Transporting and Storage

Delivery of the unit

The cooling unit is mounted on a pallet, wrapped in plastic film, and surrounded with cardboard for added protection. The unit must be transported in the upright position.

PAXXX models are delivered with 1 kg. (2.2 lb) refrigerant charge. PGXXX models are delivered with a complete refrigerant charge.

Check the unit against the shipping invoice to verify contents. Check the unit for damage. In case of damage, first notify the carrier of a claim.

Moving the unit

Use a forklift to move the cooling unit while it is still packaged on the pallet. Make sure the unit is upright when moving it. Do not move the unit on rollers and do not move it on a forklift without a pallet.

The cooling unit can be moved with lifting devices and ropes. The ropes must be fixed to the pallet and the upper edges of the unit must be protected to avoid damage.

Storage

If the unit is placed into storage before being installed, make sure to protect it from damage and corrosion.

Make sure that the water connections have protective covers. If the unit will be stored for longer than two months, the piping should be filled with nitrogen.

The temperature of the storage area should not exceed 42°C (107.6°F).

The unit should not be stored where it will be exposed to direct sunlight.

Do not leave the unit outside or in any storage area that allows the unit to be exposed to the elements.

Store the unit in the original packaging when possible to avoid damage and corrosion.