Toshiba RAS-10SAVP-E, RAS-B13SKVP-E, RAS-B10SKVP-E service manual Block Cause of operation

Page 74

Block distinction

Operation of diagnosis function

Check

 

Check

 

Air

 

 

Judgment and action

Block

Cause of operation

conditioner

Remarks

 

code

code

 

 

 

 

status

 

 

 

 

 

 

 

 

 

 

 

Outdoor P.C.

 

Inverter over-current

All off

Displayed when

Even if trying operation again, all

 

board

 

protective circuit

 

error is detected.

operations stop immediately. :

 

 

 

operates. (Short time)

 

 

Replace P.C. board.

 

 

 

Position-detect circuit

All off

Displayed when

1.

Even if connecting lead wire of

 

 

 

error or short-circuit

 

error is detected.

 

compressor is removed, position-

 

 

 

between windings of

 

 

 

detect circuit error occurred. :

 

 

 

compressor

 

 

 

Replace P.C. board.

 

 

 

 

 

 

2.

Measure resistance between

 

 

 

 

 

 

 

wires of compressor, and

 

 

 

 

 

 

 

perform short-circuit. :

 

 

 

 

 

 

 

Replace compressor.

 

 

 

Current-detect circuit

All off

Displayed when

Even if trying operation again, all

 

 

 

error

 

error is detected.

operations stop immediately. :

 

 

 

 

 

 

Replace P.C. board.

 

 

 

Being out of place,

All off

Displayed when

1.

Check sensors (TE, TS).

 

 

 

disconnection or short-

 

error is detected.

2.

Check P.C. board.

 

 

 

circuit of the outdoor

 

 

 

 

 

 

 

heat exchanger sensor

 

 

 

 

 

 

 

(TE) or suction temp.

 

 

 

 

 

 

 

sensor (Ts)

 

 

 

 

 

 

 

Disconnection or short-

All off

Displayed when

1.

Check discharge temp. sensor

 

 

 

circuit of discharge temp.

 

error is detected.

 

(TD).

 

 

 

sensor

 

 

2.

Check P.C. board

 

 

 

Outdoor fan drive system

All off

Displayed when

Position-detect error, over-current

 

 

 

error

 

error is detected.

protective operation of outdoor fan

 

 

 

 

 

 

drive system, fan lock, etc. :

 

 

 

 

 

 

Replace P.C. board or fan motor.

 

Not

 

Being out of place,

Operation

 

1.

Check outdoor temp. sensor

 

displayed

 

disconnection or short-

continues

——

 

(TO).

 

 

 

circuit of the outdoor

 

2.

Check P.C. board.

 

 

 

 

 

 

 

 

temp. sensor (TO)

 

 

 

 

 

Outdoor P.C.

 

Compressor drive output

All off

Displayed when

When 20 seconds passed after

 

board

 

error, Compressor error

 

error is detected.

start-up, position-detect circuit error

 

 

 

(lock, missing, etc.),

 

 

occurred. : Replace compressor.

 

 

 

Break down

 

 

Trouble on P.M.V.

 

Others

 

Return serial signal has

Operation

Flashes when

1.

Repeat Start and Stop with

 

(including

 

been sent when

continues

trouble is detected

 

interval of approx. 10 to 40

 

compressor)

 

operation started, but it

 

on return serial

 

minutes. (Code is not displayed

 

 

 

is not sent from halfway.

 

signal, and normal

 

during operation.)

 

 

 

1) Compressor thermo.

 

status when signal

 

Supply gas.

 

 

 

operation

 

is reset.

 

(Check also gas leak).

 

 

 

Gas shortage

 

 

2.

Unit operates normally during

 

 

 

Gas leak

 

 

 

check.

 

 

 

2) Instantaneous power

 

 

 

If return serial signal does not

 

 

 

failure

 

 

 

stop between indoor terminal

 

 

 

 

 

 

 

block 2 and 3, replace inverter

 

 

 

 

 

 

 

P.C. board.

 

 

 

 

 

 

 

If signal stops between indoor

 

 

 

 

 

 

 

terminal block 2 and 3, replace

 

 

 

 

 

 

 

indoor P.C. board.

 

 

 

Compressor does not

All off

Displayed when

1.

Trouble on compressor

 

 

 

rotate.

 

error is detected.

2.

Trouble on wiring of compressor

 

 

 

(Current protective

 

 

 

(Missed phase)

 

 

 

circuit does not operate

 

 

 

 

 

 

 

when a specified time

 

 

 

 

 

 

 

passed after compressor

 

 

 

 

 

 

 

had been activated.)

 

 

 

 

 

 

 

Discharge temp.

All off

Displayed when

1.

Check dischage temp. sensor

 

 

 

exceeded 117°C

 

error is detected.

 

(TD).

 

 

 

 

 

 

2.

Gas leakage

 

 

 

 

 

 

3.

Trouble on P.M.V.

 

 

 

Break down of

All off

Displayed when

1.

Check power voltage.

 

 

 

compressor

 

error is detected.

 

(220–230–240 V +10%)

 

 

 

 

 

 

2.

Overload operation of refrigera-

 

 

 

 

 

 

 

tion cycle

 

 

 

 

 

 

 

Check installation condition

 

 

 

 

 

 

 

(Short-circuit of outdoor diffuser).

 

 

 

4-way valve inverse error

Operation

 

1.

Check 4-way valve operation.

 

 

 

(TC sensor value

continues

——

 

 

 

 

 

lowered during heating

 

 

 

 

 

 

 

 

 

 

 

 

 

operation.)

 

 

 

 

– 74 –

Image 74
Contents AIR-CONDITIONER Contents New Refrigerant Air Conditioner Installation For general public useFor Reference Specifications SpecificationsRAS-10SKVP-ND RAS-13SKVP-ND RAS-16SKVP-ND Cooling Operation Characteristic CurveHeating CurrentHeating Capacity Variation Ratio According to TemperatureCooling Capacity ratio % 110 100Piping Materials and Joints Used Safety During Installation/ServicingRefrigerant Piping Installation Copper PipesJoints Flare processing procedures and precautionsProcessing of Piping Materials Flare tool for R22 Conventional flare tool Flare tool for R410A Conventional flare toolClutch type Wing nut type DiameterWrenches available on the market Flare Connecting Procedures and PrecautionsNm kgfcm General tools Conventional tools can be used ToolsRequired Tools 1 Configuration of refrigerant charging Recharging of RefrigerantFlux Brazing of PipesMaterials for Brazing Brazing Never use gas other than Nitrogen gasConstruction Views Indoor UnitWH-H05JE Detailed a leg part Mounting dimensions of anchor boltOutdoor Unit Detailed B leg partBoard MCC-5009MCC-5045 RAS-10SAVP-ND, RAS-13SAVP-ND, RAS-16SAVP-NDParts name Model name Rating Parts name Type SpecificationsMP24Z3N CAM-MD12TF DC12VRefrigerant Cycle Diagram CAM-B22YGTF-3Operation Data Cooling AUTO, COOL, DRY, Heat Operation START/STOP Operation Mode SelectionSleep Mode MCC5009 P.C.B Outdoor Unit Inverter AssemblyFor Indoor Unit Role of outdoor unit controller Outline of Air Conditioner ControlRole of indoor unit controller  Operations followed toOperation Description Filter IndicatorRemote Controller and Its Fuctions Auto Restart FunctionOutdoor unit Remote controllerIndoor unit ON/OFFAuto operation DRY operationIndoor fan air flow rate SymbolsIndication Fan speed Indication Fan speed Operation flow and applicable data, etc DescriptionHeating operation Cold draft preventive controlOutdoor fan shown Outdoor temperature ToMode, by the conditions Table is selectedRemote controller Indoor unit Compressor speed so that temperature of the heat When temperature of the indoorExchanger detects evaporation temperature and controls Exchanger detects condensation temperatureCondition Operation flow and applicable data, etcCase of operation stop Defrost operationLouver position in dry operation Louver position in cooling operationLouver position in heating operation Air directionCooling operation SleepMode Push Reset button again When keeping Reset button pushed forIf the filter lamp goes on, push Reset TemporaryPurpose OperationSetup value Power OFF SH control Release control PMV open degree control Stop byClean operation This completes the clean operation setting Setting the clean operation cancelSetting the clean operation Indoor P.C. boardSetting the remote controller Setting the unit8C Heat operation -ND model only Indoor control P.C. board At shipment PurposeHeat operation With Quiet control/Non-select method Purpose To reduce noise, Reset buttonOutdoor During operation of air conditioner StartDuring stop of air conditioner On 8˚C HeatAuto TSC Basic fan controlIndoor fan control Compressor speed control Refer to 4. Capacity controlOFF Base plate cord heater control PurposeTo temp Heater output Operation When the unit is in operation How to Set the Auto Restart FunctionWhen the unit is standby Not operating When the system is on stand-by not operating Power Failure During Timer OperationHow to Turn Off Filter Indicator When the system is operatingParts Name of Remote Controller Display Automatic operation Do not allow the drain hose to become slack Safety CautionsFor the rear left and left piping Accessory and Installation Parts Optional Parts, Accessories and ToolsOptional Installation Parts Changes in the product and components Installation/Servicing ToolsNew tools for R410A New tools for R410A Applicable to R22 model ChangesDrilling and Mounting Installation Plate Installation LocationRemote controller Mounting the installation plateElectrical Work When the installation plate is directly mounted on the wallWiring Connection How to connect the connecting cable Anchor bolt Projection 15mm or lessDie-cutting front panel slit How to remove the drain capHow to remove the drain hose Changing drain hoseCase of bottom right or bottom left piping How to attach the drain capHow to attach the drain hose Left-hand connection with pipingShield pipe Drain hose Inside the room Indoor Unit InstallationDrainage Precautions for adding refrigerant Strong windProjection margin in flaring a Unit mm Draining the WaterRefrigerant Piping Connection Flaring Flaring size B Unit mmTo secure To tighten Tightening ConnectionUse a vacuum pump Stripping length of connecting cable Packed Valve handling precautionsWiring Connection Model RASTest Operation Control circuitry has an uninsulated construction Precautions when handling the new inverter 3DV InverterTroubleshooting Procedure JAVP-E series insulated typeSensor leads Do not lay the circuit board assembly flatDischarging method Inverter coverFirst Confirmation Confirmation of Power SupplyConfirmation of Power Voltage Operation Which is not a Trouble Program OperationWhich lamp does flash? Primary JudgmentJudgment by Flashing LED of Indoor Unit Check Block display Description for self-diagnosis CodePush START/STOP button to release the service mode Self-Diagnosis by Remote Controller Check CodeHow to Use Remote Controller in Service Mode Push on or OFF buttonAir Block Cause of operation Block distinctionJudgment and action RemarksBlock Cause of operation Confirmation procedure Judgment of Trouble by Every SymptomIndoor Unit Including Remote Controller Primary checkOnly the indoor motor fan does not operate Inspection procedure CauseTroubleshooting for remote controller Outdoor unit does not operate Wiring Failure Interconnecting and Serial Signal WireCheck procedure Select phenomena described below Terminal block at indoor side1C1E Check Code 1C Miswiring in indoor/outdoor units and 1ECheck procedure Conduction check of micro-switch TroubleshootingHow to Check Whether the Air Purifier is Good or Not Primary checkDiagnosis/Process flowchart Contents Summary How to Diagnose Trouble in Outdoor UnitSummarized Inner Diagnosis of Inverter Assembly Operating precautions How to Check Simply the Main PartsHow to Check the P.C. Board Indoor Unit Inspection proceduresOPERATION, TIMER, Filter Check proceduresProcedure Check points Causes CoolSensor characteristic table 11-9-2. P.C. Board LayoutOutdoor Unit Part name Checking procedureIndoor Unit Other Parts Tester rod Resistance value Good product Checking Method for Each PartCase that product is good Symptom CausePart name Procedures Remarks 12-1 Indoor UnitHow to assemble the front panel How to assemble the high voltage generator How to assemble the electric parts box Slide the horizontal Remove the two screws used to secure Bearing base Pull out here Drain pipe Board layout Part name Procedure RemarksMicrocomputer No. Part name Procedure Remarks Common 1. Detachment AttachmentNo. Part name Procedure Remarks STIT-4X8MSZN 100Some cases 101 Disconnect the leads and connectors connected toOther parts from the control board assembly Board base102 Side cabinet left103 Detachment Handling precaution104 Detail B 105Detail a Arrow D Detail C Detail a Arrow DPart name 106Parts name Qty Remarks MCC-5009-04 107MCC-5009 108 240237 Part Description402 407, 408 403 406 404 405 410401 109110 402 411, 412 403 406 404 405 410401 11113, 16, 19 14, 15, 17 20, 21, 23, 24 112113 13, 16, 19 14, 15, 17 20, 21, 23, 24 CORD, HEATER, Ass’y 114115 13-3. P.C. Board Layout 116117 Model 118Corresponding Toshiba Carrier Corporation

RAS-10SAVP-E, RAS-B10SKVP-E, RAS-B13SKVP-E specifications

Toshiba has established itself as a leader in the HVAC market, known for its innovative technologies and reliable performance. Among its range of air conditioning units, the Toshiba RAS-B10SKVP-E, RAS-10SAVP-E, and RAS-B13SKVP-E models stand out for their efficiency and advanced features.

The Toshiba RAS-B10SKVP-E is designed for optimal cooling and heating efficiency, making it an ideal choice for small to medium-sized rooms. One of its main features is the Super Hi-M-PAM inverter technology, which enhances energy savings by continuously adjusting the compressor speed to match the cooling demand. This results in lower energy consumption while maintaining a stable temperature. Additionally, the unit boasts a 4-in-1 operation mode that allows users to select cooling, heating, dehumidification, or ventilating modes, ensuring maximum comfort at all times.

Similarly, the RAS-10SAVP-E model incorporates advanced features such as an eco-friendly refrigerant, R32, which has a lower Global Warming Potential (GWP) compared to traditional refrigerants. This model is equipped with a high-efficiency filter that captures dust and allergens, ensuring cleaner air quality. The sleek design allows for easy integration into various interior styles, while its quiet operation makes it a preferred choice for residential environments.

The RAS-B13SKVP-E model takes performance to the next level with a robust cooling capacity, designed for larger spaces. This model utilizes Toshiba's unique DC Hybrid Inverter technology, which not only enhances cooling efficiency but also facilitates faster temperature control. A notable characteristic of this unit is its wide-angle air distribution system, which allows for even airflow throughout the room, enhancing comfort.

In addition to these features, all three models are equipped with smart controls that enable users to operate their air conditioning systems remotely via mobile devices. This connectivity adds convenience and ensures that users can manage their indoor climate at their fingertips. They also come with user-friendly interfaces and programmable timers, allowing for personalized comfort settings.

In conclusion, the Toshiba RAS-B10SKVP-E, RAS-10SAVP-E, and RAS-B13SKVP-E air conditioning units combine energy efficiency, innovative technology, and user-friendly features to deliver exceptional indoor comfort. With their advanced technologies, these models are ideal choices for anyone seeking reliable and effective climate control solutions.