Toshiba RAS-10SAVP-E, RAS-B13SKVP-E, RAS-B10SKVP-E service manual Setup value Power OFF

Page 41

Item

Operation flow and applicable data, etc.

 

Description

 

 

 

 

14. Pulse motor

This function controls throttle amount of the refriger-

1)

When starting the operation, move the

valve (PMV)

ant in the refrigerating cycle.

 

valve until it fits to the stopper. (Initialize)

control

According to operating status of the air conditioner,

 

* In this time, “Click” sound may be heard.

 

 

 

this function controls the open degree of valve with

2)

Adjust the open degree of valve by super

 

an expansion valve with pulse motor.

 

 

heat amount. (SH control)

 

 

 

 

 

3) If the discharge temperature was exces-

 

 

sively up, adjust the open degree of valve

 

Starting up

so that it is in the range of set tempera-

 

ture. (Discharge temp. control)

 

 

 

 

4) When defrost operation is performed, the

 

Initialize

open degree of PMV is adjusted accord-

 

ing to each setup conditions; during

 

 

 

 

preparation for defrost or during defrost

 

 

operation (4-way valve is inversed.).

 

Move to initial position

5) When turn off the compressor by thermo.

 

OFF or STOP by remote controller, the

 

 

open degree of the PMV is adjusted to

 

 

the setup valve.

 

 

Compressor ON

SH control

 

Td

 

release control

 

 

 

PMV open degree control

 

Stop by

Thermo. OFF

Defrost

remote controller

 

 

Setup value

Setup value

Setup value

Power OFF

 

 

*SH (Super Heat amount) =

Ts (Temperature of suction pipe of the compressor) –

Tc or Te (Heat exchanger temperature at evaporation side)

*PMV: Pulse Motor Valve

– 41 –

Image 41
Contents AIR-CONDITIONER Contents For general public use New Refrigerant Air Conditioner InstallationFor Reference Specifications SpecificationsRAS-10SKVP-ND RAS-13SKVP-ND RAS-16SKVP-ND Heating Operation Characteristic CurveCooling CurrentCooling Capacity Variation Ratio According to TemperatureHeating Capacity ratio % 110 100Refrigerant Piping Installation Safety During Installation/ServicingPiping Materials and Joints Used Copper PipesJoints Flare processing procedures and precautionsProcessing of Piping Materials Clutch type Wing nut type Flare tool for R410A Conventional flare toolFlare tool for R22 Conventional flare tool DiameterWrenches available on the market Flare Connecting Procedures and PrecautionsNm kgfcm General tools Conventional tools can be used ToolsRequired Tools Recharging of Refrigerant 1 Configuration of refrigerant chargingFlux Brazing of PipesMaterials for Brazing Never use gas other than Nitrogen gas BrazingIndoor Unit Construction ViewsWH-H05JE Outdoor Unit Mounting dimensions of anchor boltDetailed a leg part Detailed B leg partMCC-5009 BoardRAS-10SAVP-ND, RAS-13SAVP-ND, RAS-16SAVP-ND MCC-5045MP24Z3N Parts name Type SpecificationsParts name Model name Rating CAM-MD12TF DC12VCAM-B22YGTF-3 Refrigerant Cycle DiagramOperation Data Cooling AUTO, COOL, DRY, Heat Operation START/STOP Operation Mode SelectionSleep Mode MCC5009 P.C.B Outdoor Unit Inverter AssemblyFor Indoor Unit Role of indoor unit controller Outline of Air Conditioner ControlRole of outdoor unit controller  Operations followed toRemote Controller and Its Fuctions Filter IndicatorOperation Description Auto Restart FunctionIndoor unit Remote controllerOutdoor unit ON/OFFDRY operation Auto operationIndoor fan air flow rate SymbolsIndication Fan speed Heating operation Operation flow and applicable data, etc DescriptionIndication Fan speed Cold draft preventive controlMode, by the conditions Outdoor temperature ToOutdoor fan shown Table is selectedRemote controller Indoor unit Exchanger detects evaporation temperature and controls When temperature of the indoorCompressor speed so that temperature of the heat Exchanger detects condensation temperatureCase of operation stop Operation flow and applicable data, etcCondition Defrost operationLouver position in heating operation Louver position in cooling operationLouver position in dry operation Air directionCooling operation SleepMode If the filter lamp goes on, push Reset When keeping Reset button pushed forPush Reset button again TemporaryOperation PurposeSH control Release control PMV open degree control Stop by Setup value Power OFFClean operation Setting the clean operation Setting the clean operation cancelThis completes the clean operation setting Indoor P.C. boardSetting the unit Setting the remote controller8C Heat operation -ND model only Indoor control P.C. board At shipment PurposeHeat operation With Quiet control/Non-select method Purpose To reduce noise, Reset buttonOutdoor During stop of air conditioner StartDuring operation of air conditioner On 8˚C HeatIndoor fan control Basic fan controlAuto TSC Compressor speed control Refer to 4. Capacity controlOFF Base plate cord heater control PurposeTo temp Heater output Operation When the unit is in operation How to Set the Auto Restart FunctionWhen the unit is standby Not operating How to Turn Off Filter Indicator Power Failure During Timer OperationWhen the system is on stand-by not operating When the system is operatingParts Name of Remote Controller Display Automatic operation Do not allow the drain hose to become slack Safety CautionsFor the rear left and left piping Accessory and Installation Parts Optional Parts, Accessories and ToolsOptional Installation Parts New tools for R410A Installation/Servicing ToolsChanges in the product and components New tools for R410A Applicable to R22 model ChangesRemote controller Installation LocationDrilling and Mounting Installation Plate Mounting the installation plateWiring Connection How to connect the connecting cable When the installation plate is directly mounted on the wallElectrical Work Anchor bolt Projection 15mm or lessHow to remove the drain hose How to remove the drain capDie-cutting front panel slit Changing drain hoseHow to attach the drain hose How to attach the drain capCase of bottom right or bottom left piping Left-hand connection with pipingShield pipe Drain hose Inside the room Indoor Unit InstallationDrainage Strong wind Precautions for adding refrigerantRefrigerant Piping Connection Flaring Draining the WaterProjection margin in flaring a Unit mm Flaring size B Unit mmTo secure To tighten Tightening ConnectionUse a vacuum pump Wiring Connection Packed Valve handling precautionsStripping length of connecting cable Model RASTest Operation Troubleshooting Procedure Precautions when handling the new inverter 3DV InverterControl circuitry has an uninsulated construction JAVP-E series insulated typeDischarging method Do not lay the circuit board assembly flatSensor leads Inverter coverConfirmation of Power Voltage Confirmation of Power SupplyFirst Confirmation Operation Which is not a Trouble Program OperationJudgment by Flashing LED of Indoor Unit Primary JudgmentWhich lamp does flash? Check Block display Description for self-diagnosis CodeHow to Use Remote Controller in Service Mode Self-Diagnosis by Remote Controller Check CodePush START/STOP button to release the service mode Push on or OFF buttonJudgment and action Block distinctionAir Block Cause of operation RemarksBlock Cause of operation Indoor Unit Including Remote Controller Judgment of Trouble by Every SymptomConfirmation procedure Primary checkOnly the indoor motor fan does not operate Cause Inspection procedureTroubleshooting for remote controller Check procedure Select phenomena described below Wiring Failure Interconnecting and Serial Signal WireOutdoor unit does not operate Terminal block at indoor side1C1E Check Code 1C Miswiring in indoor/outdoor units and 1ECheck procedure How to Check Whether the Air Purifier is Good or Not TroubleshootingConduction check of micro-switch Primary checkDiagnosis/Process flowchart Contents Summary How to Diagnose Trouble in Outdoor UnitSummarized Inner Diagnosis of Inverter Assembly How to Check the P.C. Board Indoor Unit How to Check Simply the Main PartsOperating precautions Inspection proceduresProcedure Check points Causes Check proceduresOPERATION, TIMER, Filter Cool11-9-2. P.C. Board Layout Sensor characteristic tableOutdoor Unit Part name Checking procedureIndoor Unit Other Parts Tester rod Resistance value Good product Checking Method for Each PartCase that product is good Cause Symptom12-1 Indoor Unit Part name Procedures RemarksHow to assemble the front panel How to assemble the high voltage generator How to assemble the electric parts box Slide the horizontal Remove the two screws used to secure Bearing base Pull out here Drain pipe Board layout Part name Procedure RemarksMicrocomputer Attachment No. Part name Procedure Remarks Common 1. DetachmentNo. Part name Procedure Remarks STIT-4X8MSZN 100Some cases Other parts from the control board assembly Disconnect the leads and connectors connected to101 Board baseSide cabinet left 102103 Detachment Handling precaution104 Detail a Arrow D Detail C 105Detail B Detail a Arrow DPart name 106Parts name Qty Remarks MCC-5009-04 107MCC-5009 237 240108 Part Description109 402 407, 408 403 406 404 405 410401110 111 402 411, 412 403 406 404 405 410401112 13, 16, 19 14, 15, 17 20, 21, 23, 24113 114 13, 16, 19 14, 15, 17 20, 21, 23, 24 CORD, HEATER, Ass’y115 116 13-3. P.C. Board Layout117 Model 118Corresponding Toshiba Carrier Corporation

RAS-10SAVP-E, RAS-B10SKVP-E, RAS-B13SKVP-E specifications

Toshiba has established itself as a leader in the HVAC market, known for its innovative technologies and reliable performance. Among its range of air conditioning units, the Toshiba RAS-B10SKVP-E, RAS-10SAVP-E, and RAS-B13SKVP-E models stand out for their efficiency and advanced features.

The Toshiba RAS-B10SKVP-E is designed for optimal cooling and heating efficiency, making it an ideal choice for small to medium-sized rooms. One of its main features is the Super Hi-M-PAM inverter technology, which enhances energy savings by continuously adjusting the compressor speed to match the cooling demand. This results in lower energy consumption while maintaining a stable temperature. Additionally, the unit boasts a 4-in-1 operation mode that allows users to select cooling, heating, dehumidification, or ventilating modes, ensuring maximum comfort at all times.

Similarly, the RAS-10SAVP-E model incorporates advanced features such as an eco-friendly refrigerant, R32, which has a lower Global Warming Potential (GWP) compared to traditional refrigerants. This model is equipped with a high-efficiency filter that captures dust and allergens, ensuring cleaner air quality. The sleek design allows for easy integration into various interior styles, while its quiet operation makes it a preferred choice for residential environments.

The RAS-B13SKVP-E model takes performance to the next level with a robust cooling capacity, designed for larger spaces. This model utilizes Toshiba's unique DC Hybrid Inverter technology, which not only enhances cooling efficiency but also facilitates faster temperature control. A notable characteristic of this unit is its wide-angle air distribution system, which allows for even airflow throughout the room, enhancing comfort.

In addition to these features, all three models are equipped with smart controls that enable users to operate their air conditioning systems remotely via mobile devices. This connectivity adds convenience and ensures that users can manage their indoor climate at their fingertips. They also come with user-friendly interfaces and programmable timers, allowing for personalized comfort settings.

In conclusion, the Toshiba RAS-B10SKVP-E, RAS-10SAVP-E, and RAS-B13SKVP-E air conditioning units combine energy efficiency, innovative technology, and user-friendly features to deliver exceptional indoor comfort. With their advanced technologies, these models are ideal choices for anyone seeking reliable and effective climate control solutions.