Toshiba RAS-B10GKVP-E, RAS-B16GKVP-E, RAS-B13GKVP-E Appendix-5, Used screw Screw type Quantity

Page 110

Appendix

No.

Photo / Explanatory diagram

 

 

Procedure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove the motor base assembly, partition plate assembly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and the sound insulation board.

 

 

 

 

 

 

 

 

Motor base

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

assembly

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Related parts / Screws list

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Partition plate

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Used screw

 

 

 

 

 

 

 

 

 

 

assembly

 

 

 

 

 

 

 

Part name

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Screw type

Quantity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor base assembly

 

 

Ø4 × 8

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Including motor and fan)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Partition plate assembly

 

 

Ø4 × 8

3

 

 

 

 

 

 

 

 

 

 

Sound

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Including reactor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

insulation board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove the fixing screws of the heat exchanger and the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

valve fixing plate. Remove the compressor fixing bolt.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valve fixing plate

 

 

 

 

 

 

 

 

 

Heat exchanger

Related parts / Screws list

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Part name

 

 

Used screw

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Screw type

Quantity

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat exchanger

 

 

Ø4 × 8

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valve fixing plate

 

 

Ø4 × 8

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

bolt

3

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

As shown in the left figure, remove the set of refrigeration cycle assembly from the outdoor unit base plate.

*In this time, work attentively so that the cycle pipes are not damaged by dent or deformation. Apply protective measures to pipes if necessary.

1-7

Appendix-5

Image 110
Contents Split Type Contents For general public use Safety PrecautionsNew Refrigerant Air Conditioner Installation For Reference Specifications SpecificationsCooling Heating Operation Characteristic CurveCapacity Variation Ratio According to Temperature CoolingRefrigerant R410A Safety During Installation/ServicingRefrigerant Piping Installation Piping Materials and Joints UsedJoints Flare processing procedures and precautionsProcessing of Piping Materials 1 Thicknesses of annealed copper pipes Thickness mmFlare tool for R22 Conventional flare tool Flare tool for R410A Conventional flare toolClutch type Wing nut type 13.2 13.5 12.70 16.6 16.0 12.9 15.88 19.7 19.0Nm kgfcm Flare Connecting Procedures and Precautions43˚ Wrenches available on the marketGeneral tools Conventional tools can be used ToolsRequired Tools 1 Configuration of refrigerant charging Recharging of RefrigerantFlux Brazing of PipesMaterials for Brazing Brazing Never use gas other than Nitrogen gasConstruction Views Indoor UnitDetailed B leg part Outdoor UnitDetailed a leg part Identification Wiring DiagramColor Parts name Model name Rating Specifications of Electrical PartsParts name Type Specifications Refrigerant Cycle Diagram Refrigerant Cycle DiagramRAS-B13GKVP-E/RAS-13GAVP-E, RAS-B16GKVP-E/RAS-16GAVP-E Outdoor Temperature Standard Heat exchanger Compressor Condition COperation Data Cooling Outdoor MPa T1 C T2 C RpsOperation START/STOP Operation Mode Selection Control Block DiagramRemote Controller Hi-POWER Air PurifierFor Indoor Unit AssemblyOutdoor Unit Inverter MCC5009 P.C.BRole of indoor unit controller Operation DescriptionOutline of Air Conditioner Control Role of outdoor unit controllerOperation Description Filter IndicatorRemote Controller and Its Fuctions Auto Restart FunctionOutdoor unit Remote controllerIndoor unit +1.0 Cooling operationTs + +0.5+ M SymbolsIndication Fan speed + HIndication Fan speed Operation flow and applicable data, etc DescriptionHeating operation Cold draft preventive controlOutdoor unit Operation command Outdoor fan controlAir conditioner Alarm OFF statusRemote controller Indoor unit Outdoor temp Cooling current Heating current Release valueWhen temperature of the indoor Condition Operation flow and applicable data, etcCase of operation stop Defrost operationLouver position in cooling operation PowerfulThis function controls the air direction of the indoor unit Air directionCooling operation FanLouver*1 Fan speed *2 Operation buttonPresent status Pure button Air conditioner Td value Control operation PurposeOperation PMV open degree control Stop by Room temp. sensor Move toSH control Ta sensor controlClean operation Operation mode Operation time Clean operation timeSetting the clean operation Indoor P.C. boardSetting the remote controller Setting the selector switch on the main unitWhen the unit is in operation How to Set the Auto Restart FunctionWhen the unit is standby Not operating When the system is on stand-by not operating Power Failure During Timer OperationHow to Turn Off Filter Indicator When the system is operatingParts Name of Remote Controller Display Cooling operation Hi-POWER mode can not be set in Dry operationAutomatic operation Heating operationInstallation Procedure Safety CautionsAccessory and Installation Parts Optional Parts, Accessories and ToolsOptional Installation Parts Attachment bolt arrangement of outdoor unitNew tools for R410A Installation/Servicing ToolsChanges in the product and components New tools for R410A Applicable to R22 model ChangesMounting the installation plate Installation PlaceRemote controller When install the refrigerant pipes from the rearElectrical Work When the installation plate is directly mounted on the wallWiring Connection How to connect the connecting cable Die-cutting front panel slit How to remove the drain capHow to remove the drain hose Changing drain hoseCase of bottom right or bottom left piping How to attach the drain capHow to attach the drain hose Left-hand connection with pipingIndoor Unit Installation DrainagePrecautions for adding refrigerant Projection margin in flaring a Unit mm Draining the WaterRefrigerant Piping Connection Flaring Flaring size B Unit mmTightening Connection Use a vacuum pumpStripping length of connecting cable Packed Valve handling precautionsWiring Connection Hexagonal wrench is requiredTest Operation Auto Restart SettingHow to Set the Auto Restart Gas Leak TestControl circuitry has an uninsulated construction HOW to Diagnose the TroublePrecautions when handling the new inverter 3DV Inverter JAVP-E series insulated typeDo not lay the circuit board assembly flat Discharging methodFirst Confirmation Confirmation of Power SupplyConfirmation of Power Voltage Operation Which is not a Trouble Program OperationBlock display Description for self-diagnosis Code Primary JudgmentJudgment by Flashing LED of Indoor Unit CheckPress START/STOP button to release the service mode Self-Diagnosis by Remote Controller Check CodeHow to Use Remote Controller in Service Mode Press on or OFF buttonRemarks Block distinctionAir Judgment and action Block Cause of operation StatusBlock distinction Operation of diagnosis function Is the fuse F01 blown? Judgment of Trouble by Every SymptomIndoor Unit Including Remote Controller Only the indoor motor fan does not operate Primary check Is it possible toInspection procedure Troubleshooting for remote controller Primary check Outdoor unit does not operate Wiring Failure Interconnecting and Serial Signal WireInverter Assembly check Normal time1C1E Check Code 1C Miswiring in indoor/outdoor units and 1ECheck procedure Conduction check of micro-switch TroubleshootingHow to Check Whether the Air Purifier is Good or Not Operation checkHow to Check Whether the Minus Ion Generator is Good or Not Primary checkDiagnosis/Process flowchart Contents Summary How to Diagnose Trouble in Outdoor UnitSummarized Inner Diagnosis of Inverter Assembly Operating precautions How to Check Simply the Main PartsHow to Check the P.C. Board Indoor Unit Inspection proceduresCheck procedures Procedure Check points Causes+12V +5V Sensor characteristic table11-9-2. P.C.BoardLayout Resistance value k 100OutdoorUnit Part name Checking procedureIndoor Unit Other Parts Part nameTester rod Resistance value Good product Checking Method for Each PartCase that product is good Symptom CN30012-1 Indoor Unit HOW to Replace the Main PartsPart name Procedures Remarks How to assemble the front panel How to assemble the high voltage generator How to assemble the electric parts box Drain pan above the claws and atSecure it Slightly, and remove the bearing base Remove the two screws used to secure Bearing baseRaise the left side of the heat exchanger Secure using the fixing screw Screw Motor band Right Drain pipe Board layout Part name Procedure RemarksMicrocomputer Hands on the parts, etc Wear gloves for this jobOtherwise, you may injure your AttachmentProcedure Remarks Front cabinet Detachment Some cases Lead connected to compressor ProcedureTerminal block Disengage the four claws of the P.C. board baseSide cabinet left With a burner Take care to keep the 4-way valve awayHandling precaution Shown in the above figure is TE sensor outdoor heat exchanging temperature sensorTS sensor Suction pipe temperature sensor Part name Procedure Parts name Qty RemarksMCC-5009 Part Description Exploded Views and Parts List13-1 Indoor Unit 221 43047671 Pipe, Outlet402 407, 408 403 404 406 410401 405 14, 15, 17, 18 104 13-3. P.C. Board Layout Appendix-1 Required parts for installation work RecommendationPart name ’ty Specifications/Vendor Remarks Applicable Models RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-EAppendix-2 Required tools for installation workPart name Specifications Usage Cord heater installation wiring diagram Appendix-3Appendix-4 Cord heater installation work procedurePhoto / Explanatory diagram Procedure Appendix-5 Used screw Screw type QuantityAppendix-6 Appendix-7 Photo / Explanatory diagram Procedure Assembly Appendix-8Ø3.4 burring hole Upward Ø3.4 burring hole Downward Drawing of thermostat fixing plateMaterial SGCC-Z08, Thickness 0.8t Appendix-9 Appendix-10 Toshiba Carrier Corporation

RAS-10GAVP-E, RAS-16GAVP-E, RAS-13GAVP-E, RAS-B10GKVP-E, RAS-B13GKVP-E specifications

Toshiba has long been a renowned name in the world of air conditioning, delivering reliable and energy-efficient solutions that meet the demands of modern living. Among their innovative product line, the Toshiba RAS-B13GKVP-E, RAS-10GAVP-E, RAS-B10GKVP-E, RAS-16GKVP-E, and RAS-13GAVP-E stand out for their advanced features and cutting-edge technologies.

The RAS-B13GKVP-E is a powerful air conditioning unit designed for medium-sized rooms. It boasts a robust cooling capacity, ensuring comfort even during the hottest days. One of its standout features is the inverter technology, which optimizes energy consumption by adjusting the compressor speed according to the temperature, resulting in significant energy savings.

Next, the RAS-10GAVP-E is tailored for smaller spaces, offering efficient cooling and heating capabilities. It comes with an easy-to-use remote control and a user-friendly interface, allowing for effortless operation. The model also incorporates a quiet operation feature, making it suitable for bedrooms and study areas where noise can be a distraction.

The RAS-B10GKVP-E strikes a balance between size and efficiency, ideal for compact living spaces. Its dual cooling and heating function ensures year-round climate control. This model further enhances indoor air quality with its built-in filters, which capture dust and allergens, creating a healthier environment for occupants.

For larger areas, the RAS-16GKVP-E provides an impressive cooling capacity combined with turbo mode functionality. This feature enables rapid cooling of spaces during sweltering summer days. Its sleek design and compact form factor allow for easy installation, making this unit a popular choice for both residential and commercial applications.

Lastly, the RAS-13GAVP-E excels in energy efficiency with its eco-friendly refrigerant options. It is equipped with a smart control system that allows users to monitor and adjust settings remotely, adding convenience and flexibility to its operation. This model is particularly beneficial for users looking to minimize their carbon footprint while enjoying the comfort of climate control.

Overall, Toshiba's lineup of air conditioning units, including RAS-B13GKVP-E, RAS-10GAVP-E, RAS-B10GKVP-E, RAS-16GKVP-E, and RAS-13GAVP-E, promises high performance, energy efficiency, and advanced technology. These features affirm Toshiba's commitment to creating a comfortable indoor environment while ensuring sustainability and user satisfaction.