Toshiba MMY-MAP1404HT8-E „ Selection of pipe size, Capacity code of indoor and outdoor units

Page 12

21-EN

– 11 –

22-EN

SMMS-iInstallation Manual

Coupling size of brazed pipe

 

 

 

 

 

Connected section

 

 

 

 

 

 

External size

 

Internal size

 

 

 

 

 

 

 

 

 

K

 

 

 

 

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ØC

 

 

ØF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Unit: mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connected section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Standard outer dia.

External size

 

Internal size

Min. depth of

 

Min. thickness

of connected

 

Standard outer dia.

 

 

insertion

Oval value

of coupling

copper pipe

 

(Allowable difference)

 

 

 

 

 

 

 

 

 

 

 

C

 

F

K

G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6.35

 

 

 

 

6.35 (±0.03)

 

 

 

 

6.45 (+0-0..0204)

7

6

0.06 or less

0.50

9.52

 

 

 

 

9.52 (±0.03)

 

 

 

 

9.62 (+0-0..0204)

8

7

0.08 or less

0.60

12.70

 

 

 

 

12.70 (±0.03)

 

 

 

 

12.81 (+0-0..0204)

9

8

0.10 or less

0.70

15.88

 

 

 

 

15.88 (±0.03)

 

 

 

 

16.00 (+0-0..0204)

9

8

0.13 or less

0.80

19.05

 

 

 

 

19.05 (±0.03)

 

 

 

 

19.19 (+0-0..0303)

11

10

0.15 or less

0.80

22.22

 

 

 

 

22.22 (±0.03)

 

 

 

 

22.36 (+0.03-0.03)

11

10

0.16 or less

0.82

28.58

 

 

 

 

28.58 (±0.04)

 

 

 

 

28.75 (+0-0..0206)

13

12

0.20 or less

1.00

34.92

 

 

 

 

34.90 (±0.04)

 

 

 

 

35.11 (+0-0..0404)

14

13

0.25 or less

1.20

38.10

 

 

 

 

38.10 (±0.05)

 

 

 

 

38.31 (+0-0..0208)

15

14

0.27 or less

1.26

41.28

 

 

 

 

41.28 (±0.05)

 

 

 

 

41.50 (+0-0..0208)

15

14

0.28 or less

1.35

„Selection of pipe size

Capacity code of indoor and outdoor units

Selection of pipe material

For the indoor unit, the capacity code is decided at each capacity rank. (Table 1)

The capacity codes of the outdoor units are decided at each capacity rank. The maximum number of connectable indoor units and the total value of capacity codes of the indoor units are also decided. (Table 2)

NOTE

Compared with the capacity code of the outdoor unit, the total value of capacity codes of the connectable indoor units differs based on the height difference between the indoor units.

When the height difference between the indoor units is 15m or less: Up to 135% of the capacity code (Equivalent to HP) of the outdoor unit (Equivalent to HP) of the outdoor unit

When the height difference between the indoor units is over 15m: Up to 105% of the capacity code

SMMS-i

 

 

 

 

 

 

 

 

 

 

Installation Manual

Table 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

Capacity code

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

capacity rank

 

Equivalent to HP

 

Equivalent to

 

 

 

 

 

 

 

 

 

 

 

capacity

 

 

 

 

 

 

007

0.8

 

 

2.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

009

1

 

 

2.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

012

1.25

 

 

3.6

 

 

 

 

 

 

 

015

1.7

 

 

4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

018

2

 

 

5.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

2.5

 

 

7.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

027

3

 

 

8

 

 

 

 

 

 

 

030

3.2

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

4

 

 

11.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

5

 

 

14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

056

6

 

 

16

 

 

 

 

 

 

 

072

8

 

 

22.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

096

10

 

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

 

Capacity code

 

No. of

 

Outdoor unit

Capacity code

No. of

 

 

 

 

 

 

 

 

model name

 

 

 

model name

 

Equivalent to

Equivalent to

 

indoor

 

(High Efficiency

Equivalent to

Equivalent to

indoor

 

(Standard model)

 

HP

 

capacity

 

units

 

model)

HP

capacity

units

 

MMY-MAP0804

 

8

 

22.4

 

13

 

 

MMY-MAP1004

 

10

 

28

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-MAP1204

 

12

 

33.5

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-MAP1404

 

14

 

40

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-MAP1604

 

16

 

45

 

27

MMY-AP1624

16

45

27

 

MMY-AP1814

 

18

 

50.4

 

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP2014

 

20

 

56

 

33

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP2214

 

22

 

61.5

 

37

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP2414

 

24

 

68

 

40

MMY-AP2424

24

68

40

 

MMY-AP2614

 

26

 

73

 

43

MMY-AP2624

26

73

43

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP2814

 

28

 

78.5

 

47

MMY-AP2824

28

78.5

47

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP3014

 

30

 

85

 

48

MMY-AP3024

30

85

48

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP3214

 

32

 

90

 

48

MMY-AP3224

32

90

48

 

MMY-AP3414

 

34

 

96

 

48

MMY-AP3424

34

96

48

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP3614

 

36

 

101

 

48

MMY-AP3624

36

101

48

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP3814

 

38

 

106.5

 

48

MMY-AP3824

38

106.5

48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP4014

 

40

 

112

 

48

 

MMY-AP4024

40

112

48

 

MMY-AP4214

 

42

 

118

 

48

 

MMY-AP4224

42

118

48

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP4414

 

44

 

123

 

48

MMY-AP4424

44

123

48

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP4614

 

46

 

130

 

48

MMY-AP4624

46

130

48

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-AP4814

 

48

 

135

 

48

MMY-AP4824

48

135

48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* For combination of the outdoor units, refer to “Combination of outdoor units”.

Image 12
Contents Not accessible to the general public Non accessibile a clienti genericiFor commercial use Vente interdite au grand publicContents Precautions for Safety Selection of installation locationInstallation „ Warning Indications on the Air Conditioner UnitElectrical wiring SMMS-i Installation Manual RelocationNew Refrigerant Air Conditioner Installation To Disconnect the Appliance from Main Power SupplyAccessory Parts Installation of NEW Refrigerant AIR ConditionerExplanation of symbols „ Required Tools and Cautions on handlingSelection of Installation Place „ Installation spaceAvoid the following places Carrying in the Outdoor Unit Combination of outdoor unitsSide Front /BackInstallation of the Outdoor Unit „ Weight centre and weightWeight centre of an outdoor unit Installation in a snowfall areaLiquid piping Gas pipingAt a level position Model typeWhen drawing pipes downward SMMS-iInstallation ManualRefrigerant Piping „ Connection of refrigerant pipeExtruding margin of copper pipe with flare tools a Unit mm Pipe connection method of valve at the gas side Example„ Selection of pipe size Capacity code of indoor and outdoor unitsCoupling size of brazed pipe Selection of pipe materialPipe size for connecting piping between outdoor units Type Gas side Liquid sideCapacity Size of main piping26-EN „ Airtightness test System restrictionPacked valve details Able to detect a serious leakage„ Vacuum drying „ Adding refrigerant Calculation of additional refrigerant charge amountCharging of refrigerant MAP080 MAP100 MAP120 MAP140 MAP160 Type„ Finishing after connecting pipes „ Full opening of the valve„ F-GAS label „ Heat insulation for pipeElectric Wiring „ Power supply specificationsPower wiring selection Pipe holding bracket„ Specifications for communication wiring Design of communication wiringSummary of communication wiring Model Phase and frequency Nominal Voltage„ Connection of power wires and communication wires Group control through a Remote ControllerCommunication wiring between outdoor units L5 Remote controller wiring L6, L7Power supply wire connection Communication wire connectionSMMS-i Installation Manual Screw size and tightening torque Address Setting „ Automatic address setting„ Regulation of high frequency wave Address setting procedure Remains lit on the display, the setting is Set the central control addressBoard of the header outdoor unit indicates 7-segment display indicates„ Manual address setting using the remote controller Wiring example of 2 refrigerant linesOutdoor units setting manually Installation Manual SMMS-i Installation Manual Relay connector connectionAn indoor unit using Remote controller„Confirming the indoor unit Addresses and the positionAddress using a remote Wired remote controller„Changing the indoor unit Controller„Resetting the address Resetting to the factoryDefault address undecided Set the addresses again after finishing the clearanceWhen executing a test run using a Remote controller 10TEST RUN„ Before test run „ Methods of test runCorrective trial Push and hold SW04 for more than 2 secondsInterface PC board 11TROUBLESHOOTING Rotary switch setting valueSegment display and check code SW01 SW02 SW03 Indication12MACHINE Card and Logbook „ Machine card„ Logbook Describe the following items on the machine cardStandards for minimum room volume are as follows EH99871699 Check of Concentration Limit

MMY-MAP0804HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP0804HT8Z-E, MMY-MAP1204HT8Z-E specifications

The Toshiba MMY-MAP0804HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP0804HT8-E, and MMY-MAP1604HT8-E are part of Toshiba's advanced air conditioning line-up, designed for both residential and commercial applications. These models are engineered to offer high efficiency, comfort, and reliability, making them an excellent choice for modern HVAC solutions.

One of the standout features of these models is their high Seasonal Energy Efficiency Ratio (SEER), which indicates their superior energy performance. They are built to reduce energy consumption while providing optimal cooling and heating capabilities. This is particularly beneficial for users looking to lower their energy bills without sacrificing comfort.

In terms of technology, Toshiba incorporates inverter technology in these air conditioning units. The inverter system adjusts the compressor's speed according to the cooling demand, ensuring consistent temperatures and enhanced energy savings. This feature is especially useful during peak usage periods, as it minimizes energy spikes associated with traditional on/off systems.

Additionally, the MMY-MAP series includes sophisticated air filtration systems that improve indoor air quality. These filters capture dust, allergens, and other pollutants, creating a healthier living or working environment. The units also come equipped with a quiet operation mode, allowing them to function with minimal noise – a crucial aspect for residential settings and quiet commercial spaces.

These models boast a sleek and compact design, making them easy to install in various configurations. Their aesthetic appeal ensures they blend seamlessly with any interior decor. Furthermore, they are built to withstand diverse environmental conditions, with robust materials that ensure durability and longevity.

User-friendly controls are another hallmark of the Toshiba MMY-MAP series. Many of these models support smart technology, allowing for remote operation via smartphones or tablets. This capability enhances convenience, enabling users to monitor and adjust settings in real-time.

In summary, the Toshiba MMY-MAP0804HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP0804HT8-E, and MMY-MAP1604HT8-E models epitomize efficiency and comfort. With their energy-saving features, advanced inverter technology, effective air filtration, and smart connectivity, these air conditioning units are designed to meet the demands of modern users, ensuring a comfortable and healthy indoor environment all year round.