Limits of use
| Voltage limits | DB air intake temperature to coil |
| Water outlet temperature |
| Temperature | |||||||
|
|
| differential between | ||||||||||
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
| Operating | cycle |
|
| Operating | cycle |
| water discharge and | ||
|
|
|
|
|
|
| intake | ||||||
Model | Nominal at 400 V |
|
|
|
|
|
|
|
| ||||
Minimum °C | Maximum °C | Minimum °C | Maximum °C | Minimum | Maximum | ||||||||
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
| |||
| Minimum | Maximum | Cool | Heat | Cool | Heat | Cool | Heat | Cool | Heat | °C | °C | |
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| |
YLCC | 342 | 436 | 10 | - | 46 | - | 5* | - | 15 | - | 3 | 7 | |
|
|
|
|
|
|
|
|
|
|
|
|
| |
| 342 | 436 | 10 | 46 | 20 | 5* | 30 | 15 | 50 | 3 | 7 |
* At water temperatures below the nominal limits, it is always necessary to use
Limits of use,YLCC (cooling only unit)
Water discharge temperature: +6° C to +15° C.
Brine discharge temperature:
Temperature difference in heat exchanger: 3 to 7° C.
Maximum air intake temperature: +46° C.
Minimum ambient temperature: +10° C (standard),
Limits of use, YLCC-H (heat pump unit)
Cool mode
Water discharge temperature: +6° C to +15° C.
Brine discharge temperature:
Temperature difference in heat exchanger: 3 to 7° C.
Maximum air intake temperature: +46° C.
Minimum ambient temperature: +10° C (standard),
Nominal flows, cool only
The cooling capacities on the corresponding tables are valid for the following nominal flows:
| Nominal | Pressure | Nominal | Available |
Model | water flow | drop | air flow | pressure fan |
| l/h | Kpa | m3/h | Pa |
|
|
|
|
|
6 760 | 16.1 | 13 268 | 50 | |
|
|
|
|
|
11 020 | 43.5 | 20 122 | 50 | |
|
|
|
|
|
12 285 | 57 | 23 304 | 50 | |
|
|
|
|
|
16 424 | 94 | 28 834 | 50 | |
|
|
|
|
|
19 404 | 20.4 | 33 247 | 50 | |
|
|
|
|
|
22 948 | 45,6 | 38 312 | 50 | |
|
|
|
|
|
Heat mode
Water discharge temperature: +30° C to +50° C.
Ambient temperature:
Temperature difference in heat exchanger: 3 to 7° C.
Minimum air intake temperature: 0° C with maximum dis- charge water temperature of 50° C.
Minimum air intake temperature:
Test conditions
| Outdoor air |
| Water | |
Voltage | temperature °C | Water intake | discharge | |
|
| temperature | temperature | |
400 V |
|
| ||
|
| |||
|
| °C | °C | |
| DB | WB | ||
|
|
| ||
|
|
|
|
|
Summer | 35 | 24 | 12 | 7 |
|
|
|
|
|
Winter | 7 | 6 | 40 | 45 |
|
|
|
|
|
Nominal flows, heat pump
The capacities on the corresponding tables are valid for the following nominal flows:
| Nominal water | Pressure | Nominal | Available | ||
| flow l/h | pressure | ||||
Model | drop | air flow | ||||
|
| fan | ||||
|
|
| Kpa | m3/h | ||
| Cool | Heat | Pa | |||
|
|
| ||||
|
|
|
|
|
| |
7 107 | 6 829 | 16.4 | 13 268 | 50 | ||
|
|
|
|
|
| |
10 041 | 10 045 | 36.6 | 20 122 | 50 | ||
|
|
|
|
|
| |
12 211 | 13 629 | 56.6 | 23 304 | 50 | ||
|
|
|
|
|
| |
16 165 | 16 103 | 91 | 28 834 | 50 | ||
|
|
|
|
|
| |
17 977 | 18 889 | 17,5 | 37 403 | 50 | ||
|
|
|
|
|
| |
22 085 | 20 801 | 42,3 | 37 403 | 50 | ||
|
|
|
|
|
|