Toshiba RAS-B10SKVP-E, RAS-B13SKVP-E Setting the clean operation cancel, Indoor P.C. board

Page 43

Item

 

Operation flow and applicable data, etc.

 

Description

 

 

 

 

16. Clean operation

Setting the clean operation cancel

 

NOTE:

cancel

 

 

 

 

Once J201 is added, the [RESET]

 

 

 

 

 

 

 

Add J201 of the indoor P.C. board assembly.

 

button on the unit is designated for

 

 

 

CLEAN OPERATION (Set/Cancel),

 

 

* This cancels the auto restart function.

 

 

 

 

therefore the [RESET] button can

 

 

 

 

 

 

 

 

 

 

not be used for the selection (Set/

 

 

 

 

 

Cancel) of AUTO RESTART

 

 

 

 

 

 

Hold down the [RESET] button on the indoor unit

 

function (Page 50).

 

 

 

 

 

 

for at least 3 seconds but not more than 10 seconds.

 

 

 

 

 

 

 

* J201 will be near the MCU so

 

 

 

 

 

 

 

 

 

take steps to ensure that it will

 

 

 

 

 

not be exposed to excessive of

 

 

The indoor unit’s buzzer emits three beeps.

 

 

 

heat.

 

 

 

 

 

Also take care to avoid solder

 

 

 

 

 

 

 

 

 

bridging with the surrounding

 

 

 

 

 

components.

 

 

 

 

This completes the clean operation cancel setting.

Setting the clean operation

Hold down the [RESET] button on the indoor unit for at least 3 seconds but not more than 10 seconds.

The indoor unit’s buzzer emits three beeps, and the OPERATION indicator flashes at 5 Hz intervals.

This completes the clean operation setting.

Indoor P.C. board

J201

C24

– 43 –

Image 43
Contents AIR-CONDITIONER Contents For general public use New Refrigerant Air Conditioner InstallationFor Reference Specifications SpecificationsRAS-10SKVP-ND RAS-13SKVP-ND RAS-16SKVP-ND Current Operation Characteristic CurveHeating CoolingCapacity ratio % 110 100 Capacity Variation Ratio According to TemperatureCooling HeatingCopper Pipes Safety During Installation/ServicingRefrigerant Piping Installation Piping Materials and Joints UsedProcessing of Piping Materials Flare processing procedures and precautionsJoints Diameter Flare tool for R410A Conventional flare toolClutch type Wing nut type Flare tool for R22 Conventional flare toolNm kgfcm Flare Connecting Procedures and PrecautionsWrenches available on the market Required Tools ToolsGeneral tools Conventional tools can be used Recharging of Refrigerant 1 Configuration of refrigerant chargingMaterials for Brazing Brazing of PipesFlux Never use gas other than Nitrogen gas BrazingIndoor Unit Construction ViewsWH-H05JE Detailed B leg part Mounting dimensions of anchor boltOutdoor Unit Detailed a leg partMCC-5009 BoardRAS-10SAVP-ND, RAS-13SAVP-ND, RAS-16SAVP-ND MCC-5045CAM-MD12TF DC12V Parts name Type SpecificationsMP24Z3N Parts name Model name RatingCAM-B22YGTF-3 Refrigerant Cycle DiagramOperation Data Cooling Sleep Mode Operation START/STOP Operation Mode SelectionAUTO, COOL, DRY, Heat For Indoor Unit Outdoor Unit Inverter AssemblyMCC5009 P.C.B  Operations followed to Outline of Air Conditioner ControlRole of indoor unit controller Role of outdoor unit controllerAuto Restart Function Filter IndicatorRemote Controller and Its Fuctions Operation DescriptionON/OFF Remote controllerIndoor unit Outdoor unitDRY operation Auto operationIndication Fan speed SymbolsIndoor fan air flow rate Cold draft preventive control Operation flow and applicable data, etc DescriptionHeating operation Indication Fan speedTable is selected Outdoor temperature ToMode, by the conditions Outdoor fan shownRemote controller Indoor unit Exchanger detects condensation temperature When temperature of the indoorExchanger detects evaporation temperature and controls Compressor speed so that temperature of the heatDefrost operation Operation flow and applicable data, etcCase of operation stop ConditionAir direction Louver position in cooling operationLouver position in heating operation Louver position in dry operationMode SleepCooling operation Temporary When keeping Reset button pushed forIf the filter lamp goes on, push Reset Push Reset button againOperation PurposeSH control Release control PMV open degree control Stop by Setup value Power OFFClean operation Indoor P.C. board Setting the clean operation cancelSetting the clean operation This completes the clean operation settingSetting the unit Setting the remote controllerHeat operation Indoor control P.C. board At shipment Purpose8C Heat operation -ND model only Outdoor To reduce noise, Reset buttonWith Quiet control/Non-select method Purpose On 8˚C Heat StartDuring stop of air conditioner During operation of air conditionerCompressor speed control Refer to 4. Capacity control Basic fan controlIndoor fan control Auto TSCTo temp Heater output Operation Base plate cord heater control PurposeOFF When the unit is standby Not operating How to Set the Auto Restart FunctionWhen the unit is in operation When the system is operating Power Failure During Timer OperationHow to Turn Off Filter Indicator When the system is on stand-by not operatingParts Name of Remote Controller Display Automatic operation For the rear left and left piping Safety CautionsDo not allow the drain hose to become slack Optional Installation Parts Optional Parts, Accessories and ToolsAccessory and Installation Parts New tools for R410A Applicable to R22 model Changes Installation/Servicing ToolsNew tools for R410A Changes in the product and componentsMounting the installation plate Installation LocationRemote controller Drilling and Mounting Installation PlateAnchor bolt Projection 15mm or less When the installation plate is directly mounted on the wallWiring Connection How to connect the connecting cable Electrical WorkChanging drain hose How to remove the drain capHow to remove the drain hose Die-cutting front panel slitLeft-hand connection with piping How to attach the drain capHow to attach the drain hose Case of bottom right or bottom left pipingDrainage Indoor Unit InstallationShield pipe Drain hose Inside the room Strong wind Precautions for adding refrigerantFlaring size B Unit mm Draining the WaterRefrigerant Piping Connection Flaring Projection margin in flaring a Unit mmUse a vacuum pump Tightening ConnectionTo secure To tighten Model RAS Packed Valve handling precautionsWiring Connection Stripping length of connecting cableTest Operation JAVP-E series insulated type Precautions when handling the new inverter 3DV InverterTroubleshooting Procedure Control circuitry has an uninsulated constructionInverter cover Do not lay the circuit board assembly flatDischarging method Sensor leadsOperation Which is not a Trouble Program Operation Confirmation of Power SupplyConfirmation of Power Voltage First ConfirmationCheck Block display Description for self-diagnosis Code Primary JudgmentJudgment by Flashing LED of Indoor Unit Which lamp does flash?Push on or OFF button Self-Diagnosis by Remote Controller Check CodeHow to Use Remote Controller in Service Mode Push START/STOP button to release the service modeRemarks Block distinctionJudgment and action Air Block Cause of operationBlock Cause of operation Primary check Judgment of Trouble by Every SymptomIndoor Unit Including Remote Controller Confirmation procedureOnly the indoor motor fan does not operate Cause Inspection procedureTroubleshooting for remote controller Terminal block at indoor side Wiring Failure Interconnecting and Serial Signal WireCheck procedure Select phenomena described below Outdoor unit does not operateCheck procedure Check Code 1C Miswiring in indoor/outdoor units and 1E1C1E Primary check TroubleshootingHow to Check Whether the Air Purifier is Good or Not Conduction check of micro-switchSummarized Inner Diagnosis of Inverter Assembly How to Diagnose Trouble in Outdoor UnitDiagnosis/Process flowchart Contents Summary Inspection procedures How to Check Simply the Main PartsHow to Check the P.C. Board Indoor Unit Operating precautionsCool Check proceduresProcedure Check points Causes OPERATION, TIMER, Filter11-9-2. P.C. Board Layout Sensor characteristic tableIndoor Unit Other Parts Part name Checking procedureOutdoor Unit Case that product is good Checking Method for Each PartTester rod Resistance value Good product Cause Symptom12-1 Indoor Unit Part name Procedures RemarksHow to assemble the front panel How to assemble the high voltage generator How to assemble the electric parts box Slide the horizontal Remove the two screws used to secure Bearing base Pull out here Drain pipe Microcomputer Part name Procedure RemarksBoard layout Attachment No. Part name Procedure Remarks Common 1. DetachmentNo. Part name Procedure Remarks Some cases 100STIT-4X8MSZN Board base Disconnect the leads and connectors connected toOther parts from the control board assembly 101Side cabinet left 102103 104 Handling precautionDetachment Detail a Arrow D 105Detail a Arrow D Detail C Detail BParts name Qty Remarks 106Part name MCC-5009 107MCC-5009-04 Part Description 240237 108109 402 407, 408 403 406 404 405 410401110 111 402 411, 412 403 406 404 405 410401112 13, 16, 19 14, 15, 17 20, 21, 23, 24113 114 13, 16, 19 14, 15, 17 20, 21, 23, 24 CORD, HEATER, Ass’y115 116 13-3. P.C. Board Layout117 Corresponding 118Model Toshiba Carrier Corporation

RAS-10SAVP-E, RAS-B10SKVP-E, RAS-B13SKVP-E specifications

Toshiba has established itself as a leader in the HVAC market, known for its innovative technologies and reliable performance. Among its range of air conditioning units, the Toshiba RAS-B10SKVP-E, RAS-10SAVP-E, and RAS-B13SKVP-E models stand out for their efficiency and advanced features.

The Toshiba RAS-B10SKVP-E is designed for optimal cooling and heating efficiency, making it an ideal choice for small to medium-sized rooms. One of its main features is the Super Hi-M-PAM inverter technology, which enhances energy savings by continuously adjusting the compressor speed to match the cooling demand. This results in lower energy consumption while maintaining a stable temperature. Additionally, the unit boasts a 4-in-1 operation mode that allows users to select cooling, heating, dehumidification, or ventilating modes, ensuring maximum comfort at all times.

Similarly, the RAS-10SAVP-E model incorporates advanced features such as an eco-friendly refrigerant, R32, which has a lower Global Warming Potential (GWP) compared to traditional refrigerants. This model is equipped with a high-efficiency filter that captures dust and allergens, ensuring cleaner air quality. The sleek design allows for easy integration into various interior styles, while its quiet operation makes it a preferred choice for residential environments.

The RAS-B13SKVP-E model takes performance to the next level with a robust cooling capacity, designed for larger spaces. This model utilizes Toshiba's unique DC Hybrid Inverter technology, which not only enhances cooling efficiency but also facilitates faster temperature control. A notable characteristic of this unit is its wide-angle air distribution system, which allows for even airflow throughout the room, enhancing comfort.

In addition to these features, all three models are equipped with smart controls that enable users to operate their air conditioning systems remotely via mobile devices. This connectivity adds convenience and ensures that users can manage their indoor climate at their fingertips. They also come with user-friendly interfaces and programmable timers, allowing for personalized comfort settings.

In conclusion, the Toshiba RAS-B10SKVP-E, RAS-10SAVP-E, and RAS-B13SKVP-E air conditioning units combine energy efficiency, innovative technology, and user-friendly features to deliver exceptional indoor comfort. With their advanced technologies, these models are ideal choices for anyone seeking reliable and effective climate control solutions.