APC ACPCW40-150, ACPDX21-86 Fluid Cooled Glycol 40% Continued, PG211, PG311, PG452, PG612, PG862

Models: ACPCW40-150 ACPDX21-86

1 92
Download 92 pages 27.88 Kb
Page 57
Image 57

Fluid Cooled (Glycol 40%) Continued

PG211

PG311

PG452

PG612

PG862

 

Cabinet Size 1

Cabinet Size 2

Cabinet Size 3

Cabinet Size 4

Cabinet Size 5

 

 

 

 

 

 

Fan Information

 

 

 

 

 

Number of Fans

1

1

2

2

3

Air Flow - M³/hr (CFM)

7493 (4,410)

10007 (5,890)

14000 (8,240)

20116 (11,840)

24007 (14,130)

External Static Pressure - Pa (in WC)

50 (0.2)

50 (0.2)

50 (0.2)

50 (0.2)

50 (0.2)

Sound Power Level - dBA

75.4

79.2

77.4

83.2

81.5

Total Fan Power Consumption - kW (hp)

1.7 (2.3)

2.0 (2.7)

3.1 (4.2)

6.1 (8.2)

6.2 (8.3)

Condenser Data (40% Glycol inlet temperature

40.5°C (105°F),

outlet temperature

46.1°C (115°F)

 

 

Total Heat Rejection (THR) - kW (BTU/hr)

26.5 (90,300)

39.1 (133,100)

58.4 (199,400)

77.3 (263,800)

113.3 (386,600)

Flow rate - L/m (GPM)

58.3 (15.4)

78.4 (20.7)

123.4 (32.6)

160.1 (42.3)

246.8 (65.2)

Total pressure drop water side - kPa (ft)

78.6 (26.3)

70.3 (23.5)

73.6 (24.6)

88.5 (29.6)

124.1 (41.5)

Valve size - mm (in)

20 (0.75)

25 (1.0)

32 (1.25)

32 (1.25)

40 (1.50)

Connection Sizes

 

 

 

 

 

Condenser In/Out - mm (in)

28 (1 1/8)

35 (1 3/8)

35 (1 3/8)

35 (1 3/8)

42 (1 5/8)

Humidifier Supply Line - mm (in)

6 (1/4)

6 (1/4)

6 (1/4)

6 (1/4)

6 (1/4)

Condensate Drain Line - mm OD (in ID)

21 (3/4)

21 (3/4)

21 (3/4)

21 (3/4)

21 (3/4)

Humidification – Solid State Electrode, Canister

 

 

 

 

 

Flush Cycle

Automatic

Automatic

Automatic

Automatic

Automatic

kg/hr (lb/hr)

8.0 (17.6)

8.0 (17.6)

15.0 (33.1)

15.0 (33.1

15.0 (33.1)

Electric Reheat – Equally Loaded Three (3) phase

 

 

 

 

 

Capacity - kW (BTU/hr) Includes Motor Heat

 

 

 

 

 

400 V

12 (40982.4)

18 (61473.6)

18 (61473.6)

27 (92210.4)

27 (92210.4)

Number of Stages

2

3

3

3

3

Downflow Filters - mm

 

 

Quantities

 

 

700 x 508 x 47 G4

1

N/A

N/A

N/A

N/A

1050 x 453 x 47 G4

N/A

2

1

1

1

1050 x 398 x 47 G4

N/A

1

3

4

5

Upflow Filters - mm

 

 

Quantities

 

 

700 x 340 x 47 G4

N/A

1

N/A

1

1

700 x 332 x 47 G4

N/A

1

N/A

N/A

1

700 x 502 x 47 G4

N/A

1

1

1

1

700 x 508 x 47 G4

N/A

N/A

1

1

2

700 x 516 x 47 G4

1

N/A

1

N/A

N/A

Physical Data

 

 

 

 

 

Weight - kg (lb)

356 (785)

460 (1014)

564 (1243)

693 (1528)

825 (1819)

Height - mm (in)

1980 (77.95)

1980 (77.95)

1980 (77.95)

1980 (77.95)

1980 (77.95)

Width - mm (in)

1000 (39.37)

1400 (55.11)

1750 (68.90)

2150 (84.65)

2550 (100.39)

Depth - mm (in)

890 (35)

890 (35)

890 (35)

890 (35)

890 (35)

InRoom Precision AC Tech Data Manual

53

Page 57
Image 57
APC ACPCW40-150, ACPDX21-86 manual Fluid Cooled Glycol 40% Continued, PG211, PG311, PG452, PG612, PG862, Cabinet Size