9. TROUBLESHOOTING
9-1. Summary of Troubleshooting
9-1-1. Before troubleshooting
(1)Required tools/instruments
•e and d screwdrivers, spanners, radio cutting pliers, nippers, etc.
•Tester, thermometer, pressure gauge, etc.
(2)Confirmation points before check
1The following operations are normal.
a)Compressor does not operate.
•Is not
•Does not thermostat turn off?
•Does not timer operate during fan operation?
•Is not outside
b)Indoor fan does not rotate.
•Does not cool air discharge preventive control work in heating operation?
c)Outdoor fan does not rotate or air volume changes.
•Does not
•Does not outside
•Is not defrost operation performed?
d)ON/OFF operation cannot be performed from remote control.
•Is not forced operation performed?
•Is not the control operation performed from outside/remote side?
2Did you return the cabling to the initial positions?
3Are connecting cables between indoor unit and receiving unit correct?
9-1-2. Troubleshooting procedure
When a trouble occurred, check the parts along with the following procedure.
Trouble | → | Confirmation of check code by service mode |
|
|
|
→Check defective position and parts.
NOTE :
For cause of a trouble, power conditions or malfunc- tion/erroneous diagnosis of microcomputer due to outer noise is considered except the items to be checked. If there is any noise source, change the cables of the signal line to shield cables.
9-1-3. Outline of Judgment
A primary judgment to detect cause of error exists on the indoor unit or outdoor unit is performed in the following procedure.
<Judgment by flashing display on the indoor unit display part>
The indoor unit monitors operating status of the air conditioner, and if a protective circuit works, contents of the
Table
Remote | Block display | Contents of | Check code | |
control code | ||||
|
|
| ||
|
|
|
| |
Operation lamp display flashes. (1Hz) | Power failure (In power ON) | |||
|
|
|
| |
00 | Operation lamp display flashes. (5Hz) | Indoor P.C. board | 0b to 0F, 11, 12, b5, b6 | |
|
|
|
| |
01 | Operation/timer lamp displays flash. (5Hz) | 04 | ||
|
|
|
| |
02 | Operation/defrost lamp displays flash. (5Hz) | Outdoor P.C. board | 14 to 19, 1A, 1C | |
|
|
|
| |
03 | Operation/timer/defrost lamp displays flash. (5Hz) | Cycle system, etc. | 1d, 1E, 1F, 21 | |
|
|
|
| |
1b, 8b | ||||
|
|
|
|
– 21 –