Toshiba RAS-B13GKVP-E Troubleshooting, How to Check Whether the Air Purifier is Good or Not

Page 73

11-7. Troubleshooting

11-7-1. How to Check Whether the Air Purifier is Good or Not

Primary check

Turn off the power breaker once, and turn on again after 10 seconds.

Does the OPERATION indicator flash?

YES

Turn off the power breaker and remove CN34 (Micro switch connector). Short-circuit between 1 and 2 pin of CN34 at PC side, and turn on the power breaker after 10 seconds.

Is DC12V applied

between 1 (Red/DC12V) and (Brown/GND) of CN1 of the high-voltage generator?

YES

Is there conduction of

micro-switch connector under OFF status of the micro-switch (Front panel opened)?

NO

Is there conduction of

micro-switch connector under ON status of the micro-switch (Front panel closed)?

NO

NO

Is DC12V applied

NO

between 1 (+) and 2 (–)

 

of CN33 of the main

 

 

P.C. board (MCC5020)?

 

 

 

 

 

YES

 

 

YES

Micro-switch is stuck

 

 

 

NO

Micro-switch malfunction

To item “Power supply is not turned on”

Replace the main P.C. board (MCC5020)

Replace micro-switch.

• Conduction check of micro-switch

YES

1)Check operation while short-circuiting CN34 of the main P.C. board.

2)Perform air purifying operation by the remote controller.

In this time, check that the remote controller is in status which is shortened by time on the reactivation preventive timer and all display indicators go on for approx. 3 seconds when a signal is received.

( If time on the reactivation preventive timer is not shortened,) the high-voltage is not applied to electrode of the air purifier for approx. 1 hour.

While the air purifier operates, check that the fan speed [AUTO] is not displayed. (Because the power ON/OFF is controlled on the program)

3)Be sure not to touch the electric dust collector, ionizer, or ionized wire unit with the human body.

Push the switch ON ON

Release the switch

OFF

Tester

Operation check

Does the indoor fan rotate?

YES

Does the PURE indicator (Blue) or the FILTER indicator (Orange) go on?

YES

Does the PURE indicator

go off within 2 seconds after

it was ON, and does the FILTER indicator (Orange) go on?

 

YES

 

 

 

 

Are the electric dust

NO

collector and ionizer dried?

(Electrode check)

 

 

YES

 

NO

NO

Is DC-5V to DC-10V

applied between

NO 4 (Brown/Negative voltage) NO and 2 (Brown/GND)

of CN33 of the main P.C. board?

YES

Dry the electric dust collector and ionizer.

To item “Only indoor fan does not operate”

Replace the main P.C. board (MCC5020).

How to check output of the air purifier <Caution on High Voltage!!>

Collector output

GND

Referring to the right figure, check the

 

Be sure not to come

 

 

Ionizer

 

 

 

high-output voltage of the air filter unit.

 

 

 

 

to contact to the gray

 

 

output

(NOTE)

 

 

 

 

part or not to touch

 

 

 

Use an exclusive high voltage tester;

 

 

 

 

 

the ionized cables.

High-voltage tester

otherwise the tester may be broken.

 

 

 

 

 

 

Refer to items, cleaning and check for the electric dust collector/ionizer/ ionized wire units.

When the ionized wire is

( disconnected or when dirt is ) not cleaned even cleaned, replace each unit.

YES

YES

Is output of the ionizer approx. 4.0 kV to 4.8 kV? Is output of the collector approx. 3.0 kV to 3.8 kV?

YES

Are the electric dust

collector/ionizer/ionized wire units dirty?

Is an abnormal sound (cracking noise) heard from the electrode?

NO

Replace the high-voltage generator.

NO

No trouble

– 73 –

Image 73
Contents Split Type Contents New Refrigerant Air Conditioner Installation Safety PrecautionsFor general public use For Reference Specifications SpecificationsCapacity Variation Ratio According to Temperature Operation Characteristic CurveCooling Heating CoolingRefrigerant Piping Installation Safety During Installation/ServicingRefrigerant R410A Piping Materials and Joints UsedProcessing of Piping Materials Flare processing procedures and precautionsJoints 1 Thicknesses of annealed copper pipes Thickness mmClutch type Wing nut type Flare tool for R410A Conventional flare toolFlare tool for R22 Conventional flare tool 13.2 13.5 12.70 16.6 16.0 12.9 15.88 19.7 19.043˚ Flare Connecting Procedures and PrecautionsNm kgfcm Wrenches available on the marketRequired Tools ToolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingMaterials for Brazing Brazing of PipesFlux Never use gas other than Nitrogen gas BrazingIndoor Unit Construction ViewsDetailed a leg part Outdoor UnitDetailed B leg part Color Wiring DiagramIdentification Parts name Type Specifications Specifications of Electrical PartsParts name Model name Rating Refrigerant Cycle Diagram Refrigerant Cycle DiagramRAS-B13GKVP-E/RAS-13GAVP-E, RAS-B16GKVP-E/RAS-16GAVP-E Operation Data Cooling Temperature Standard Heat exchanger Compressor Condition COutdoor Outdoor MPa T1 C T2 C RpsRemote Controller Control Block DiagramOperation START/STOP Operation Mode Selection Hi-POWER Air PurifierOutdoor Unit Inverter AssemblyFor Indoor Unit MCC5009 P.C.BOutline of Air Conditioner Control Operation DescriptionRole of indoor unit controller Role of outdoor unit controllerRemote Controller and Its Fuctions Filter IndicatorOperation Description Auto Restart FunctionIndoor unit Remote controllerOutdoor unit Ts + Cooling operation+1.0 +0.5Indication Fan speed Symbols+ M + HHeating operation Operation flow and applicable data, etc DescriptionIndication Fan speed Cold draft preventive controlAir conditioner Alarm Operation command Outdoor fan controlOutdoor unit OFF statusOutdoor temp Cooling current Heating current Release value Remote controller Indoor unitWhen temperature of the indoor Case of operation stop Operation flow and applicable data, etcCondition Defrost operationThis function controls the air direction of the indoor unit PowerfulLouver position in cooling operation Air directionFan Cooling operationPresent status Pure button Air conditioner Operation buttonLouver*1 Fan speed *2 Operation PurposeTd value Control operation SH control Move toPMV open degree control Stop by Room temp. sensor Ta sensor controlOperation mode Operation time Clean operation time Clean operationIndoor P.C. board Setting the clean operationSetting the selector switch on the main unit Setting the remote controllerWhen the unit is standby Not operating How to Set the Auto Restart FunctionWhen the unit is in operation How to Turn Off Filter Indicator Power Failure During Timer OperationWhen the system is on stand-by not operating When the system is operatingParts Name of Remote Controller Display Automatic operation Hi-POWER mode can not be set in Dry operationCooling operation Heating operationSafety Cautions Installation ProcedureOptional Installation Parts Optional Parts, Accessories and ToolsAccessory and Installation Parts Attachment bolt arrangement of outdoor unitChanges in the product and components Installation/Servicing ToolsNew tools for R410A New tools for R410A Applicable to R22 model ChangesRemote controller Installation PlaceMounting the installation plate When install the refrigerant pipes from the rearWiring Connection How to connect the connecting cable When the installation plate is directly mounted on the wallElectrical Work How to remove the drain hose How to remove the drain capDie-cutting front panel slit Changing drain hoseHow to attach the drain hose How to attach the drain capCase of bottom right or bottom left piping Left-hand connection with pipingDrainage Indoor Unit InstallationPrecautions for adding refrigerant Refrigerant Piping Connection Flaring Draining the WaterProjection margin in flaring a Unit mm Flaring size B Unit mmUse a vacuum pump Tightening ConnectionWiring Connection Packed Valve handling precautionsStripping length of connecting cable Hexagonal wrench is requiredHow to Set the Auto Restart Auto Restart SettingTest Operation Gas Leak TestPrecautions when handling the new inverter 3DV Inverter HOW to Diagnose the TroubleControl circuitry has an uninsulated construction JAVP-E series insulated typeDischarging method Do not lay the circuit board assembly flatConfirmation of Power Voltage Confirmation of Power SupplyFirst Confirmation Operation Which is not a Trouble Program OperationJudgment by Flashing LED of Indoor Unit Primary JudgmentBlock display Description for self-diagnosis Code CheckHow to Use Remote Controller in Service Mode Self-Diagnosis by Remote Controller Check CodePress START/STOP button to release the service mode Press on or OFF buttonAir Judgment and action Block Cause of operation Block distinctionRemarks StatusBlock distinction Operation of diagnosis function Indoor Unit Including Remote Controller Judgment of Trouble by Every SymptomIs the fuse F01 blown? Is it possible to Only the indoor motor fan does not operate Primary checkInspection procedure Troubleshooting for remote controller Primary check Inverter Assembly check Wiring Failure Interconnecting and Serial Signal WireOutdoor unit does not operate Normal timeCheck procedure Check Code 1C Miswiring in indoor/outdoor units and 1E1C1E How to Check Whether the Air Purifier is Good or Not TroubleshootingConduction check of micro-switch Operation checkPrimary check How to Check Whether the Minus Ion Generator is Good or NotSummarized Inner Diagnosis of Inverter Assembly How to Diagnose Trouble in Outdoor UnitDiagnosis/Process flowchart Contents Summary How to Check the P.C. Board Indoor Unit How to Check Simply the Main PartsOperating precautions Inspection proceduresProcedure Check points Causes Check procedures11-9-2. P.C.BoardLayout Sensor characteristic table+12V +5V Resistance value k 100Indoor Unit Other Parts Part name Checking procedureOutdoorUnit Part nameCase that product is good Checking Method for Each PartTester rod Resistance value Good product CN300 SymptomPart name Procedures Remarks HOW to Replace the Main Parts12-1 Indoor Unit How to assemble the front panel How to assemble the high voltage generator Drain pan above the claws and at How to assemble the electric parts boxSecure it Raise the left side of the heat exchanger Remove the two screws used to secure Bearing baseSlightly, and remove the bearing base Secure using the fixing screw Screw Motor band Right Drain pipe Microcomputer Part name Procedure RemarksBoard layout Otherwise, you may injure your Wear gloves for this jobHands on the parts, etc AttachmentProcedure Remarks Front cabinet Detachment Some cases Terminal block ProcedureLead connected to compressor Disengage the four claws of the P.C. board baseSide cabinet left Take care to keep the 4-way valve away With a burnerHandling precaution TS sensor Suction pipe temperature sensor TE sensor outdoor heat exchanging temperature sensorShown in the above figure is Parts name Qty Remarks Part name ProcedureMCC-5009 13-1 Indoor Unit Exploded Views and Parts ListPart Description 221 43047671 Pipe, Outlet402 407, 408 403 404 406 410401 405 14, 15, 17, 18 104 13-3. P.C. Board Layout Part name ’ty Specifications/Vendor Remarks Required parts for installation work RecommendationAppendix-1 Applicable Models RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-EPart name Specifications Usage Required tools for installation workAppendix-2 Appendix-3 Cord heater installation wiring diagramPhoto / Explanatory diagram Procedure Cord heater installation work procedureAppendix-4 Used screw Screw type Quantity Appendix-5Appendix-6 Appendix-7 Appendix-8 Photo / Explanatory diagram Procedure AssemblyMaterial SGCC-Z08, Thickness 0.8t Appendix-9 Drawing of thermostat fixing plateØ3.4 burring hole Upward Ø3.4 burring hole Downward Appendix-10 Toshiba Carrier Corporation

RAS-10GAVP-E, RAS-16GAVP-E, RAS-13GAVP-E, RAS-B10GKVP-E, RAS-B13GKVP-E specifications

Toshiba has long been a renowned name in the world of air conditioning, delivering reliable and energy-efficient solutions that meet the demands of modern living. Among their innovative product line, the Toshiba RAS-B13GKVP-E, RAS-10GAVP-E, RAS-B10GKVP-E, RAS-16GKVP-E, and RAS-13GAVP-E stand out for their advanced features and cutting-edge technologies.

The RAS-B13GKVP-E is a powerful air conditioning unit designed for medium-sized rooms. It boasts a robust cooling capacity, ensuring comfort even during the hottest days. One of its standout features is the inverter technology, which optimizes energy consumption by adjusting the compressor speed according to the temperature, resulting in significant energy savings.

Next, the RAS-10GAVP-E is tailored for smaller spaces, offering efficient cooling and heating capabilities. It comes with an easy-to-use remote control and a user-friendly interface, allowing for effortless operation. The model also incorporates a quiet operation feature, making it suitable for bedrooms and study areas where noise can be a distraction.

The RAS-B10GKVP-E strikes a balance between size and efficiency, ideal for compact living spaces. Its dual cooling and heating function ensures year-round climate control. This model further enhances indoor air quality with its built-in filters, which capture dust and allergens, creating a healthier environment for occupants.

For larger areas, the RAS-16GKVP-E provides an impressive cooling capacity combined with turbo mode functionality. This feature enables rapid cooling of spaces during sweltering summer days. Its sleek design and compact form factor allow for easy installation, making this unit a popular choice for both residential and commercial applications.

Lastly, the RAS-13GAVP-E excels in energy efficiency with its eco-friendly refrigerant options. It is equipped with a smart control system that allows users to monitor and adjust settings remotely, adding convenience and flexibility to its operation. This model is particularly beneficial for users looking to minimize their carbon footprint while enjoying the comfort of climate control.

Overall, Toshiba's lineup of air conditioning units, including RAS-B13GKVP-E, RAS-10GAVP-E, RAS-B10GKVP-E, RAS-16GKVP-E, and RAS-13GAVP-E, promises high performance, energy efficiency, and advanced technology. These features affirm Toshiba's commitment to creating a comfortable indoor environment while ensuring sustainability and user satisfaction.