8-5. Freeze preventive control (Low temperature release)

The cooling operation (including Dry operation) is performed as follows based on the detected temperature of Tc sensor or Tcj sensor.

When [J] zone is detected for T1 minutes (Following figure), the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 2 minutes while operation is performed in [J] zone.

T1

Normal

1 minute

In [K] zone, time counting is interrupted and the operation is held.

When [I] zone is detected, the timer is cleared and the operation returns to the normal operation.

(° C)

 

 

 

7

 

I

A

 

6

 

 

K

 

 

 

5

 

 

J

 

 

 

 

 

Fig. 8-5-1

In heating operation, the freeze-preventive control works if 4-way valve is not exchanged and the condition is satisfied.

Remarks:

Tcj : Indoor heat exchanger sensor temperature

8-6. High-temp release control

The heating operation is performed as follows based on the detected temperature of Tc sensor.

When [M] zone is detected, the commanded frequency is decreased from the real operation frequency. After then the commanded frequency changes every 30 seconds while operation is performed in [M] zone.

In [N] zone, the commanded frequency is held.

When [L] zone is detected, the commanded frequency is returned to the original value by approx. 6Hz every 60 seconds.

8-7. Louver control

(1)Vertical air flow louver

Position of veritcal air flow louver is automatically controlled according to the operation mode. Besides, position of vertical air flow louver can be arbitrarily set by pressing [FIX] button.

The louver position which is set by [FIX] button is stored in the microcomputer, and the louver is automatically set at the stored position for the next operation.

(2)Swing

If [SWING] button is pressed when the indoor unit is in operation, the vertical air flow louver starts swinging. When [SWING] button is pressed, it stops swinging.

8-8. Filter sign display

(1)The operation time of the indoor fan is calculated, the filter lamp (Orange) on the display part of the main unit goes on when the specified time (240H) has passed. When a wired remote controller is connected, the filter reset signal is sent to the remote controller, and also it is displayed on LCD of the wired remote control.

(2)When the filter reset signal has been received from the wired remote control after [FILTER] lamp has gone on or when the filter check button (Temporary button) is pushed, time of the calculation timer is cleared. In this case, the measurement time is reset if the specified time has passed, and display on LCD and the display on the main unit disappear.

Remarks:

[FILTER] goes on

Tc (° C)

55 A

M

52N

48 B

L

Fig. 8-6-1

– 18 –

Image 20
Contents AIR-CONDITIONER Contents Specifications Operation characteristic curve Cooling Heating CurrentConstruction Views Indoor UnitSystematic Refrigerating Cycle Diagram RAV-SM562XT-E / RAV-SM802XT-EWiring Diagram Color IdentificationSpecification of Electrical Parts Parts name Type SpecificationsSafety During Installation/Servicing Refrigerant Piping InstallationRefrigerant R410A Piping materials and joints usedProcessing of piping materials 1 Thicknesses of annealed copper pipes Thickness mmOuter diameter mm R410A R22 Flare tool for R410A Conventional flare tool Clutch type Wing nut typeFlare tool for R22 Conventional flare tool Width Diameter·m kgf·cm ·m kgf·mGeneral tools Conventional tools can be used ToolsRequired tools 1 Configuration of refrigerant charging Recharging of RefrigerantBrazing of Pipes Characteristics required for flux Types of flux Noncorrosive fluxActivated flux Filler FluxControl Block Diagram PRE DEFWhen power supply is reset Operation mode selectionAir volume control Operation DescriptionCool air discharge preventive control 1 Cold draft preventing controlFreeze preventive control Low temperature release High-temp release controlLouver control Filter sign displayHow to set auto restart function Auto Restart FunctionOperation MotionsHow to cancel auto restart function Power failure during timer operationHow to turn off filter check lamp Filter Check LampTroubleshooting Summary of TroubleshootingBefore troubleshooting Troubleshooting procedureSelf-Diagnosis by Remote Control Check Code How to use remote control in service modeJudgement and action No display in the setting at shipment Operation TA sensor TC, TCJ sensor Caracteristics-1 Caracteristics-2 Caracteristics-320 TE, TO, TS sensor TD sensor Caracteristics-4Remove the Panel arms from the Front panel How to install the Air inlet grilleDetachments Open 3 Cap screws and remove the screws How to remove the Drain pan Assembly Pan assembly Refrigeration How to remove the Refrigeration assemblyFan motor Part name Procedures RemarksHow to remove the Multiblade fan Exploded Views and Parts List Indoor Unit E-Parts AssyAIR-GRILLE