When using the piping cover

Piping/wiring panel

Drawing-out sideward

Close the opening with the pipe cover.

Drawing-out

frontwardDrawing-out downward

Pipe holding bracket

Attach pipe holding brackets following the table below.

Diameter of pipe (mm)

Interval

Ø15.9 - Ø19.1

2m

 

 

Ø22.2 - Ø41.3

3m

Installation Manual

When not using the piping cover

Piping/wiring panel

Drawing-out sideward

Fill silicon or putty into the periphery of the pipes.

Drawing-out

frontwardDrawing-out downward

SMMS-i

Installation Manual

8 ELECTRIC WIRING

WARNING

The appliance shall be installed in accordance with national wiring regulations.

Capacity shortages of the power circuit or an incomplete installation may cause an electric shock or fire.

CAUTION

Perform wiring of power supply complying with the rules and regulations of the local electric company.

Do not connect 380V - 415V power to the terminal blocks for control cables (U1, U2, U3, U4, U5, U6); otherwise, the unit may break down.

Be sure that electric wiring does not come into contact with high-temperature parts of piping; otherwise, the coating of cables may melt and cause an accident.

After connecting wires to the terminal block, take off the traps and fix the wires with cord clamps.

Follow the same structure for both the control wiring and refrigerate piping.

Do not conduct power to indoor units until vacuuming of the refrigerant pipes has finished.

For the wiring of power to indoor units and that between indoor and outdoor units, follow the instructions in the installation manual of each indoor unit.

„Power supply specifications

Do not bridge the power between outdoor units through the equipped terminal blocks (L1, L2, L3, N).

Power supply for outdoor units

NO GOOD

Power wiring selection

Standard model

MCA: Minimum Circuit Amps

MOCP: Maximum Overcurrent Protection (Amps)

Model

Power Supply

 

MCA

MOCP

 

 

 

 

 

(A)

(A)

 

 

Phase and frequency

 

Nominal Voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MMY-MAP0804*

 

 

 

23.5

32

 

 

MMY-MAP1004*

 

 

 

25.5

32

 

 

MMY-MAP1204*

3N~ 50Hz

 

380-400-415V

28.5

40

 

 

MMY-MAP1404*

 

 

 

33.2

40

 

 

MMY-MAP1604*

 

 

 

36.5

50

 

 

MMY-AP1814*

 

 

 

49.0

63

 

 

MMY-AP2014*

 

 

 

51.0

63

 

 

MMY-AP2214*

 

 

 

54.0

63

 

 

MMY-AP2414*

3N~ 50Hz

 

380-400-415V

57.0

63

 

 

MMY-AP2614*

 

62.0

80

 

 

 

 

 

 

 

MMY-AP2814*

 

 

 

65.0

80

 

EN

MMY-AP3014*

 

 

 

69.7

80

 

MMY-AP3214*

 

 

 

73.0

100

 

 

 

 

 

 

 

 

 

 

35-EN

– 18 –

36-EN

 

 

Image 19
Contents Vente interdite au grand public Not accessible to the general publicNon accessibile a clienti generici For commercial useContents „ Warning Indications on the Air Conditioner Unit Precautions for SafetySelection of installation location InstallationTo Disconnect the Appliance from Main Power Supply Electrical wiringSMMS-i Installation Manual Relocation New Refrigerant Air Conditioner Installation„ Required Tools and Cautions on handling Accessory PartsInstallation of NEW Refrigerant AIR Conditioner Explanation of symbols„ Installation space Selection of Installation PlaceAvoid the following places Front /Back Carrying in the Outdoor UnitCombination of outdoor units SideInstallation in a snowfall area Installation of the Outdoor Unit„ Weight centre and weight Weight centre of an outdoor unitModel type Liquid pipingGas piping At a level position„ Connection of refrigerant pipe When drawing pipes downwardSMMS-iInstallation Manual Refrigerant PipingPipe connection method of valve at the gas side Example Extruding margin of copper pipe with flare tools a Unit mmSelection of pipe material „ Selection of pipe sizeCapacity code of indoor and outdoor units Coupling size of brazed pipeSize of main piping Pipe size for connecting piping between outdoor unitsType Gas side Liquid side Capacity26-EN Able to detect a serious leakage „ Airtightness testSystem restriction Packed valve details„ Vacuum drying MAP080 MAP100 MAP120 MAP140 MAP160 Type „ Adding refrigerantCalculation of additional refrigerant charge amount Charging of refrigerant„ Heat insulation for pipe „ Finishing after connecting pipes„ Full opening of the valve „ F-GAS labelPipe holding bracket Electric Wiring„ Power supply specifications Power wiring selectionModel Phase and frequency Nominal Voltage „ Specifications for communication wiringDesign of communication wiring Summary of communication wiringRemote controller wiring L6, L7 „ Connection of power wires and communication wiresGroup control through a Remote Controller Communication wiring between outdoor units L5Communication wire connection Power supply wire connectionSMMS-i Installation Manual Screw size and tightening torque „ Automatic address setting Address Setting„ Regulation of high frequency wave Address setting procedure 7-segment display indicates Remains lit on the display, the setting isSet the central control address Board of the header outdoor unit indicatesSMMS-i Installation Manual Relay connector connection „ Manual address setting using the remote controllerWiring example of 2 refrigerant lines Outdoor units setting manually Installation ManualAddresses and the position An indoor unit usingRemote controller „Confirming the indoor unitController Address using a remoteWired remote controller „Changing the indoor unitSet the addresses again after finishing the clearance „Resetting the addressResetting to the factory Default address undecided„ Methods of test run When executing a test run using a Remote controller10TEST RUN „ Before test runPush and hold SW04 for more than 2 seconds Corrective trialInterface PC board SW01 SW02 SW03 Indication 11TROUBLESHOOTINGRotary switch setting value Segment display and check codeDescribe the following items on the machine card 12MACHINE Card and Logbook„ Machine card „ LogbookEH99871699 Check of Concentration Limit Standards for minimum room volume are as follows

MMY-MAP0804HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP0804HT8Z-E, MMY-MAP1204HT8Z-E specifications

The Toshiba MMY-MAP0804HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP0804HT8-E, and MMY-MAP1604HT8-E are part of Toshiba's advanced air conditioning line-up, designed for both residential and commercial applications. These models are engineered to offer high efficiency, comfort, and reliability, making them an excellent choice for modern HVAC solutions.

One of the standout features of these models is their high Seasonal Energy Efficiency Ratio (SEER), which indicates their superior energy performance. They are built to reduce energy consumption while providing optimal cooling and heating capabilities. This is particularly beneficial for users looking to lower their energy bills without sacrificing comfort.

In terms of technology, Toshiba incorporates inverter technology in these air conditioning units. The inverter system adjusts the compressor's speed according to the cooling demand, ensuring consistent temperatures and enhanced energy savings. This feature is especially useful during peak usage periods, as it minimizes energy spikes associated with traditional on/off systems.

Additionally, the MMY-MAP series includes sophisticated air filtration systems that improve indoor air quality. These filters capture dust, allergens, and other pollutants, creating a healthier living or working environment. The units also come equipped with a quiet operation mode, allowing them to function with minimal noise – a crucial aspect for residential settings and quiet commercial spaces.

These models boast a sleek and compact design, making them easy to install in various configurations. Their aesthetic appeal ensures they blend seamlessly with any interior decor. Furthermore, they are built to withstand diverse environmental conditions, with robust materials that ensure durability and longevity.

User-friendly controls are another hallmark of the Toshiba MMY-MAP series. Many of these models support smart technology, allowing for remote operation via smartphones or tablets. This capability enhances convenience, enabling users to monitor and adjust settings in real-time.

In summary, the Toshiba MMY-MAP0804HT8Z-E, MMY-MAP1404HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP0804HT8-E, and MMY-MAP1604HT8-E models epitomize efficiency and comfort. With their energy-saving features, advanced inverter technology, effective air filtration, and smart connectivity, these air conditioning units are designed to meet the demands of modern users, ensuring a comfortable and healthy indoor environment all year round.