InRoom Standard Condensers - 60 Hz

InRoom Standard Condensers - 60 Hz

InRoom Remote Outdoor Condenser Data, 95°F ambient, 120°F condensation - R407C

 

InRoom Cabinet Size

1

2

3

4

5

Total Heat Rejection

96.219

165.496

225.435

279.262

380.436

(THR) BTU/h

 

 

 

 

 

CFM

8,394

19,325

18,609

17,604

27,963

Fan Diameter - in

19.69

24.80

24.80

24.80

24.80

Voltage Options

 

 

 

 

 

208-230/3/60

ACCD76000

ACCD76004

ACCD76008

ACCD76012

ACCD76016

Number of Fans

2

2

2

2

3

Fan RPM (Qty)

1490

1585(1), 1500(1)

1585(1), 1500(1)

1585(1), 1500(1)

1585(2), 1500(1)

Motor HP (Qty)

1.23 Hp(2)

3.58(1), 3.85(1)

3.58(1), 3.85(1)

3.58(1), 3.85(1)

3.58(2), 3.85(1)

Electrical Data

 

 

 

 

 

FLA

8.6

19.7

19.7

19.7

29.1

MCA

9.8

22.1

22.1

22.1

31.5

MFS

15

30

30

30

40

460-480/3/60

ACCD76010

ACCD76005

ACCD76009

ACCD76013

ACCD76017

Number of Fans

2

2

2

2

3

Fan RPM (Qty)

1450(1), 1570(1)1650(1), 1500(1)

1650(1), 1500(1)

1650(1), 1500(1)

1650(2), 1500(1)

Motor HP (Qty)

1.34(1), 1.64(1)

3.90(1), 3.85(1)

3.90(1), 3.85(1)

3.90(1), 3.85(1)

3.90(2), 3.85(1)

Electrical Data

 

 

 

 

 

FLA

3.9

9.5

9.5

9.5

14.57

MCA

4.3

10.7

10.7

10.7

15.85

MFS

15

15

15

15

20

575-600/3/60

ACCD76022

ACCD76023

ACCD76024

ACCD76025

ACCD76026

Number of Fans

2

2

2

2

3

Fan RPM (Qty)

1450(1), 1570(1)1650(1), 1500(1)

1650(1), 1500(1)

1650(1), 1500(1)

1650(2), 1500(1)

Motor HP (Qty)

1.34(1), 1.64(1)

3.90(1), 3.85(1)

3.90(1), 3.85(1)

3.90(1), 3.85(1)

3.90(2), 3.85(1)

Electrical Data

 

 

 

 

 

FLA

3.4

8.0

8.0

8.0

12.3

MCA

37

9.0

9.0

9.0

13.4

MFS

15.0

15.0

15.0

15.0

15.0

Refrigerant Connections*

 

 

 

 

 

Hot Gas Line - in

1 1/8 OD

1 1/8 OD

1 3/8 OD

1 3/8 OD

1 5/8 OD

Liquid Line - in

7/8 OD

7/8 OD

1 1/8 OD

1 1/8 OD

1 3/8 OD

Physical Data**

 

 

 

 

 

Dimensions -HxWxD in

35.5x32.75x76

48x108.5x48.25

48x108.5x48.25

48x108.5x48.25

48x155.5x48.25

Approximate Weight - lb.

240

455

495

555

835