 889

17,5

37 403

50

 

 

 

 

 

 

YLCC-H-152

22 085

20 801

42,3

37 403

50

 

 

 

 

 

 

10

Image 10
Contents Technical information Page Technical specifications IndexPage Mechanical specifications General characteristicsNomenclature Accessories ControlsAnti-vibratory supports Remote control accessoryFlow switch optional accessory Remote terminalPhysical data and electrical characteristics Cooling onlyHeat pump units YLCC-HLimits of use, YLCC-H heat pump unit Limits of useLimits of use,YLCC cooling only unit Nominal flows, cool onlyCooling capacities YLCC-102 YLCC-H-42 102 Heating capacities LWT CYLCC-H-102 YLCC/YLCC-H 42 YLCC/YLCC-H YLCC/YLCC-H 82YLCC/YLCC-H Fan performances 82/82VCorrecting factors Factors with water and glycolEnvironmental protection General informationInspection TransportationDrainage Location dimensionsClearances Locating and securing the unitHydraulic connections diagram Hydraulic connectionsCirculating pump Flow switchHydro kits GH Application to YLCC/YLCC-H unitsRemote control connection optional YLCC/YLCC-H 42, 62, 82 WiringYLCC/YLCC-H 122 Ylcc and YLCC-H control system Standard componentsInterconnecting diagram NTC ProbeRemote control unit Identification of system intakes and outletsSerial board RS485 Fig Programmable key FigCopying the Eeprom memory on the key RS485 serial boardUnit addressing Access to Direct parametersAccess to User parameters Unit controlInstallation of default parameters Access to Factory parametersAlarm reset Adjusting display contrastOperation of cooling cycle Operation of set pointsCompressors Operation of heating cycleDefrost cycle Pump operationCooling cycle compressor on Heating cycle compressor onAlarms and messages ID4 IdcomProbe calibration Buzzer configurationYellow and green LEDs on base plate Remote ON/OFFHeating cycle YLCC-H Summer cycle diagram forYLCC-HWinter cycle diagram forYLCC-H Cooling cycle YLCC-HGeneral dimensions mm Ylcc andYLCC-HYlcc andYLCC-H 82 Ylcc andYLCC-H Minimum Electrical Connection Clearance Ylcc andYLCC-H 122V Wiring diagram, YLCC-H 42 and 62, 400.3.50 1 400V, 3 ~, 50 Hz, NWiring diagram, YLCC-H 42 and 62, 400.3.50 2 Wiring diagram, YLCC-H 82, 400.3.50 1 Reg. a 400V, 3 ~, 50 Hz, NWiring diagram, YLCC-H 82, 400.3.50 2 Wiring diagram, YLCC-H 102, 400.3.50 1 Wiring diagram, YLCC-H 102, 400.3.50 2 Wiring diagram, YLCC-H 122, 400.3.50 1 Wiring Wiring diagram, YLCC-H 152, 400.3.50 1 Diagram, YLCC-H Wiring diagram, YLCC- 42 and 62, 400.3.50 1 Diagram, Ylcc Wiring diagram, YLCC- 82, 400.3.50 1 Diagram,YLCC Wiring diagram, YLCC- 102, 400.3.50 1 Diagram Wiring diagram, YLCC- 122, 400.3.50 1 Diagram Wiring diagram, YLCC- 152, 400.3.50 1 152 Page Ref. Y-R70102