Toshiba RAS-B16GKVP-E Optional Parts, Accessories and Tools, Optional Installation Parts

Page 48

10-2. Optional Parts, Accessories and Tools

10-2-1. Optional Installation Parts

Part Code

 

Parts name

 

Q’ty

 

 

 

 

 

 

 

Refrigerant piping

 

 

 

 

 

 

 

Y

Indoor unit name

Liquid side (Outer diameter)

Gas side (Outer diameter)

1 ea.

 

 

 

RAS-B10GKVP-E, B13GKVP-E

6.35 mm

9.52 mm

 

 

 

 

 

 

 

 

RAS-B16GKVP-E

6.35 mm

12.7 mm

 

 

 

 

 

 

Z

Shield pipe (for extension drain hose) (polyethylene foam, 6 mm thick)

1

 

 

 

 

 

Attachment bolt arrangement of outdoor unit

Secure the outdoor unit with the attachment bolts and nuts if the unit is likely to be exposed to a strong wind.

Use Ø8 mm or Ø10 mm anchor bolts and nuts.

If it is necessary to drain the defrost water, attach drain nipple to the base plate of the outdoor unit before installing it.

Elongated drain hole

( ￿ )

Suction side

Drain hole

Diffuser ( ￿ )

10-2-2. Accessory and Installation Parts

Part No.

Part name (Q’ty)

Part No.

Part name (Q’ty)

Part No.

Part name (Q’ty)

Drain nipple* × 1

 

 

 

Installation plate × 1

Zeolite-plus filter × 1

 

(RAS-10GAVP-E,

 

13GAVP-E, 16GAVP-E)

 

Š

Water-proof rubber cap* × 2

Wireless remote control × 1

 

Plasma pure filter × 1

 

(RAS-10GAVP-E,

 

 

13GAVP-E, 16GAVP-E)

 

 

 

Parts marked with asterisk (*) are

 

 

 

packaged with the outdoor unit.

ƒ

 

 

 

Battery × 2

 

Mounting screw Ø4 × 25L × 6

 

<Others>

 

 

 

 

 

 

 

Name

 

 

 

 

Owner’s manual

ˆ

Remote control

 

Installation manual

 

 

 

 

 

 

 

Remote control holder × 1

 

holder mounting screw

Important information and warning*

 

Ø3.1 × 16L × 2

This model is not equipped with an extension drain hose.

 

B/W strips*

 

 

 

 

(Energy efficiency labels)

– 48 –

Image 48
Contents Split Type Contents Safety Precautions New Refrigerant Air Conditioner InstallationFor general public use For Reference Specifications SpecificationsOperation Characteristic Curve Capacity Variation Ratio According to TemperatureCooling Heating CoolingSafety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping Materials and Joints UsedFlare processing procedures and precautions Processing of Piping MaterialsJoints 1 Thicknesses of annealed copper pipes Thickness mmFlare tool for R410A Conventional flare tool Clutch type Wing nut typeFlare tool for R22 Conventional flare tool 13.2 13.5 12.70 16.6 16.0 12.9 15.88 19.7 19.0Flare Connecting Procedures and Precautions 43˚Nm kgfcm Wrenches available on the marketTools Required ToolsGeneral tools Conventional tools can be used 1 Configuration of refrigerant charging Recharging of RefrigerantBrazing of Pipes Materials for BrazingFlux Brazing Never use gas other than Nitrogen gasConstruction Views Indoor UnitOutdoor Unit Detailed a leg partDetailed B leg part Wiring Diagram ColorIdentification Specifications of Electrical Parts Parts name Type SpecificationsParts name Model name Rating Refrigerant Cycle Diagram Refrigerant Cycle DiagramRAS-B13GKVP-E/RAS-13GAVP-E, RAS-B16GKVP-E/RAS-16GAVP-E Temperature Standard Heat exchanger Compressor Condition C Operation Data CoolingOutdoor Outdoor MPa T1 C T2 C RpsControl Block Diagram Remote ControllerOperation START/STOP Operation Mode Selection Hi-POWER Air PurifierAssembly Outdoor Unit InverterFor Indoor Unit MCC5009 P.C.BOperation Description Outline of Air Conditioner ControlRole of indoor unit controller Role of outdoor unit controllerFilter Indicator Remote Controller and Its FuctionsOperation Description Auto Restart FunctionRemote controller Indoor unitOutdoor unit Cooling operation Ts ++1.0 +0.5Symbols Indication Fan speed+ M + HOperation flow and applicable data, etc Description Heating operationIndication Fan speed Cold draft preventive controlOperation command Outdoor fan control Air conditioner AlarmOutdoor unit OFF statusRemote controller Indoor unit Outdoor temp Cooling current Heating current Release valueWhen temperature of the indoor Operation flow and applicable data, etc Case of operation stopCondition Defrost operationPowerful This function controls the air direction of the indoor unitLouver position in cooling operation Air directionCooling operation FanOperation button Present status Pure button Air conditionerLouver*1 Fan speed *2 Purpose OperationTd value Control operation Move to SH controlPMV open degree control Stop by Room temp. sensor Ta sensor controlClean operation Operation mode Operation time Clean operation timeSetting the clean operation Indoor P.C. boardSetting the remote controller Setting the selector switch on the main unitHow to Set the Auto Restart Function When the unit is standby Not operatingWhen the unit is in operation Power Failure During Timer Operation How to Turn Off Filter IndicatorWhen the system is on stand-by not operating When the system is operatingParts Name of Remote Controller Display Hi-POWER mode can not be set in Dry operation Automatic operationCooling operation Heating operationInstallation Procedure Safety CautionsOptional Parts, Accessories and Tools Optional Installation PartsAccessory and Installation Parts Attachment bolt arrangement of outdoor unitInstallation/Servicing Tools Changes in the product and componentsNew tools for R410A New tools for R410A Applicable to R22 model ChangesInstallation Place Remote controllerMounting the installation plate When install the refrigerant pipes from the rearWhen the installation plate is directly mounted on the wall Wiring Connection How to connect the connecting cableElectrical Work How to remove the drain cap How to remove the drain hoseDie-cutting front panel slit Changing drain hoseHow to attach the drain cap How to attach the drain hoseCase of bottom right or bottom left piping Left-hand connection with pipingIndoor Unit Installation DrainagePrecautions for adding refrigerant Draining the Water Refrigerant Piping Connection FlaringProjection margin in flaring a Unit mm Flaring size B Unit mmTightening Connection Use a vacuum pumpPacked Valve handling precautions Wiring ConnectionStripping length of connecting cable Hexagonal wrench is requiredAuto Restart Setting How to Set the Auto RestartTest Operation Gas Leak TestHOW to Diagnose the Trouble Precautions when handling the new inverter 3DV InverterControl circuitry has an uninsulated construction JAVP-E series insulated typeDo not lay the circuit board assembly flat Discharging methodConfirmation of Power Supply Confirmation of Power VoltageFirst Confirmation Operation Which is not a Trouble Program OperationPrimary Judgment Judgment by Flashing LED of Indoor UnitBlock display Description for self-diagnosis Code CheckSelf-Diagnosis by Remote Controller Check Code How to Use Remote Controller in Service ModePress START/STOP button to release the service mode Press on or OFF buttonBlock distinction Air Judgment and action Block Cause of operationRemarks StatusBlock distinction Operation of diagnosis function Judgment of Trouble by Every Symptom Indoor Unit Including Remote ControllerIs the fuse F01 blown? Only the indoor motor fan does not operate Primary check Is it possible toInspection procedure Troubleshooting for remote controller Primary check Wiring Failure Interconnecting and Serial Signal Wire Inverter Assembly checkOutdoor unit does not operate Normal timeCheck Code 1C Miswiring in indoor/outdoor units and 1E Check procedure1C1E Troubleshooting How to Check Whether the Air Purifier is Good or NotConduction check of micro-switch Operation checkHow to Check Whether the Minus Ion Generator is Good or Not Primary checkHow to Diagnose Trouble in Outdoor Unit Summarized Inner Diagnosis of Inverter AssemblyDiagnosis/Process flowchart Contents Summary How to Check Simply the Main Parts How to Check the P.C. Board Indoor UnitOperating precautions Inspection proceduresCheck procedures Procedure Check points CausesSensor characteristic table 11-9-2. P.C.BoardLayout+12V +5V Resistance value k 100Part name Checking procedure Indoor Unit Other PartsOutdoorUnit Part nameChecking Method for Each Part Case that product is goodTester rod Resistance value Good product Symptom CN300HOW to Replace the Main Parts Part name Procedures Remarks12-1 Indoor Unit How to assemble the front panel How to assemble the high voltage generator How to assemble the electric parts box Drain pan above the claws and atSecure it Remove the two screws used to secure Bearing base Raise the left side of the heat exchangerSlightly, and remove the bearing base Secure using the fixing screw Screw Motor band Right Drain pipe Part name Procedure Remarks MicrocomputerBoard layout Wear gloves for this job Otherwise, you may injure yourHands on the parts, etc AttachmentProcedure Remarks Front cabinet Detachment Some cases Procedure Terminal blockLead connected to compressor Disengage the four claws of the P.C. board baseSide cabinet left With a burner Take care to keep the 4-way valve awayHandling precaution TE sensor outdoor heat exchanging temperature sensor TS sensor Suction pipe temperature sensorShown in the above figure is Part name Procedure Parts name Qty RemarksMCC-5009 Exploded Views and Parts List 13-1 Indoor UnitPart Description 221 43047671 Pipe, Outlet402 407, 408 403 404 406 410401 405 14, 15, 17, 18 104 13-3. P.C. Board Layout Required parts for installation work Recommendation Part name ’ty Specifications/Vendor RemarksAppendix-1 Applicable Models RAS-10GAVP-E, RAS-13GAVP-E, RAS-16GAVP-ERequired tools for installation work Part name Specifications UsageAppendix-2 Cord heater installation wiring diagram Appendix-3Cord heater installation work procedure Photo / Explanatory diagram ProcedureAppendix-4 Appendix-5 Used screw Screw type QuantityAppendix-6 Appendix-7 Photo / Explanatory diagram Procedure Assembly Appendix-8Drawing of thermostat fixing plate Material SGCC-Z08, Thickness 0.8t Appendix-9Ø3.4 burring hole Upward Ø3.4 burring hole Downward Appendix-10 Toshiba Carrier Corporation

RAS-10GAVP-E, RAS-16GAVP-E, RAS-13GAVP-E, RAS-B10GKVP-E, RAS-B13GKVP-E specifications

Toshiba has long been a renowned name in the world of air conditioning, delivering reliable and energy-efficient solutions that meet the demands of modern living. Among their innovative product line, the Toshiba RAS-B13GKVP-E, RAS-10GAVP-E, RAS-B10GKVP-E, RAS-16GKVP-E, and RAS-13GAVP-E stand out for their advanced features and cutting-edge technologies.

The RAS-B13GKVP-E is a powerful air conditioning unit designed for medium-sized rooms. It boasts a robust cooling capacity, ensuring comfort even during the hottest days. One of its standout features is the inverter technology, which optimizes energy consumption by adjusting the compressor speed according to the temperature, resulting in significant energy savings.

Next, the RAS-10GAVP-E is tailored for smaller spaces, offering efficient cooling and heating capabilities. It comes with an easy-to-use remote control and a user-friendly interface, allowing for effortless operation. The model also incorporates a quiet operation feature, making it suitable for bedrooms and study areas where noise can be a distraction.

The RAS-B10GKVP-E strikes a balance between size and efficiency, ideal for compact living spaces. Its dual cooling and heating function ensures year-round climate control. This model further enhances indoor air quality with its built-in filters, which capture dust and allergens, creating a healthier environment for occupants.

For larger areas, the RAS-16GKVP-E provides an impressive cooling capacity combined with turbo mode functionality. This feature enables rapid cooling of spaces during sweltering summer days. Its sleek design and compact form factor allow for easy installation, making this unit a popular choice for both residential and commercial applications.

Lastly, the RAS-13GAVP-E excels in energy efficiency with its eco-friendly refrigerant options. It is equipped with a smart control system that allows users to monitor and adjust settings remotely, adding convenience and flexibility to its operation. This model is particularly beneficial for users looking to minimize their carbon footprint while enjoying the comfort of climate control.

Overall, Toshiba's lineup of air conditioning units, including RAS-B13GKVP-E, RAS-10GAVP-E, RAS-B10GKVP-E, RAS-16GKVP-E, and RAS-13GAVP-E, promises high performance, energy efficiency, and advanced technology. These features affirm Toshiba's commitment to creating a comfortable indoor environment while ensuring sustainability and user satisfaction.