Optional Features
Humidifier
The humidifier utilizes a pure steam generator specifically designed for precision environmental close control. The pure steam eliminates contaminating mineral deposits, potentially harmful bacteria, white dust, and excessive humidity. The humidifier requires little scheduled maintenance. The humidifier is proportionally controlled to meet the humidification demands of the conditioned space. Humidifier canisters are replaceable.
Electric Reheat
Electric reheat elements are low watt density, wired for
Spot Water Detector
The
Smoke Detector
The
Hot Gas Bypass Valve
The hot gas bypass valve (HGBV) adjusts the flow of compressor discharge gas to the evaporator coil at low load conditions to protect the coil from freezing and the compressor from excessive cycling. 60 Hz cooling units use a mechanical HGBV.
50 Hz cooling units use an electronically controlled HGBV. On 50 Hz cooling units, the HGBV option requires the analog extension board EAIO.
Cable Leak Detector (60 Hz only)
The optional 6 m (20 ft) leak detection sensing cable (APC part number ACAC75105) is available for 60 Hz cooling units only. The cable leak detector is placed on the floor or subfloor around all possible leak sources. If water or other conductive liquids contact the cable anywhere along its length, the master controller visually and audibly announces the leak.
Floorstand
The floorstand raises the unit above the subfloor to match the height of the raised floor. Heights are available from 254 mm (10 in) to 610 mm (24 in) in 76.2 mm (3 in) increments and are adjustable +/– 38.1 mm (1.5 in). Adjustment is provided by threaded pedestals. Vibration- absorbing pads are included. The floorstand, pedestal, and pads ship loose. In areas where earthquakes are a concern, seismic floorstands are available in 305 mm (12 in), 457 mm (18 in), and 610 mm (24 in) heights.
Plenums
Discharge plenums are available on upflow configurations. This application is recommended in rooms where raised floors are not available for air distribution. Discharge air should be ducted down cold aisles.
Base Plenum
Insulated base plenums are available for downflow cooling units where raised floors are not available for air distribution. Four
Water Regulating Valves
Water and fluid cooled systems utilize two- or
Extreme Low Temperature Kit (Direct Expansion units only)
Extreme Low Temperature Kits for air cooled condensers are available for operation below
4 | InRoom Precision AC Tech Data Manual |