The InRoom Fluid Cooled (Glycol) System with Chilled Water System is a combination of a factory sealed glycol system and a chilled water system and contains two separate cooling coils. The controller microprocessor manages the systems to allow the glycol system to operate as standby to the chilled water system or vice versa, giving the added security of back-up cooling to the computer room.

Chilled Water

InRoom Chilled Water systems are available in a packaged fan-coil design. Room air is recirculated through the cooling coil, which transfers the heat load directly into the chilled water ring main. Water flow rate is regulated by a 2- or 3-way valve controlled by the controller microprocessor. Cooling towers are used as a source of heat rejection and can be used to serve multiple indoor units. Towers utilizing outdoor air require water treatment.

The system is used with a cooling tower or other source of water.

Factory sealed and tested system.

The need for field refrigerant piping is eliminated.

na2843a

Fluid Cooled (Glycol) System with

Chilled Water Cooling System

na2844a

Chilled Water Cooling System

InRoom Precision AC Tech Data Manual