APC ACPCW40-150 Air Cooled DX System – 60Hz, PA211, PA311, PA452, PA612, PA862, Cabinet Size

Models: ACPCW40-150 ACPDX21-86

1 92
Download 92 pages 27.88 Kb
Page 29
Image 29
Air Cooled (DX) System – 60Hz

Air Cooled (DX) System – 60Hz

Air Cooled

PA211

 

PA311

PA452

 

PA612

 

PA862

 

Cabinet Size 1

Cabinet Size 2

Cabinet Size 3

Cabinet Size 4

Cabinet Size 5

 

 

 

 

 

 

 

 

 

 

26.7°C DB, 19.4°C WB (80°F DB, 67°F WB)

50% RH

 

 

 

 

 

 

 

 

Total - kW (BTU/hr)

19.8 (67,450)

29.9

(102,000)

44.2

(151,000)

55.2

(188,290)

84.9

(290,000)

Sensible - kW (BTU/hr)

19.8 (67,450)

29.9

(102,000)

41.3

(141,000)

55.2 (188,290)

75.4

(257,000)

23.9°C DB, 16.9°C WB (75°F DB, 62.5°F WB) 50% RH

 

 

 

 

 

 

 

 

Total - kW (BTU/hr)

18.1 (61,940)

27.6

(94,000)

40.5

(138,000)

50.8

(173,470)

78.8

(269,000)

Sensible - kW (BTU/hr) *

18.1 (61,940)

27.6

(94,000)

40.5

(138,000)

50.8

(173,470)

72.8

(249,000)

23.9°C DB, 16.1°C WB (75°F DB, 61°F WB)

45% RH

 

 

 

 

 

 

 

 

Total - kW (BTU/hr)

18.1 (61,940)

27.6

(94,000)

40.5

(138,000)

50.8

(173,470)

77.2

(264,000)

Sensible - kW (BTU/hr)

18.1 (61,940)

27.6

(94,000)

40.5

(138,000)

50.8

(173,470)

77.2

(264,000)

22.2°C DB, 15.5°C WB (72°F DB, 60°F WB)

50% RH

 

 

 

 

 

 

 

 

Total - kW (BTU/hr)

17.1 (58,330)

26.4

(90,000)

38.7

(132,000)

48.2

(164,635)

75.1

(256,000)

Sensible - kW (BTU/hr)

17.1 (58,330)

26.4

(90,000)

38.7

(132,000)

48.2

(164,635)

71.0

(242,000)

22.2°C DB, 14.8°C WB (72°F DB, 58.6°F WB) 45% RH

 

 

 

 

 

 

 

 

Total - kW (BTU/hr)

17.1 (58,330)

26.4

(90,000)

38.6

(132,000)

48.2

(164,635)

75.1

(256,000)

Sensible - kW (BTU/hr)

17.1 (58,330)

26.4

(90,000)

38.6

(132,000)

48.2

(164,635)

71.0

(242,000)

21.1°C DB, 14.0°C WB (70°F DB, 58.5°F WB) 50% RH

 

 

 

 

 

 

 

 

Total - kW (BTU/hr)

16.7 (57,095)

25.6

(87,000)

37.4

(128,000)

47.1

(160,740)

74.4

(253,840)

Sensible - kW (BTU/hr)

16.7 (57,095)

25.6

(87,000)

37.4

(128,000)

47.1

(160,740)

74.4

(253,840)

21.1°C DB, 14.0°C WB (70°F DB, 57.2°F WB) 45% RH

 

 

 

 

 

 

 

 

Total - kW (BTU/hr)

16.7 (57,095)

25.6

(87,000)

37.4

(128,000)

47.1

(160,740)

74.4

(253,840)

Sensible - kW (BTU/hr)

16.7 (57,095)

25.6

(87,000)

37.4

(128,000)

47.1

(160,740)

74.4

(253,840)

Condensing temperature for all above conditions: 52°C (125° F)

 

 

 

 

 

 

 

Refrigerant type for all models: R-407C

 

 

 

 

 

 

 

 

 

Refrigerant Charge per Circuit - kg (lbs)

2.8 (6.17)

3.9 (8.6)

4.4 (9.7)

3.9 (8.6)

4.6 (10.1)

Compressor Information – COP** (ARI***

Conditions): 7.2°C

(45°F) Evaporating, 54°C (130°F) Condensing

 

 

Number of compressors

1

1

 

2

 

2

 

2

 

COP

3.0

3.0

 

3.0

 

3.0

 

3.1

 

Evaporator Coil

 

 

 

 

 

 

 

 

 

Face Area - m² (ft²)

0.77 (8.32)

1.17

(12.63)

1.46

(15.72)

1.86

(20.02)

2.22

(23.90)

Rows Deep

4

4

 

4

 

4

 

5

 

Face Velocity - m/min (ft/min)

125 (410)

104 (342)

117 (383)

130 (428)

141 (461)

* Nominal Rating Point

 

 

 

 

 

 

 

 

 

** Coefficient of Performance

 

 

 

 

 

 

 

 

 

*** Air Conditioning and Refrigeration Institute